Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Infra Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹23.2 LAccepted-AOC 53 MIDDLE STREET ARUMALAI TIRUKOILUR VILLUPURAM DISTRICT | VILLUPURAM | TAMIL NADU | 604001 | 1 | Accepted-AOC WORK AWARDED | |
| 2 | 2₹24.1 L+₹46,389.34 (1.96%)Rejected-Finance NO 75 80 VINAYAGAR KOIL STREET THALAVANUR VILLUPURAM DISTRICT 605 103 | VILLUPURAM | TAMIL NADU | 605103 | 2 | Rejected-Finance Second Lowest |
Tender Value
₹23.2 L
EMD Value
₹22,000
Closing Date
27 Oct 2023, 3:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
The Special Chief Engineer
The Superintending Engineer, PWD., Buildings Construction and Maintenance Circle,Tiruvannamalai-4.
Providing of 13 Person Passenger Lift to the RHDC Building in HMDI Campus at Villupuram in Villupuram District.
2023_PWD_380346_1
32/TVM-CLE/23-24/2/ Dt.09.10.2023
Open Tender
Electrical Works
Lump-sum
90 days
VILLUPURAM
Please refer Tender documents.
8 documents required · 8 mandatory
₹0
₹22,000
4 Jan 2024
18 Oct 2023
27 Oct 2023
18 Oct 2023
27 Oct 2023
18 Oct 2023
Amount
Design, Engineering, Supply, Fabrication, Erection, Testing, commissioning and handing over of 1 no 13 persons capacity passenger lift as per the following specifications including taxes and duties.(Gearless lift without machine room)
1.Location: HMDI building , Villupuram
2.No of lift: one no. (Gearless)
3.Type of lift: passenger
4.Capacity of lift: 13 persons / 884 Kgs
5.Speed: 1m / sec
6.Type of drive: V3F drive with enhanced ride comfort and near zero level functions
7.No of floors: GF+4 Floor
8.Total travel: 3.3 mts x 4 Landing = 13.2 mts
9.Leveling accuracy: high level accuracy with smooth and jerk free stopping
10. Construction of CAR: No. 4 hardened sheet high quality stainless steel car and hand rail granite flooring and Perspex false ceiling.
11. Position of machine: directly above the lift well.
12. No of landing service: One in the front side- 1 no.
13. No. of car entrance: one in the front side only
14. Car entrance door: power operated automatic V3F drive center opening sliding SS door
15. Landing entrance door: power operated V3F drive center opening sliding SS door with provision for emergency exit key at all landings.
16.Lift well :2500 mm (wide) X 1900 mm (depth) as per IS 14665(part1) 2000 to be constructed by PWD civil wing
17.Lift pit depth:1600 mm
18. Car inner size: 2000 mm (width)x1100 mm (depth) as per IS 14665 (part 1 )2000,over head 4200mm and Total weight of person – 680 Kg
19. Car clear opening: 900 mm wide as per IS 14665 (part 1)2000
20. Power supply: 400 / 440 v three phase 50 Hz AC supply for power and 230 V 50 Hz single phase power supply for light.
21.Control: micro computer (micro processor):based simplex collective control with / without attendant
22. Car fittings: CFL lighting with 1 no 300 mm sweep cabin fan.
23. Lift well: RCC construction with brick masonry to be constructed by PWD civil wing.
24. Induction: UP / DOWN digital direction and position indicator for all landings and inside the car.
25.Emergency alarm bell: battery operated bell to be provided with automatic charging device
26.Emergency light: battery operated light to be provided with automatic charging device
27.Fire mans switch: to be provided at the GF
28. Minor builder works: to be provided by the lift contractor.
29. Scaffoldings: to be provided by the lift contractor.
30. Sill angles and facia plates: SS to be provided by the lift contractor.
31. Steel for lift machinery: to be provided by the lift contractor.
32. Servicing and maintenance: free comprehensive servicing and maintenance for one year Guarantee period to be provided by the lift contractor.
33. Automatic rescue device: to facilitate the landing of the nearest floor at the time of power failure this shall consist of suitable battery system with charger inverter under voltage protection system etc. complete with all accessories.
34. Provision for intercom with phone: to be provided by the lift contractor.
35.Lift license: preparation of drawings payment of charges to CEIG and insurance policy if any and obtaining CEIG approval for the lift as per lift act should be done by the lift contractor
36. Floor position announcer: to be provided by the lift contractor.
37.Special features
a) Infra red door sensor with full height screen
b) Full width half height rear panel mirror
c)Tubular SS hand rail in car
d) Stainless steel signal features
e) Vandal proof SS button with SS cover
f) SS door frames for landing doors
g) V3F door operator
h) Call register signal
i) Stainless steel facia plates for car operating panel and landing fixtures
j) Steel ladder for lift machine room
k) On / off switch for fan and light
l) Over load warning indicator with audio announcer
m)Voltage stabilizer for control circuits
n)Braille button and mirror
o) Disabled friendly
38.Over speed governor phase failure and phase reversal relay alarm bell T guide brackets for car and counter weight rubber padding under the winding unit motor of adequate capacity signal reduction worm gear electromagnetic brake with compression springs car safety gears buffers electro mechanical locks emergency key side supporting angles motor over load protection devices final limit switch main suspension ropes counter weight lifting joist for mounting the machineries
39. Guarantee: guarantee at least for one year for the material and workman ship of equipments should be offered by the lift contractor.
40. Site testing in accordance with IS 14665 should be carried out at the time of handing over to the user department
41. Supply operation and maintenance manual and necessary tools for operation and a set of Spare parts required for One year
Wiring with 2 x1.5 sq.mm. (22/0.3) PVC insulated single core unsheathed copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with PVC accessories with Module GI switch box in flush with wall with 6A one way module switch with module front plate with continuous earth wire connection by 2.5 sq.mm. PVC insulated SC unsheathed copper wire and making good of the concealed portion with suitable colour for Concealed PVC Light point / fan point (for electronic regulator) (6 points / Coil) Higher End
Supply and fixing of single box type 4' 18 W LED fitting complete with TW round blocks on wall or ceiling with 18 W LED tube light with single side connection ( Havells / equivalant) with PVC unsheathed Copper leads from terminals to the fitting.
Supply and fixing of 15 W LED bulk head fitting with guard
Supply and fixing of 1 no.6A two module 5 pin socket , 1 no. 6A one module switch with module cover plate (plastic) on suitable module concealed Box (GI ) in flush with wall with connections. Higher End
Supply and fixing of 8 way single pole and neutral MCB sheet steel enclosure Distribution board with Double Door (Metal) and 1 No 32 Amps DP MCB as incoming and 6 No's 6A to 32A SPMCB outgoing in flush with wall and making good of the concealed portion with earth connection only. The MCB DB and MCB's should be ISI mark(Like standard make).
Supply and fixing of Vertical type 4 way triple pole netural MCB distribution board double door type with 125 A 4 pole MCCB as incoming 1 No. 63A TP MCB and 9 Nos 32 A SP MCB asoutgoing inflush with wall and making good of the concealed portion with earth connection only. The MCB DB and MCB's should be Like Craftree / euqivelant
Supply and Run of 2 of 2.5 sq.mm. (36/0.3) PVC insulated SC unsheathed copper conductor of 1100 V grade in suitable PVC rigid pipe Concealed in wall and ceiling with continuous earth wire connection by 2.5 sq.mm. PVC insulated SC unsheathed copper wire and making good of the concealed portion with suitable colour.
Supply and Run of 4 of 10 sq.mm. (140/0.3) PVC insulated SC unsheathed copper conductor of 1100 V grade in suitable PVC rigid pipe concealed in wall and ceiling with continuous earth wire connection by 4 sq.mm. PVC insulated SC unsheathed copper wire with painting of suitable colour.
Earthing as per the ISI specification with an earth electrode of 2.1mt class 'B' GI pipe
Supply and run of 25mm*3mm tinned copper flat with necessary clamps / supports on wall / floor / ground for earth connection.
Rajasekar
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .