Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.5 CrAdmitted-Finance | ₹12.5 Cr | L1 | Admitted-Finance |
| 2 | L2₹12.9 CrAdmitted-Finance | ₹12.9 Cr | L2 | Admitted-Finance |
| 3 | L3₹15.4 CrAdmitted-Finance | ₹15.4 Cr | L3 | Admitted-Finance |
| 4 | Rejected-Technical | - | - | Rejected-Technical As Per Tender Committee Reccommendations |
| 5 | Rejected-Technical | - | - | Rejected-Technical As Per Tender Committee Reccommendations |
| Sl No | Description | Qty | Unit | Konstelec Engineers Pvt. Ltd. L3 | Shree Electricals and Engineers (India) Private Limited L2 | M/s SterlingElectro Enterprises.P.Ltd L1 |
|---|---|---|---|---|---|---|
| 1.00Supply, Delivery, Installation, Testing and Commissioning of the undermentioned items all in accordance with detailed technical specifications, drawing, etc. (Design & preparation of electrical system / layout and submission of "Good for Construction" drawing shall be in the scope of contractor. No separate charges shall be paid.) | ||||||
| 2.00PANELS & D.B.S | ||||||
| 3.00Providing Panel / Power distribution Boards suitable for 415V, 50Hz ,3ph 4 wire,Totally type tested as per IEC 61439-1&2, & Internal arc tested for 85kA for 0.4 Sec as per IEC 61641- V2, Seismic zone 5 compliance as per IEC 60068-3-3, IP 54,Form 4b ( Main Panels) Construction, supply dust and vermin proof floor/ wall mounting cubicle pattern with removable gland plates, copper bus bar, mounting frame, grouting made out of crca sheet, double door(for oudoor), duly powder coated painted as specified as follows. MCB with ‘c’ curve for lighting & power, d curve will be used for PC. | ||||||
| 4.00RETAIL Floor Panel For GF/FF Comprising of: 400Amp 4P Microprocessor Based open transition type Auto changeover Switch (ASCO 230 Series) - 1 No. Incoming – 400Amp TPN MCCB, 50kA, Microprocessor Over current, Short circuit and 3Ph 4 Wire Earth fault - 1No. Three Nos. Phase Indicating Lamps, Control fuses- Voltmeter with Selector switch –1 set, Ammeter with selector switch -1 set, Energy Meter with RS 485 port – 1 no, Copper Bus Bar 400 Amp. TPN , 50kA for 1 sec. - 1 Set, 40kA Class (B+C) Surge Supressor -1 No. Outgoing – 200 Amp 4P MCCB, 36kA with Microprocessor Over current, Short circuit -1No, 160 Amp. TPN MCCB, 36kA -2 Nos, 125 Amp. TPN MCCB, 36kA -2 Nos, All outgoing will be having Load manager with RS 485 port- 1 No, As per SLD provided. | ||||||
| 4.10 | Material | 2 | Nos. | 5,20,135 ₹10.4 L | 8,42,736 ₹16.9 L | 4,77,905 ₹9.6 L |
| 4.20 | Installation | 2 | Nos. | 15,300 ₹30,600 | 30,000 ₹60,000 | 16,968 ₹33,936 |
| 5.00Retail Panel-1 For GF/FF/SF Incoming –125 Amp. TPN MCCB, 25kA, with T/M release- 1 No. Three Nos. Phase Indicating Lamps, Load Manager with RS 485 port – 1 no. Outgoing – 63Amp TPN MCB- 6 Nos, all outgoing will be having Energy meter with RS 485 port, Copper Bus Bar 125 Amp. TPN, 25kA for 1 sec. - 1 Set, as per SLD provided. | ||||||
| 5.10 | Material | 2 | Nos. | 1,43,412 ₹2.9 L | 2,16,380 ₹4.3 L | 1,90,755 ₹3.8 L |
| 5.20 | Installation | 2 | Nos. | 7,650 ₹15,300 | 15,000 ₹30,000 | 11,312 ₹22,624 |
| 6.00Retail Panel-2 For GF/FF Incoming –125 Amp. TPN MCCB, 25kA, with T/M release- 1 No., Three Nos. Phase Indicating Lamps, Load Manager with RS 485 port – 1 no. Outgoing – 20Amp TPN MCB- 12 Nos, all outgoing will be having Energy meter with RS 485 port, Copper Bus Bar 125 Amp. TPN, 25kA for 1 sec. - 1 Set, as per SLD provided. | ||||||
Tender Value
₹15.6 Cr
Closing Date
1 Jun 2021, 3:00 pmClosed
Chief Mechanical Engineer
NIRMAN BHAVAN, 5TH FLOOR N. V. NAKHWA MARG, MAZGAON, MUMBAI 400 010
ELECTRICAL WORK FOR PROPOSED INTERNATIONAL CRUISE TERMINAL AT MUMBAI PORT TRUST
2021_MBPT_627878_1
MEED 06/2021
Open Tender
Electrical Works
240 days
Ballard Pier Extension, Mumbai Port Trust
Please refer Tender documents.
6 documents required · 6 mandatory
₹5,250
Yes
The Board of Trustees of Port of Mumbai
Exempted
Online.
28 Jun 2021
23 Apr 2021
2 Jun 2021
23 Apr 2021
1 Jun 2021
11 May 2021
23 Apr 2021 - 4 May 2021
4 May 2021
Amount
Supply, Delivery, Installation, Testing and Commissioning of the undermentioned items all in accordance with detailed technical specifications, drawing, etc. (Design & preparation of electrical system / layout and submission of "Good for Construction" drawing shall be in the scope of contractor. No separate charges shall be paid.)
PANELS & D.B.S
Providing Panel / Power distribution Boards suitable for 415V, 50Hz ,3ph 4 wire,Totally type tested as per IEC 61439-1&2, & Internal arc tested for 85kA for 0.4 Sec as per IEC 61641- V2, Seismic zone 5 compliance as per IEC 60068-3-3, IP 54,Form 4b ( Main Panels) Construction, supply dust and vermin proof floor/ wall mounting cubicle pattern with removable gland plates, copper bus bar, mounting frame, grouting made out of crca sheet, double door(for oudoor), duly powder coated painted as specified as follows. MCB with ‘c’ curve for lighting & power, d curve will be used for PC.
Material
Installation
Retail Panel-1 For GF/FF/SF Incoming –125 Amp. TPN MCCB, 25kA, with T/M release- 1 No. Three Nos. Phase Indicating Lamps, Load Manager with RS 485 port – 1 no. Outgoing – 63Amp TPN MCB- 6 Nos, all outgoing will be having Energy meter with RS 485 port, Copper Bus Bar 125 Amp. TPN, 25kA for 1 sec. - 1 Set, as per SLD provided.
Material
Installation
Retail Panel-2 For GF/FF Incoming –125 Amp. TPN MCCB, 25kA, with T/M release- 1 No., Three Nos. Phase Indicating Lamps, Load Manager with RS 485 port – 1 no. Outgoing – 20Amp TPN MCB- 12 Nos, all outgoing will be having Energy meter with RS 485 port, Copper Bus Bar 125 Amp. TPN, 25kA for 1 sec. - 1 Set, as per SLD provided.
Material
Installation
Material
Installation
Cruise Area MLDB GF/FF Incoming –250 Amp. TPN MCCB, 25kA, with T/M release- 1 No., Three Nos. Phase Indicating Lamps, Load Manager with RS 485 port – 1 no. Out going – 63Amp TPN MCB- 15 Nos, Copper Bus Bar 250 Amp. TPN , 25kA for 1 sec. - 1 Set. As per SLD provided.
Material
Installation
Cruise Area MPDB GF/FF Incoming –250 Amp. TPN MCCB, 25kA, with T/M release- 1 No. Three Nos. Phase Indicating Lamps, Load Manager with RS 485 port – 1 no. Outgoing – 63Amp TPN MCB- 15 Nos, Copper Bus Bar 250 Amp. TPN , 25kA for 1 sec. - 1 Set. As per SLD provided.
Material
Installation
Cruise Area MACDB GF/FF Incoming – 250 Amp. TPN MCCB *, 25kA, with T/M release- 1 No., Three Nos. Phase Indicating Lamps, Load Manager with RS 485 port – 1 no. Outgoing – 63Amp TPN MCB- 15 Nos, Copper Bus Bar 250 Amp. TPN , 25kA for 1 sec. - 1 Set. *This MCCBs is to be provided with Shunt trip arrangement for operation in case of fire alarm with 230/24 V Transformer and 24 V Pla relay. As per SLD provided.
Material
Installation
Cruise Area Retail Panel Comprising of: Incoming – 160 Amp. TPN MCCB, 25kA, with T/M release- 1 No., Three Nos. Phase Indicating Lamps, Load Manager with RS 485 port – 1 no. Outgoing – 20Amp DP MCB- 24 Nos, All outgoing will be having Energy meter with RS 485 port, Copper Bus Bar 160 Amp. TPN, 25kA for 1 sec. - 1 Set. As per SLD provided.
Material
Installation
External LTG Panel Comprising of: 160Amp 4P Microprocessor Based open transition type Auto changeover Switch (ASCO 230 Series) - 1 No. Incoming –160 Amp. TPN MCCB, 25kA, with T/M release- 1 No. Load Manager with RS 485 port – 1 no., 40kA Class (B+C) Surge Supressor -1 No. Out going – 63A TPN MCB - 28 Nos., Copper Bus Bar 160 Amp. TPN , 25kA for 1 sec. - 1 Set. As per SLD provided.
Material
Installation
Material
Installation
Material
Installation
Material
Installation
Emergency Lighting Panel Comprising of: Incoming – 160 Amp. 4P MCCB, 25kA, with T/M release- 1 No., Load Manager with RS 485 port – 1 no. , Three Nos. Phase Indicating Lamps, 20kA Class (C) Surge suppressor -1 No. Outgoing – 63 4P MCB - 28 Nos., Copper Bus Bar 160 Amp. 4P , 25kA for 1 sec. - 1 Set. As per SLD provided.
Material
Installation
UPS OUTPUT Panel Comprising of: Incoming –160 Amp. 4P MCCB, 25kA, with T/M release- 1 No., Load Manager with RS 485 port – 1 no., Three Nos. Phase Indicating Lamps, 20kA Class (C) Surge suppressor -1 No. Outgoing – 63 4P MCB - 28 Nos., Copper Bus Bar 160 Amp. 4P, 25kA for 1 sec. - 1 Set. As per SLD provided.
Material
Installation
Material
Installation
Material
Installation
Material
Installation
Outdoor Type ODU Panel for Vestibule 1 & 2 Providing Below Mentioned Configuration in IP 66 enclosure Panel, for free standing outdoor application, complete with MS Frameworks Legs Incoming – 250A TPN 36kA MCCB with O/C,S/C & E/F module - 1 No., Three Nos. Phase Indicating Lamps, Control fuses– 1 set. 250 Amps TPN Cu. Busbar 36kA for 1 sec. - 1 Set. Outgoing – 63 Amp TPN MCB - 13 Nos. As per SLD provided. Providing On/Off/ Trip status contact of incoming breakers for BMS * This MCCBs is to be provided with Shunt trip arrangement for operation in case of fire alarm with 230/24 V Transformer and 24 V Pla relay.
Material
Installation
Outdoor Tyep Smoke Exactor panel for Retail & Cruise Providing Below Mentioned Configuration in IP 66 enclosure Panel, for free standing outdoor application, complete with MS Frameworks Legs, 630Amp 4P Microprocessor Based open transition type Auto changeover Switch (ASCO 230 Series) – 1 No. Incoming –630A TPN 36kA MCCB with O/C,S/C & E/F module - 1 No., Three Nos. Phase Indicating Lamps, Control fuses– 1 set. 630 Amps TPN Cu. Busbar 36kA for 1 sec. - 1 Set. Outgoing – 63 Amp TPN MCB - 26 Nos. As per SLD provided. Providing On/Off/ Trip status contact of incoming breakers for BMS * This MCCBs is to be provided with Shunt trip arrangement for operation in case of fire alarm with 230/24 V Transformer and 24 V Pla relay.
Material
Installation
Lighting Distribution Board Comprising of : Incoming of 63 A TPN MCB - 1 No. Phase indicating lamps Outgoing – 40 Amp, DP 30 mA RCCB – 3 Nos., 10 A SP MCB -12 Nos. per phase Total-36 Nos., 100 A TPN CU Bus Bars - 1 Set.
Material
Installation
Power Distribution Board Comprising of: Incoming of 63 A TPN MCB - 1 No. Phase indicating lamps Outgoing – 40 Amp DP 100mA RCCB -3 Nos., 20 A SP MCB – 12, Nos. per phase Total –36 Nos., 100 A TPN CU Bus Bars - 1 Set.
Material
Installation
A C Distribution Board (for Indoor Units & VAV) Comprising of: Incoming of 63A TPN 300mA RCBO - 1 No. Phase indicating lamps Outgoing – 20 A SP MCB – 12 Nos. per phase Total – 36 Nos. 100 A TPN CU Bus Bars - 1 Set.
Material
Installation
UPS Distribution Boards Comprising of: Incoming of 63 Amp 4P MCB - 1 No. Phase indicating lamps Outgoing – 32 Amp DP 300 ma Si RCCB -3 Nos., 16 A SP MCB – 8 Nos. per phase Total – 24 Nos., 100 A TPN CU Bus Bars - 1 Set.
Material
Installation
BMS Distribution Boards Comprising of: Incoming of 63 Amp 4P MCB - 1 No. Phase indicating lamps Outgoing – 16 A SP MCB – 12 Nos. per phase Total – 36 Nos. 100 A TPN CU Bus Bars - 1 Set.
Material
Installation
Emergency Distribution Board Comprising of: Incoming of 63 A 4P MCB - 1 No., Phase indicating lamps Outgoing – 40 Amp, DP 30 mA RCCB – 3 Nos., 10 A SP MCB -8 Nos. per phase Total-24 Nos., 100 A TPN CU Bus Bars - 1 Set.
Material
Installation
External Lighting Board Providing Below Mentioned Configuration DB in IP 66 enclosure, for free standing outdoor application, complete with MS Frameworks Legs Comprising of: Incoming of 63 A TPN MCCB - 1 No. T/M release O/C,S/C & E/F, Photoelectric programmable lux sensor IP 65, Astronomical Timer as override for above sensor, Phase indicating, lamps- 1 set Outgoing – 40 Amp, TPN 300 mA RCCB – 1 No., 32 A TPN MCB – 10 Nos., 20 TPN MCB – 14 Nos., 100 A TPN CU Bus Bars - 1 Set.
Material
Installation
Providing in weatherproof IP65 enclosure 1000 Amp, 4P Microprocessor Based open transition type Auto changeover Switch (ASCO 230 Series) & 1000A TPN Microprocessor Over current, Short circuit and Earth fault.
Material
Installation
Providing in sheet steel enclosure 160 Amp, 4P Microprocessor Based open transition type Auto changeover Switch (ASCO 230 Series) & 160A 4P Microprocessor Over current & Short circuit.
Material
Installation
Providing in weatherproof IP66 enclosure 63Amp TPN MCB including mounting, fabrication, cable box etc.
Material
Installation
Providing in weatherproof IP66 enclosure 32Amp TPN MCB including mounting, fabrication, cable box etc.
Material
Installation
Providing in sheet steel enclosure 200 Amp TPN MCCB with T/M release, 36 KA, including mounting, fabrication, cable box etc.
Material
Installation
Providing in sheet steel enclosure 160 Amp TPN MCCB with T/M release, 36 KA, including mounting, fabrication, cable box etc.
Material
Installation
Providing in sheet steel enclosure 125 Amp TPN MCCB with T/M release, 36 KA, including mounting, fabrication, cable box etc.
Material
Installation
Providing in sheet steel enclosure 100 Amp TPN MCCB with T/M release, 36 KA, including mounting, fabrication, cable box etc.
Material
Installation
Providing in weatherproof IP66 enclosure 125 Amp TPN MCCB with T/M release, 36 KA, including mounting, fabrication, cable box etc.
Material
Installation
Providing in sheet steel enclosure 63 Amp TPN MCB, including mounting, fabrication, cable box etc.
Material
Installation
Providing in sheet steel enclosure 32 Amp TPN MCB, including mounting, fabrication, cable box etc.
Material
Installation
Providing in sheet steel enclosure 40 Amp DP MCB, including mounting, fabrication, cable box etc.
Material
Installation
Providing in sheet steel enclosure 63 Amp DP MCB, including mounting, fabrication, cable box etc.
Material
Installation
Providing in sheet steel enclosure 32 Amp DP MCB, including mounting, fabrication, cable box etc.
Material
Installation
Cables: Providing 1.1KV stranded copper / aluminum conductor 3½ core XLPE insulated conductor and insulation , flat steel wires armoring, tough heat resisting outer sheets of following sizes.
3½ C x 300 Sq. mm.Al Conductor XLPE
Material
Installation
3½ C x 240 Sq. mm.Al Conductor XLPE
Material
Installation
3½ C x 185 Sq. mm.Al Conductor XLPE
Material
Installation
3½ C x 150 Sq. mm.Al Conductor XLPE
Material
Installation
3½ C x 120 Sq. mm.Al Conductor XLPE
Material
Installation
3½ C x 95 Sq. mm.Al Conductor XLPE
Material
Installation
3½ C x 70 Sq. mm.Al Conductor XLPE
Material
Installation
3½ C x 50 Sq. mm.Al Conductor XLPE
Material
Installation
3½ C x 35 Sq. mm.Al Conductor XLPE
Material
Installation
4 C x 25 Sq. mm.Al Conductor XLPE
Material
Installation
Providing of 1.1 KV Grade PVC insulated, PVC sheathed GI wire armored multicore copper Stranded conductor, Cable of following sizes to be laid in prepared trenches/ excavated trenches/ on wall / on trays complete with dressing saddling clamping etc. Including civil work and required accessories spacers, clamps and hardware etc.
4C x 10 Sq mm YWY
Material
Installation
4 C x 6 Sq. mm. YRY
Material
Installation
4 C x 4 Sq. mm. YRY
Material
Installation
3 C x 6 Sq. mm. YRY
Material
Installation
3 C x 4 Sq. mm. YRY
Material
Installation
3 C x 2.5 Sq. mm. YWY
Material
Installation
4 C x 16 Sq. mm. YWY
Material
Installation
3 C x 2.5 Sq. mm. YY
Material
Installation
Providing Termination of cables with Double compression Brass cable gland and with crimping type copper/AL lugs suitable for copper/AL conductor cable with consumable such as tape, hard ware.
3½ C x 300 Sq. mm.Al Conductor XLPE
Material
Installation
3½ C x 240 Sq. mm.Al Conductor XLPE
Material
Installation
3½ C x 185 Sq. mm.Al Conductor XLPE
Material
Installation
3½ C x 150 Sq. mm.Al Conductor XLPE
Material
Installation
3½ C x 120 Sq. mm.Al Conductor XLPE
Material
Installation
3½ C x 95 Sq. mm.Al Conductor XLPE
Material
Installation
3½ C x 70 Sq. mm.Al Conductor XLPE
Material
Installation
3½ C x 50 Sq. mm.Al Conductor XLPE
Material
Installation
3½ C x 35 Sq. mm.Al Conductor XLPE
Material
Installation
4 C x 25 Sq. mm.Al Conductor XLPE
Material
Installation
Providig Termination of cables with Double compression Brass cable gland and with crimping type copper/AL lugs suitable for copper/AL conductor cable with consumable such as tape, hard ware.
4Cx 10Sq mm YWY
Material
Installation
4 C x 6 Sq. mm. YRY
Material
Installation
4 C x 4 Sq. mm. YRY
Material
Installation
3 C x 6 Sq. mm. YRY
Material
Installation
3 C x 4 Sq. mm. YRY
Material
Installation
3 C x 2.5 Sq. mm. YWY
Material
Installation
4 C x 16 Sq. mm. YWY
Material
Installation
3 C x 2.5 Sq. mm. YY
Material
Installation
Supply, Installation and testing of 1100 V Grade PVC insulated, PVC sheathed unarmored single core copper Stranded conductor, Cable of 300 Sq. mm. size through Flexible GI conduit in approved manner on wall / on trays complete with dressing saddling clamping termination etc. Including civil work and required accessories spacers, clamps and hardware etc.
Material
Installation
Supply, Installation and testing of 1100 V Grade PVC insulated, PVC sheathed unarmored single core copper Stranded conductor, Cable of 50 Sq. mm. size through Flexible GI conduit in approved manner on wall / on trays complete with dressing saddling clamping termination etc. Including civil work and required accessories spacers, clamps and hardware etc.
Material
Installation
Supply, Installation and testing of 1100 V Grade PVC insulated, PVC sheathed unarmored single core copper Stranded conductor, Cable of 35 Sq. mm. size through Flexible GI conduit in approved manner on wall / on trays complete with dressing saddling clamping termination etc. Including civil work and required accessories spacers, clamps and hardware etc.
Material
Installation
Excavation of cable trench having as per standard drawing in existing strata of soil, sand bedding, brick protection cover, plastic cover , back filling and making good as required as per standard specification and drawing.
Material
Installation
Providing 50 mm GI Conduit with accessories
Material
Installation
LIGHTING - POINT WIRING : Concealed points wiring for light, fan, 6A socket switch point, using ISI marked rigid GI 25 mm dia. Conduit along with heavy duty GI conduit accessories, GI boxes, switches, regulators, sockets, plug top, mounting plates, hardware, ceiling rose, holders, ball socket, anchor hooks, clamps etc. Wiring through GI conduit including termination. 2 Nos. of 2.5 mm² copper conductor FRLS PVC wire for phase, neutral and 1.5 mm² copper conductor FRLS PVC wire for earthing will be used for- Primary Point includes conduiting and wiring from LDB to Switch Board, Switch Board to looped Switch Board and Switch Board to first point measured as one Primary point. 3 Nos. of 1.5 mm² copper conductor FRLS PVC wire for phase, neutral and earthing will be used for- wiring from primary point to looped point said as Secondary Point Point wiring will be done as per IE rules
Primary Light point
Material
Installation
Secondary Light point looped from above mentioned Primary Light point with distance up to 1 meter.
Material
Installation
Secondary Light point looped from above mentioned Primary Light point with distance over 1 meter.
Material
Installation
6 A switch and 6A socket mounted on switchboard along with lighting switches.
Material
Installation
6A switch and 6A socket mounted separately away from switch box on wall/partition. Wiring from nearest switch box through GI conduit embedded in wall or through partition.
Material
Installation
Exhaust Fan Point
Material
Installation
LIGHT FIXTURES
Providing following equipments along with accessories, hardware, down rods made out of 19mm 16 SWG GI conduit, ball and socket and check nut arrangement. In case of conduit with S.S. Chains/Gear Chain are used then same will be suspended from ceiling by ISI marked anodized anchor fasteners. Light fittings to be suspended individually at all four corners.
Providing of LED recessed Luminaire with a nomial system lumen output of 3000 lumens and a minimum system efficacy of 120 lm/W. The luminaire shall have a rated system lifetime of 50,000 burning hours at L80 B50-50KHrs @ Ta :45 Degrees. The luminaire should have a color temperature of 4000K/6500k and CRI>80. Driver of the luminaire shall have THD<10% and PF >0.9. The luminaire housing should made of powder coated CRCA with high efficiency opal diffuser. The total power consumption should not exceed 25W (including driver) with 2KV surge protection. Leakage current should be as per as per IEC 60598 and Fixture should be EMC/EMI compliant. Model similar to Philips Make Full Glow RC380B LED30S-6500 L60W60 PSU OD S1
Material
Installation
Providing of RECESSED LED Luminaire with a nominal system lumen output of 1300 lumens and a minimum system efficacy of 100lm/W. System wattage should not exceed 13W. The luminaire shall have a rated system lifetime of 50,000 burning hours at L80. The luminaire should have a color temperature of3000K, 4000K and CRI>80. Driver of the luminaire shall have THD < 10% and PF > 0.95. The luminaire housing should be made of extruded Aluminium with PMMA diffuser. The driver shall comply to IEC 62384 , IEC 61347-2-13, IEC 61547, EMI- CISPR15 standards. Model similar to Philips Make Green LED i 1200 DN193B LED12S-6500 PSU WH S1
Material
Installation
Providing of Surface mounted 4ft Luminaire Equivalent to Philips Make TCW450 P 1XTLED 18W/ 2100lm IP65 protection against dust and water
Material
Installation
Providing of recesseed Equivalent to Philips Make RS271 -2x 28W LED downlight with double bezzel plate
Material
Installation
Providing of LED 4ft Batten with a nominal system lumen output of 2000 lumens and a minimum system efficacy of 100 lm/W. System wattage should not exceed 20W. The luminaire shall have a rated system lifetime of 50,000 burning hours at L80. The luminaire should have a color temperature of 4000K and CRI>80. Driver of the luminaire shall have THD < 10% and PF > 0.95. The luminaire housing should be made of CRCA with a PC glossy diffuser. Similar to Philips Make Endura LED Batten "BN 108C LED 20S PSU NW WH"
Material
Installation
Providing of RECESSED LED Luminaire with a nominal system lumen output of 700 lumens and a minimum system efficacy of 100lm/W. System wattage should not exceed 7W. The luminaire shall have a rated system lifetime of 50,000 burning hours at L80. The luminaire should have a color temperature of3000K, 4000K and CRI>80. Driver of the luminaire shall have THD < 10% and PF > 0.95. The luminaire housing should be made of extruded Aluminium with PMMA diffuser. The driver shall comply to IEC 62384 , IEC 61347-2-13, IEC 61547, EMI- CISPR15 standards. Model similar to Philips Make Green LED i 600 DN191B LED6S-6500 PSU WH S1
Material
Installation
Providing Square surface mounted 300x300 mm luminaire. With CRI>80 and SDCN<5. Body made of PC/CRCA and with Opal PMMA diffuser. THD should be <10% and with minimum 85% efficinecy. Model similar to Philips Make Cirrus mini Pro SM200C LED16S 6500 PSU OD WH
Material
Installation
Providing Surface mounted Bulkhead. The product should have THD <=20% with pf>0.9. The fixture should be IP66 and IK09 rated with high pressure die cast housing and PC diffuser. Model similar to Endura LED Bulkhead WT202W LED6S
Material
Installation
Providing of LED Highbay Luminarie, 100 W , 125 Lm/W Equivalent to Phiips Cat No. BY325P LED130s
Material
Installation
Supply Recessed 3W LED Downlight
Material
Installation
Providing of Decorative Light Fittings (upto Rs. 10,000/-)
Material
Installation
Providing of Decorative Chandelier Light Fittings (upto Rs. 1,00,000/-)
Material
Installation
Providing of PIR Sensors with contact rating of 10 Amps inductive, covering area of 8 meters at mounting height of 3 meter, occupancy Sensor Eequivalent to Model no LRM 1070 of Philips Make
Material
Installation
POWER WIRING
Concealed points wiring for power plug point.
Concealed 16A power plug points includes for conduiting from RAW Power DB to point as directed, by 25 mm ISI marked GI conduit, conduit accessories, pull boxes, plates, 16A switch, 16 A+6A sockets, wiring by 2 nos. of 2.5 mm². Copper conductor PVC wire for phase and 1.5 mm². Copper conductor PVC wire for earthing through GI conduit including termination, as shown from D.B. to power point. Maximum Two Nos. of Power points to be looped and will be measured as Two separate points.
Material
Installation
Concealed 16A power plug points includes for conduiting from AC DB to point as directed, by 25 mm ISI marked GI conduit, conduit accessories, pull boxes, plates, 16A switch, 16 A+6A sockets, wiring by 2 nos. of 2.5 mm². Copper conductor PVC wire for phase and 1.5 mm². Copper conductor PVC wire for earthing through GI conduit including termination, as shown from D.B. to power point. Maximum Two Nos. of Power points to be looped and will be measured as Two separate points.
Material
Installation
Concealed 6A power plug points includes for conduiting from Raw Power DB to point as directed, by 25 mm ISI marked GI conduit, conduit accessories, pull boxes, plates, 6A switch & 6 A sockets, wiring by 2 nos. of 2.5 mm². Copper conductor PVC FRLS wire for phase and 1.5 mm². Copper conductor PVC FRLS wire for earthing through GI conduit including termination, as shown from D.B. to power point. Maximum Six Nos. of Power points to be looped and will be measured as Six separate points.
Material
Installation
Concealed 6A power plug points includes for conduiting from AC DB to point as directed, by 25 mm ISI marked GI conduit, conduit accessories, pull boxes, plates, 6A switch & 6 A sockets, wiring by 2 nos. of 2.5 mm². Copper conductor PVC FRLS wire for phase and 1.5 mm². Copper conductor PVC FRLS wire for earthing through GI conduit including termination, as shown from D.B. to power point. Maximum Six Nos. of Power points to be looped and will be measured as Six separate points.
Material
Installation
Concealed 20 A SPN BCH / Crompton Rey rolled porcelains socket and 20 A SP MCB housed in GI Box without wiring. Conduiting from DB to point as directed through wall/partition, by 25 mm ISI marked GI conduit, conduit accessories, plated pull boxes. Wiring by 2Nos. 2.5 Sq. mm. & 1 no. 1.5sq.mm copper conductor PVC insulated multicore flexible cable through GI conduit including termination.
Material
Installation
Providing 32 AMPS Single phase Power point with 32 A SP MCB & Industrial Socket, and wiring with 2 Nos 4 mm and 1 No. 2.5 sq mm PVC insulated copper FRLS wire from DB to point as directed through GI Conduit and GI conduit accessories.
Material
Installation
Providing 20 AMPS Single phase Power point with 32 A SP MCB & Industrial Socket, and wiring with 2 Nos 4 mm and 1 No. 2.5 sq mm PVC insulated copper FRLS wire from DB to point as directed through GI Conduit and GI conduit accessories.
Material
Installation
Providing 32 AMPS Three phase Power point with 32 A TPN MCB & Industrial Socket, and wiring with 3 Nos 4 mm and 2 Nos. 2.5 sq mm PVC insulated copper FRLS wire from DB/Panel to point as directed through GI Conduit and GI conduit accessories.
Material
Installation
Providing 63 Amp Three phase Power point comprising of 63 Amp socket and MCB in IP 56 weather proof enclosure and wiring with 3 Nos 10 sq mm and 2 Nos.6 Sqmm PVC insulated copper FRLS wire from DB/Panel to point as directed through GI Conduit and GI conduit accessories.
Material
Installation
Imigration Counter Raw Point Concealed 16A+6A, 6A switch socket combined power point as Power Point. Providing concealed Power Point wiring for – 2 Nos. of 16A+6A Socket Controlled by 2 Nos.16A switch in housing as mentioned below. Conduiting from J. B. of Power Raceway embedded in floor to point as directed through wall/partition, by 25 mm ISI marked GI conduit, conduit accessories, plated MS pull boxes. Wiring by 3 Core 2.5 Sq. mm. copper conductor PVC FRLS insulated and overall PVC sheathed multicore flexible Grey color cable through GI conduit and raceway including termination. Cost of providing raceways will be covered in separate item mentioned elsewhere. No point to be looped.
Material
Installation
UPS POWER WIRING
Concealed switch socket combined power point as UPS Point.
Concealed 16A power plug points includes for conduiting from UPS Power DB to point as directed, by 25 mm ISI marked GI conduit, conduit accessories, pull boxes, plates, 16A switch, 16 A+6A sockets, wiring by 2 nos. of 2.5 mm². Copper conductor PVC FRLS wire for phase and 1.5 mm². Copper conductor PVC FRLS wire for earthing through GI conduit including termination, as shown from D.B. to power point. Maximum Two Nos. of Power points to be looped and will be measured as Two separate points.
Material
Installation
Concealed 13A power plug points includes for conduiting from UPS Power DB to point as directed, by 25 mm ISI marked GI conduit, conduit accessories, pull boxes, plates, 16A switch, 13A Universal sockets, wiring by 2 nos. of 2.5 mm². Copper conductor PVC FRLS wire for phase and 1.5 mm². Copper conductor PVC FRLS wire for earthing through GI conduit including termination, as shown from D.B. to power point. Maximum Two Nos. of Power points to be looped and will be measured as Two separate points.
Material
Installation
Concealed 3 x 13A soxket with 1 no. of 16A switch power plug points includes for conduiting from UPS Power DB to point as directed, by 25 mm ISI marked GI conduit, conduit accessories, pull boxes, plates, 16A switch, 13A Universal sockets, wiring by 2 nos. of 2.5 mm². Copper conductor PVC FRLS wire for phase and 1.5 mm². Copper conductor PVC FRLS wire for earthing through GI conduit including termination, as shown from D.B. to power point. Maximum Four Nos. of Power points to be looped and will be measured as Fouro separate points.
Material
Installation
Concealed 6A power plug points includes for conduiting from UPS Power DB to point as directed, by 25 mm ISI marked GI conduit, conduit accessories, pull boxes, plates, 6A switch, 6 A sockets, wiring by 2 nos. of 2.5 mm². Copper conductor PVC wire for phase and 1.5 mm². Copper conductor PVC wire for earthing through GI conduit including termination, as shown from D.B. to power point. Maximum Four Nos. of Power points to be looped or as directed and will be measured as Four separate points.
Material
Installation
Concealed 32 A Single Phase 250V, 2P+E Mobile socket and straight plug IP44 in GI Box. Conduiting from DB to point as directed through wall/partition, by 25 mm ISI marked GI conduit, conduit accessories, plated pull boxes. Wiring by 3C x 4 sq.mm copper conductor PVC insulated multicore flexible cable through GI conduit including termination.
Material
Installation
Points For Racks
Surface 32 A Single Phase 250V, 2P+E Mobile socket and straight plug IP44 in GI Box. Cabling from DB to point located under/above Rack as directed through cable tray or trunking. Wiring by 3C x 6 sq mm Copper conductor PVC insulated cable including termination.
Material
Installation
Imigration Counter Raw Point
Concealed 16A+6A, 6A switch socket combined power point as UPS Point. Providing concealed Power Point wiring for – 2 Nos. of 16A+6A Socket Controlled by 2 Nos.16A switch in housing as mentioned below. Conduiting from J. B. of UPS Power Raceway embedded in floor to point as directed through wall/partition, by 25 mm ISI marked GI conduit, conduit accessories, plated MS pull boxes. Wiring by 3 Core 2.5 Sq. mm. copper conductor PVC FRLS insulated and overall PVC sheathed multicore flexible Grey color cable through GI conduit and raceway including termination. Cost of providing raceways will be covered in separate item mentioned elsewhere. No point to be looped.
Material
Installation
EARTHING
Providing Earthing pit by auguring and installation of Copper Coated electrolytically bonded 250 micron MS Earth Rod of 17.2 mm dia 3 mtr long Earth enhancement compund 25 Kg , connector for testing link complete with inspection chamber made out of brick masonary and cast iron inspection cover duly painted and marked.
Material
Installation
Providing 3 meters Earthing having pipe in pipe technology with cast iron pipe outside and GI pipe inside duly filled by chemical for conductivity.
Material
Installation
Providing single core 95 mm² copper conductor PVC FRLS insulated PVC sheathed cable in GI conduit with Termination.
Material
Installation
Providing single core 70 mm² copper conductor PVC FRLS insulated PVC sheathed cable in GI conduit with Termination.
Material
Installation
Providing single core 35 mm² copper conductor PVC FRLS insulated PVC sheathed cable in GI conduit with Termination.
Material
Installation
Providing single core 16 mm² copper conductor PVC FRLS insulated PVC sheathed cable in GI conduit with Termination.
Material
Installation
Providing single core 10 mm² copper conductor PVC FRLS insulated PVC sheathed cable in GI conduit with Termination.
Material
Installation
Providing single core 2.5 mm² copper conductor PVC FRLS insulated PVC sheathed cable with Termination.
Material
Installation
Providing single core 1.5 mm² copper conductor PVC FRLS insulated PVC sheathed cable with Termination
Material
Installation
Providing copper earth Busbar of size 450 mm x 50 mm x 4 mm mounted on insulators having holes on it with termination arrangement, nut bolts etc. Fitted in ms junction box with acrylic cover.
Material
Installation
Providing copper earth Busbar of size 300 mm x 50 mm x 4 mm mounted on insulators having holes on it with termination arrangement, nut bolts etc. Fitted in ms junction box with acrylic cover.
Material
Installation
Providing 50 mm x 6 mm GI earthing flat
Material
Installation
Providing 50 mm x 6 mm Cu earthing flat
Material
Installation
Providing 32 mm x 6 mm GI earthing flat
Material
Installation
Providing 25 mm x 6 mm GI earthing flat
Material
Installation
Providing 12 SWG copper earthing wire
Material
Installation
Providing 8SWG Copper earthing wire.
Material
Installation
Providing 25 mm x 3 mm CU. earthing flat
Material
Installation
Providing 25 mm x 3 mm GI. earthing flat
Material
Installation
Supply of conventional type lightning arrestor with 100MM dia copper spheare with 5 nos spike and 1.5 Mtr copper pole with base plate.
Material
Installation
DATA VOICE CONDUITING
Providing MS box for DATA/VOICE socket point
Material
Installation
50 mm. rigid GI ISI marked conduit with conduit accessories
Material
Installation
50 mm. flexible GI ISI marked conduit with conduit accessories
Material
Installation
Providing 25 mm GI ISI marked Rigid conduit for Data/Voice/AV with accessories.
Material
Installation
CABLE TV
25mm dia ISI marked rigid GI conduit for T. V. points along with medium duty GI conduit accessories, splitters, J. B.s, electro plated Pull Boxes etc. on surface in Duct & concealed in floors, through floors slab, wall etc.
Material
Installation
TV coaxial cable of RG-11 size with copper conductor.
Material
Installation
Providing TV socket outlet in plated GI box.
Material
Installation
OTHER ITEMS
Emergency Point, by using 25 mm dia GI ISI marked conduit and with GI accessories, 3 Nos. of 2.5 sq. mm. PVC FRLS insulated copper conductor wires to various points from Emergency DB to Emergency switch Board to Emergency Point. Maximum six points will be looped together. Same phase sequence to be maintained with respect to adjacent light fitting.
Material
Installation
CABLE SUPPORTS
Providing Structural fabrication for Cable Tray supports made out of Angle/C-Channel, plate, Anchor fasteners etc in wall/ceiling including supply of steel, cutting, welding, drilling, erecting at site including consumables like welding rods, gas drill bits etc. Job also includes for minor civil work, duly Painted with two coats of Red oxide and two coats of Synthetic namel paint of grade 631.
Material
Installation
Providing FRP ladder type Cable Tray made out of FRP sheet as per drawing having following width with supporting structure duly painted with two coats of red oxide and two coats of enamal paint. Steel structure will be measured and paid saperately against steel structure item.
1000 mm width x 75 mm x 4mm Thick
Material
Installation
750 mm width x 75 mm x 4mm Thick
Material
Installation
600 mm width x 75 mm x 4mm Thick
Material
Installation
450 mm width x 75 mm x 4mm Thick
Material
Installation
300 mm width x 75 mm x 3 mm Thick
Material
Installation
150 mm width x 75 mm x 3 mm Thick
Material
Installation
Providing 600 mm x 75 mm x 3mm FRP Perforated type Cable Tray with removable cover of 3 mm. Job includes providing cable Raceway and it’s supports / hangers installation with supporting structure duly painted with two coats of red oxide and two coats of enamal paint. Steel structure will be measured and paid saperately against steel structure item.
Material
Installation
Providing 450 mm x 75 mm x 3 mm FRP Perforated type Cable Tray with removable cover of 3 mm. Job includes providing cable Raceway and it’s supports / hangers installation. with supporting structure duly painted with two coats of red oxide and two coats of enamal paint. Steel structure will be measured and paid saperately against steel structure item.
Material
Installation
Providing 300 mm x 75 mm x 3 mm FRP Perforated type Cable Tray with removable cover of 3 mm. Job includes providing cable Raceway and it’s supports / hangers installation. with supporting structure duly painted with two coats of red oxide and two coats of enamal paint. Steel structure will be measured and paid saperately against steel structure item.
Material
Installation
UNDER FLOOR RACEWAYS
Providing raceways below false floor Comprising rectangular aluminum extruded tubes. Cleaning wherever necessary, fixing the raceways, minor civil work with providing sealing at joints at junction boxes and proper alignment, vacuum cleaning and connection of following sizes. Job also includes of data/voice/power conduit supply and installation.
100 x 40mm x2mm thick Al Raceway
Material
Installation
80 x 40mm x2mm thick Al Raceway
Material
Installation
40 x 40mm x2mm thick Al Raceway
Material
Installation
Providing junction boxes for aforesaid raceways fabricated out of MS sheet with powder coating, having following sizes made out of 1.6 mm thick sheet, 50 mm deep, with cut outs for raceways and Cover plate of the junction box.
Junction Box of size 200 mm x 200 mm.
Material
Installation
Junction Box of size 300 mm x 300 mm.
Material
Installation
Junction Box of size 350 mm x 350 mm.
Material
Installation
Junction Box of size 500 mm x 500 mm.
Material
Installation
Providing Table Top Popup Boxes rated for 230V AC, ABS-FR, low concentration of heavy metal, aluminum casing, gounded to protect against electrical shock in Gang Box of configuration mentioned below- Equivalent to A.H. Meyer 12 Module Box, 3 Nos. International Socket + 1 No. International Socket + 2 Nos. 16A Switch, Provision of space with balanking cover for 2 Nos. LAN Ports.
Material
Installation
Rubber Mat of 1Mtr x 2Mtr, 12mm size for electrical & ups room
Material
Installation
Resuscitation chart
Material
Installation
UPS & Batteries Supply, Installation, Testing and Commissioning of UPS having rating given as under and as specified. UPS should be true ON Line Double conversion technology with pure sine wave output. UPS should be without Isolation Transformer. Technology in UPS should be with IGBT Rectifier & Inverter with IGBT. It should be achieving current harmonics of less than 5% for 100% computer load. UPS should have- 1) Emergency Power Off to be provided, which can be connected through Fire suppression system. 2) BMS compatible facility with communication card, Auto dialer facility. 3) Report generation facility on UPS to track the history of UPS status. 4) Minimum four Potential free contacts. 5) Static Bypass 6) Maintenance Bypass 7) Synchronizing circuit 8) 4 Nos potential free contacts 9) Filter cut off arrangement in case of input pf goes to leading. 10) Monitoring and control system shall be state of the art technology LCD Panel Type, providing all relevant data. 11) Contact in UPS suitable to be used for tripping of MCCB provided by electrical contractor. In case UPS is in `ON` it will operate Job includes cabling & cable tray between UPS, STS and batteries. Commissioning of UPS will be done with load testing with heater load arrangement.
Providing 30 KVA UPS 3 phase In & 3 phase out without isolation transformer.UPS will be with VRLA SMF Battery Backup of 90 minutes.
Material
Installation
Providing 60 KVA UPS 3 phase In & 3 phase out without isolation transformer.UPS will be with VRLA SMF Battery Backup of 30 minutes.
Material
Installation
EXTERNAL LIGHTING
PANELS & D.B.S
Providing Panel / Power distribution Boards suitable for 415V 50Hz 3ph 4 wire supply dust and vermin proof floor/ wall mounting cubicle pattern with removable gland plates, copper bus bar, mounting frame, grouting made out of crca sheet, double door, duly powder coated painted as specified as follows. MCB with ‘c’ curve for lighting & power, d curve will be used for PC.
Material
Installation
Material
Installation
Material
Installation
CABLES
Providing 1.1KV stranded copper / aluminum conductor 3½ core XLPE insulated conductor and insulation , flat steel wires armoring, tough heat resisting outer sheets of following sizes.
3½ C x 95 Sq. mm. A2XFY
Material
Installation
3½ C x 70 Sq. mm. A2XFY
Material
Installation
4 C x 25 Sq. mm. A2XFY
Material
Installation
Providing of 1100 V Grade PVC insulated, PVC sheathed GI wire armored multicore copper Stranded conductor, Cable of following sizes to be laid in prepared trenches/ excavated trenches/ on wall / on trays complete with dressing saddling clamping etc. Including civil work and required accessories spacers, clamps and hardware etc.
4 C x 6 Sq. mm. YRY
Material
Installation
4 C x 4 Sq. mm. YRY
Material
Installation
3 C x 6 Sq. mm. YRY
Material
Installation
Providing of Termination of cables with double compression Brass cable gland including gland earthing and with crimping type copper lugs suitable for copper conductor cable with consumable such as tape, hard ware.
3½ C x 95 Sq. mm. A2XFY
Material
Installation
3½ C x 70 Sq. mm. A2XFY
Material
Installation
4 C x 25 Sq. mm. A2XFY
Material
Installation
Providing of Termination of cables with double compression Brass cable gland including gland earthing and with crimping type copper lugs suitable for copper conductor cable with consumable such as tape, hard ware.
4 C x 6 Sq. mm. YRY
Material
Installation
4 C x 4 Sq. mm. YRY
Material
Installation
3 C x 6 Sq. mm. YRY
Material
Installation
LIGHTING
Providing following equipments along with accessories, hardware, down rods made out of 19mm 14 SWG MS enamel painted conduit, ball and socket and check nut arrangement. In case of conduit with S.S. Chains are used then same will be suspended from ceiling by ISI marked anodized anchor fasteners. Light fittings to be suspended individually at all four corners. Providing LED fitting with sutiable Driver approved by Architect/Consultant having following Cat Number.
Providing 8 meter decorative poles made out of combination of GI & CI with double arm decorative bracket, anchor bolts, looping box of IP66 grade, suitable 2/3way terminal block along with LED of 135w, IP66. The cost of LED is deemed to be included in the quoted price.The Junction box will be placed inside the pole to improve the asthetic look in a window cut at the bottom neatly places the connector, MCB, Earthing point for loop in loop out arrangement. The Pole consist of a base plate having 16-25mm thickness. Pole to be mounted with suitable foundation of 1.5-3mtr alongwith suitable mounting accessories like foundation bolts, base plate etc... Street LIght Fixture to be mounted on ARM with termination cable running from pole base internally in absence of external junction box. Equivalent to Dwaraka Cat. No. DLP-3-80-302
Material
Installation
Providing 10-12W LED IP65 500-mm, Iron Decorative Bollard. Fixture to be mounted on concrete base Equivalent to Dwaraka Cat. No. DBL-103-S
Material
Installation
Providing 8 meter decorative poles made out of combination of GI & CI with Four arm decorative bracket, anchor bolts, looping box of IP66 grade, suitable 2/3way terminal block along with LED of 135w, IP66. The cost of LED is deemed to be included in the quoted price.The Junction box will be placed inside the pole to improve the asthetic look in a window cut at the bottom neatly places the connector, MCB, Earthing point for loop in loop out arrangement. The Pole consist of a base plate having 16-25mm thickness. Pole to be mounted with suitable foundation of 1.5-3mtr alongwith suitable mounting accessories like foundation bolts, base plate etc... Street LIght Fixture to be mounted on ARM with termination cable running from pole base internally in absence of external junction box. Equivalent to Dwaraka Cat. No. DBP-002
Material
Installation
OTHER WORKS
Providing Out door IP 65 Junction Boxes for termination of cables of size 100 mm x 100 mm.
Material
Installation
Providing Out door IP 65 Junction Boxes for termination of cables of size 200 mm x 200 mm.
Material
Installation
IP 65 Out door cable male female gas filled termination kit for terminating cables.
Material
Installation
Providing 350 x 350 mm Square Concrete base for mounting Outdoor Shrub light and Bollards
Material
Installation
Excavation of 450 mm wide 600 mm deep in existing strata of soil with horizontal accross bricks on top of cables, sand bedding of 50 mm above and bellow cable & Back filling and making good as per existing condition. for External Lighting cable work
Material
Installation
Providing 50 mm GI Conduit with accessories
Material
Installation
Providing Structural fabrication for supports made out of 40 x 40 x 3mm angle, plate, Anchor fasteners etc in wall/ceiling including supply of steel, cutting, welding, drilling, erecting at site including consumables like welding rods, gas drill bits etc. Job also includes for minor civil work, duly Painted with two coats of Red oxide and two coats of Synthetic namel paint of grade 631.
Material
Installation
Providing Hot Dipped Galvanised ladder type Cable Tray made out of 14 SWG MS sheet steel as per drawing having following width with two sets of GI Full threaded 6mm GI Bolts, Nuts and two numbers of 50mm Anchor Fasners duly installed on slab.
150 mm width x 75 mm
Material
Installation
EARTHING
Providing ASHLOK make 3 meters Earthing having pipe in pipe technology with cast iron pipe outside and GI pipe inside duly filled by chemical for conductivity.
Material
Installation
Providing 50 mm x 6 mm GI earthing flat
Material
Installation
Providing 8SWG Copper earthing wire.
Material
Installation
Shree Electricals and Engineers (India) Private Limited
Konstelec Engineers Pvt. Ltd.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.30 MB
DRAW03062021.pdf
Tender Documents • 0.17 MB
TECH062021.pdf
Tender Documents • 1.55 MB
PREAMBLE062021.pdf
Tender Documents • 0.22 MB
DRAW01062021.pdf
Tender Documents • 1.68 MB
DRAW02062021.PDF
Tender Documents • 1.58 MB
BOQ_660620.xls
BOQ • 0.54 MB
Download all tender documents and submit your bid