Loading…
New: tenders and results on WhatsApp
New: Find tenders, results and companies on WhatsApp, by text or voice note
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹41.1 LAccepted-AOC MES CHOWPATHY PO HASIMARA DISTT JALPAIGURI PIN 735215 WB | HASIMARA | JALPAIGURI | WB | 735215 | L1 | Accepted-AOC BEING L1 BIDDER | |
| 2 | L2₹42.8 L+₹1.0 L (2.40%)Rejected-Finance SUBHASINI TEA ESTATE HASIMARA PS JAIGOAN DIST ALIPURDUAR WB PIN 735215 | ALIPURDUAR | WEST BENGAL | 735215 | L2 | Rejected-Finance Other than L1 | |
| 3 | L3₹45.3 L+₹3.5 L (8.41%)Rejected-Finance | L3 | Rejected-Finance Other than L1 | |
| 4 | L4₹45.9 L+₹4.1 L (9.75%)Rejected-Finance | L4 | Rejected-Finance Other than L1 | |
| 5 | L5₹46.3 L+₹4.5 L (10.7%)Rejected-Finance | L5 | Rejected-Finance Other than L1 |
Tender Value
₹40.5 L
EMD Value
₹81,000
Closing Date
16 Nov 2024, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (AF) HASIMARA
GE (AF) HASIMARA, PO-HASIMARA, DIST- ALIPURDUAR, PIN-735215
ADDN/ALTN OF UG LT ELECTRIC SUPPLY SCHEME IN WSA AT AFS HASI MARA
2024_MES_681397_1
C/8825/2024-25/E8
Open Tender
Civil Works
Item Rate
180 days
GE (AF) HASIMARA
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE (AF) HASIMARA
₹81,000
Yes
22 Nov 2024
25 Oct 2024
18 Nov 2024
25 Oct 2024
16 Nov 2024
9 Nov 2024
Amount
Supply, fabricating, installing, testing and commissioning of outdoor type LT feeder pillar box of suitable size factory fabricated, cubical panel, wall/floor mounted single door, dust and vermin proof CPRI approved made out of 3.15mm thick CRCA sheet alongwith both side cable alley of width not less than 200mm each side for termination of cable with provision for top and bottom cable entry mounting on 50 x 50 x 5mm Angle iron supports at the base duly painted with synthetic enamel paint and panel board with front and back opening and locking arrangement compete including finishing with two coats of powder coated paint of approved shade over one coat of red oxide zinc chrome primer including all busbar of copper bus bar strip 40mm x 10mm for three phase 4 wire 415 Volts, 50 Hz, AC supply including suitable size copper conductor control wiring, necessary cable glands, lugs etc, proper arrangement for ventilation with and including the following accessories at WSA sub stn including taking down old unserviceable LT panel/feeder pillar box of any size : INCOMING: (i) MCCB 250 Amps, AC 4 pole 415 Volt 36 KA Breaking Capacity thermal magnetic release range 250-320A, with suitable rotary extendable handle for operation of MCCB-01 No. (ii) On load motorised change over open execution AC 4 pole 250 Amp, 415 volt with auto/manual function with extended rotary handle for operation of change over including making auto/manual/DG/Mains supply 01 No. OUTGOING: (i) MCCB 160 Amps, AC 4 pole 415 Volt 25 KA Breaking Capacity thermal magnetic release range 160-200A, with suitable rotary extendable handle for operation - 05 Nos (ii) MCCB 63 Amps, AC 4 pole 415 Volt 25 KA Breaking Capacity thermal magnetic release range 63-80A, with suitable rotary extendable handle for operation - 02 Nos. (iii) Isolator 04 pole 80 Amp - 04 Nos (iv) MCB SPN 63 Amp 'C' curve, 10 KA - 08 Nos. (v) Digital volt meter with all accessories for incoming -01 No. (vi) Digital Ammeter with all accessories for incoming and each outgoing - 08 Nos. (vii) Phase indicating lamp LED Type (R-Y-B) for incoming and outgoing connections- 24 Nos.
Supply, fabricating, installing, testing and commissioning of outdoor type LT feeder pillar box of suitable size factory fabricated, cubical panel, wall/floor mounted single door, dust and vermin proof CPRI approved made out of 3.15mm thick CRCA sheet alongwith both side cable alley of width not less than 200mm each side for termination of cable with provision for top and bottom cable entry mounting on 50 x 50 x 5mm Angle iron supports at the base duly painted with synthetic enamel paint and panel board with front and back opening and locking arrangement compete including finishing with two coats of powder coated paint of approved shade over one coat of red oxide zinc chrome primer including all busbar of copper bus bar strip 40mm x 10mm for three phase 4 wire 415 Volts, 50 Hz, AC supply including suitable size copper conductor control wiring, necessary cable glands, lugs etc, proper arrangement for ventilation with and including the following accessories at WSA around fencing including taking down old unserviceable LT panel/feeder pillar box of any size : INCOMING: (i) MCCB 160 Amps, AC 4 pole 415 Volt 25 KA Breaking Capacity thermal magnetic release range 160-200A, with suitable rotary extendable handle for operation - 01 No. OUTGOING: (i) MCCB 100 Amps, AC 4 pole 415 Volt 25 KA Breaking Capacity thermal magnetic release range 100-125A, with suitable rotary extendable handle for operation - 06 Nos (iii) Isolator 04 pole 80 Amp - 04 Nos (iv) MCB SPN 63 Amp 'C' curve, 10 KA - 08 Nos (v) Digital volt meter with all accessories for incoming -01 No. (vi) Digital Ammeter with all accessories for incoming and each outgoing - 07 Nos. (vii) Phase indicating lamp LED Type (R-Y-B) for incoming and outgoing connections- 21 Nos.
M&L for earthing complete with GI earth plate electrode 60 × 60cm × 6mm thick , buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to existing earth lead strip by means of bolts, nuts, check nuts and washers of brass or HS steel all as shown in electrical plate No. 3 connected to earthing test point and and necessary excavation and earth work PCC (1:3:6) type C-1 as earth pit with pre-cast RCC (1:2:4) type B-1 cover slab size 400 x 400 x 50mm reinforced with 8mm dia TMT bar, 100mm c/c both ways including one handle made of 12mm dia including providing charcoal or coke and common salt in alternate layer of 15cm compacted thickness all around the earth electrode with funnel and 20mm bore galvanized iron watering pipe (light grade) wire mesh, copper lugs, complete in all respect, including galvanised iron earth strip 25 x 4mm, protected by 40mm bore (medium grade) galvanized iron pipe up to earthing test point as directed, incl disposal of spoil to a distance not exc. 50 mtr and necessary testing on completion including dismantling of old unserviceable earthing of any description, complete all as specified and as directed. Note : GI strip from earthing to LT panel/Bus bar shall deemed to be included in the unit quoted rate.
Supply, fabricating, installing, testing and commissioning of outdoor type LT bus bar box of size not less than 900 mm (L) x 900mm (B) x 450mm (D) of suitable size, factory fabricated, cubical panel, floor mounted double door, dust and vermin proof CPRI approved made out of 3.15 mm thick CRCA sheet mounting on 40 x 40 x 5mm angle iron supports at the base duly painted with synthetic enamel paint and panel board with front and back opening and locking arrangement compete including finishing with two coats of powder coated paint of approved shade over one coat of red oxide zinc chrome primer including all busbar of copper bus Bar strip 40mm x 10mm for three phase 4 wire 415 volts, 50 Hz, AC supply including suitable size cable glands, lugs etc, proper arrangement for ventilation including taking down old unserviceable bus bar box of any type and size, complete all as specified and directed.
Taking down/out unserviceable UG cables of any cross sectional and connection including bricks, GI pipes etc of any description, laid in trenches and/or fixing with walla/poles, complete all as specified and directed.
Relaying of serviceable LT UG cables carefully obtained from loop of existing panel of any cross sectional and connection including laid in trenches/duct/DWC pipe/fixing with walla/poles, complete all as specified and directed.
Excavation in trenches n. exc. 1.5m wide and n. exc. 1.5m in deep for foundation etc. or for shaft, wells, cesspits, manhole, pair house or for foundation of pole/stay etc. n. exc. 10 Sqm on plan and getting out in soft/loose soil, complete all as specified and directed.
Returning filling in incl spreading, leveling watering and well ramming in layers not exceeding 25cm in soft/loose soil, complete all as specified and directed.
Removing excavated materials to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 metre above the starting point in any type of soil, complete all as specified and directed.
Supply & laying double walled corrugated (DWC) HDPE duct pipe of 63mm (inner dia) conforming to IS approved colour complete with fittings for cable protection, complete all as specified and directed.
Supply & laying double walled corrugated (DWC) HDPE duct pipe of 32mm (inner dia) conforming to IS approved colour complete with fittings for cable protection, complete all as specified and directed.
M&L for 50mm bore GI tubing, light grade, with necessary fittings such for cable protection, laid in trenches, complete all as specified and directed. Note: Boring/Earth work shall be measured and paid separately.
M&L for 40mm bore GI tubing, light grade, with necessary fittings such for cable protection, laid in trenches, complete all as specified and directed. Note: Boring/Earth work shall be measured and paid separately.
Supply, laying, jointing and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 185 Sqmm 3.5 core, complete all as specified and directed.
All as per item No. 14.00 here-in-before but cross sectional area 95 Sqmm 3.5 core, complete all as specified and directed.
All as per item No. 14.00 here-in-before but cross sectional area 25 Sqmm 4 core, complete all as specified and directed.
Horizontal boring under the road/pavment/hardstanding (with manual method) below 1mtr from the road surface and dia of hole not exc 100mm, with out damaging the existing road, getting out and disposal of soil to a distance not exceeding 50m from the site of work and making good both the ends, complete all as specified and directed.
Note: An amount of Rs 66,200.00 on account of Credit Schedule for schedule 'A' part - II shall be deducted from the total amount of BOQ to arrive at the contract sum.
M/S. VINITA CONSTRUCTION (BID ID -3165830)
M/S DEY ENTERPRISE (BID ID -3165820)
M/S ROY ENTERPRISE (BID ID -3166827)
M/S ANIL KUMAR BAUL (BID ID -3166080)
MAA TARA TRADING (BID ID -3166627)
M/S SARKAR ELECTRIC (BID ID -3164749)
BHARAT ELECTRIC (BID ID -3166818)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .