CWE AF BIKANER
HQ CWE AF BIKANER
PROVN OF COMMERCIAL POWER SUPPLY TO PH-II AT AF STN NAL
2024_MES_637966_1
81548/E8
Open Tender
Civil Works
Item Rate
180 days
GE AF NAL
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE AF NAL
₹49,180
Yes
28 Mar 2024
17 Jan 2024
21 Feb 2024
17 Jan 2024
14 Feb 2024
31 Jan 2024
17 Jan 2024 - 25 Jan 2024
Amount
Supply, Installation, testing, Commissioning of 11kV Air Insulated Indoor type Switchgear Panels with maximum system voltage rating of 12kV consisting of 01 incomer (from 3 SQN DSS) of 800 Amp VCB +01 bus coupler of 800 Amp + 01 riser as applicable [Total 03 Nos], Busbar Rating of 1250A, Short Circuit Capacity of 26.3kA. Bus-bars shall have full Voltage Sleeving on it and shall be self-supported type i.e. without any support insulators. The Incomer Panels shall contain Line/Bus PT arrangement. The Panel, Vacuum Circuit Breaker, Vacuum Bottle, Numerical relays shall be of same make as the Panel Manufacturer. Bus bar should be electrolyte copper. The panel shall be tested for IAC AFLR for 26.3kA/1s. The IED (Numerical relay) shall be Complied to 61850 protocol without any external protocol converter. GOOSE (Generic Object Oriented Substation Event) signals shall be freely configurable. WEB HMI feature should be present. Inter-operability test shall preferably shall be done. Proof w.r.t Interoperability shall be submitted by the Manufacturer. The relay shall have integral/Provided with arc-protection based on simultaneous detection of current and light to ensure reduced cubicle damage and increase personal safety. (<15 ms) The relay must support IEC 61850 Edition 1 and Edition 2(with test reports) and shall support HSR/PRP redundancy protocols. It shall comply with international standard of NERC CIP. Operation: Motorised 24 V DC. The Circuit Breaker shall be of floor rolling design with Vacuum bottles, and shall have all fool-proof interlocks as: Interlocks shall be provided to prevent a ‘Closed’ breaker to rack out from ‘Service’ to ‘Test’ /'Isolated’, position or insert a ‘closed’ breaker from ‘Test’ to ‘Service’ position. In either case the breaker contacts must remain in open position. Before racking out the breaker must be fully discharged from any static charge. Switchgear should be SCADA Compatible.
All Panels shall have integral earth Switch with making capacity. VCB Panels shall be from same manufacturer to ensure ease of maintenance after expiry of warranty period. Panels shall be tested for Seismic Zone –IV as NAL Station fall under same earthquake zone. Type test reports shall be submitted for the same. The Switchboard shall be configured as follows: 01 incomer of 800 Amp VCB with PT & CT + 1 bus coupler of 800 Amp VCB with CT+01 riser as applicable). Incomer and Bus Coupler CTs : 200-100/1-1, 15VA, Cl-5P10, Cl-1.0, Incomer VTs : 11000/V3/110/V3/110/3,50VA,Cl-1.0,3P, Incomer IEDs : Feeder Protection and Control Relay, Protections 50, 51, 50N, 51N, 46, 49, 67, 67N, 27, 59, 59N, 95 Measurement for 3I, I0, 3U, U0, Kw, KVA, PF, Hz, Kwh, 16 DI + 10 DO/8 DO, One front RJ45/USB Port, Two Rear FO(LC) Port for IEC-61850 Protocol, Drawout Type with CT Shorting feature. Interlocking for all existing incomer and out going with bus coupler having additional key interlock and hardwire interlock by extending to control wire, closing coil, tripping coil, under voltage relay, NO + NC control and auxiliary for 04 NO + 04 NC element including control wiring up to external connector for control through PLC (soft interlock and auto operation)”. Other necessary items like AC/DC MCBs , Power pack with each panel, TNC Switches, Indication Lamps (R, Y, B, ON, OFF, Spring Charge, Test, Service) shall be considered in the scope of Panel and ”VCB panel, accessories, hardwire interlock and control wiring shall be factory fitted only”. The proposed VCB feeders are to be integrated mechanically as well as electrically with the existing panels and the rate of integration is to be included in the quoted rate. Also it is advised to all bidders to visit the site before quoting the tender. Make: - ABB, Siemens, Schneider
Supply, laying and testing HT cable aluminium conductor, standared compact circular aluminium conductor screened with extruded semi conducting compound, XLPE insulated, insulation screening with extruded semi conducting compound in combination with copper tape, core laid up, innersheath of PVC, galvanised steel flat strip, and overall pvc sheathed cable conforming to IS 7098 (PART-2) 2011 suitable for 11000 Volt (E) grade of cross sectional area 95 Sqmm x 3 core complete all as specified and directed.
Material and labour for jointing and testing HT cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm complete all as specified and directed.
Excavation in trenches, not exceeding 1.5 m wide and n. exc 1.5 m in depth for laying of cable in soft/ loose soil and getting out of excavated material complete all as specified and directed.
Returning, filling in including spreading, leveling, watering and well ramming in layers n. exc 25 cm apart for soft/loose soil complete all as specified and directed.
Material and labour for dry Sand cushioning in trenches for protection of cable including watering and consolidation complete all as specified and directed. Note: - Punned thickness shall be considered for measurement purpose.
Supply and laying unreinforced precast concrete cable cover class HVP, type -I with peak of size 300mmx180mmx40mm laid in trenches over underground cables complete all as specified and as directed.
Removing of surplus excavated material to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified and directed by Engineer-in-Charge.
Leo Air and Power Solution pvt Ltd.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .