Superindenting Engineer(Electrical)
CSIR MADRAS COMPLEX, TARAMANI, CHENNAI
Elevating the existing HT Panel board, capacitor panel board (LT Panel) above maximum flood level with suitable MS Structure platform at SS 1 and SS 3 in CSIR Campus
2025_CSIR_258890_1
480(403)2024-25/EW
Open Tender
Electrical Works
Works
90 days
CSIR MADRAS COMPLEX, TARAMANI
Please refer tender documents
5 documents required · 5 mandatory
₹0
₹16,000
7 Jan 2026
12 Dec 2025
29 Dec 2025
12 Dec 2025
26 Dec 2025
12 Dec 2025
Removing of existing Cubicle type Industrial Panel, Fabrication and installation of Box Type structural steel support (MS Channel) platform 100 mm x 50 mm height of 600mm and 65 mmx 6 mm L angle (for providing additional strength) provision for fixing of MS chequred plate of 6 mm thickness for platform and sintex sheet of 2.5mm thickness sheet covers for the Front sides and rear sides of the structural steel platform ( as per Annexure A enclosed). Reinstallation of Cubicle type Industrial Panel at the elevated location/platform, testing and commissioning complete in all aspects as instructed by Engineer-In-Charge. Note : Before submitting the tender the contractor may visit the site.
HT Panel at SS 1 ( Total 6 VCB Compartments) & HT Panel at SS 3 (5 VCB Compartments) (100mm x 50 mm channel -202 kgs(approx.) & 65mm x 6 mm -62 Kgs (approx.) 264 kgs per VCB chamber/ compartment including Platform). Total 11 compartemnts (264 x 11 = 2904 kgs approx.) One VCB Compartment size 650 mm(L) x 3150 mm (W) x 600 mm (H) as per drawing enclosed in Annexure A and as per directions of the Engineer-In-Charge.
Removing of existing Cubicle type Industrial Panel, Fabrication and installation of Box Type structural steel support (MS Channel) platform 100 mm x 50 mm height of 600mm and 65 mmx 6 mm L angle (for providing additional strength) and provision of sintex sheet of 2.5mm thickness sheet covers for the Front sides and rear sides of the structural steel platform ( as per Annexure B enclosed). Reinstallation of Cubicle type Industrial Panel at the elevated location/platform, testing and commissioning complete in all aspects as instructed by Engineer-In-Charge. Note : Before submitting the tender the contractor may visit the site.
Size of platform to raise the exisiting Capacitor bank panel is 2300 mm(L) x 650 mm (W) x 600 mm (H) as per drawing enclosed in Annexure B. Box type platform of 156 kgs (approx.) (100mm x 50 mm - C Channel) & 65mm x 6 mm L- angle - 29 Kgs (approx.) per capacitor panel. Total 185 kgs . Note : Capacitor bank at SS 1 ( Total 3 Nos.) & Capacitor bank at SS 3 (Total 2 Nos.)
Supplying and fixing 2.5 MM Thickness sintex SMC Chequered plate with suitable accessories (Bolts,nuts ,cutting etc..as required) for all panels in mentioned in ITEM NO:1.01 & 2.01 for front and rear side of existing panels with suitable Fabrication work as per site condition etc.., as required.
Sintex SMC Chequerd Plate 2.5 mm for HT VCB Panel SS I , SS 3 and Capacitor Bank panel (5 Nos)
Supplying and fixing 6 MM Thickness MS Chequered plate with suitable accessories (Bolts,nuts ,cutting etc..as required) for all panels in mentioned in ITEM NO:1.01 for front and rear side of existing panels with suitable Fabrication work as per site condition etc.., as required.
6MM MS Chequered Plate for HT VCB Panel platform at SS I (3900 mm x 1500 mm) & SS 3 (3250 mm x 1500mm)
Excavation for soil for locating/ retrieving of loose cables and HT cable removing and reconnecting of the exisitng cables in the existing panel after raising the panel board height as per site condition…as required.for ITEM no:1.01. HT 3 core 400 sq mm cable 5 Nos. HT 3 core 300 sq mm cable 5 Nos.
Locating/retrieving of loose cables and LT cable removing and reconnecting of the exisitng cables in the existing panel after raising the panel board height as per site condition…as required.for ITEM No: 2.01. LT 4 Core 240 sq mm cable 2 runs/job x 5 Jobs.
Providing and laying 25 mm X 5 mm GI strip on surface for connections etc. as required. Note 1: The rates quoted for all items shall be incusive of Income Tax,GST TNCWW Cess etc.., as applicable. Note 2: TNCWW Cess@1% and Income Tax2% will be deducted from the bill. Note 3:The tenderers are requested to inspect the site and submit the tender before quoting.
tech_bid_open.pdf
tech_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.86 MB
Tendernotice_2.pdf
PDF • 24.06 MB
Tendernotice_3.pdf
PDF • 0.45 MB
BOQ_299019.xls
BOQ • 0.40 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .