| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.0 LAccepted-AOC 1101 A WING SACHDEV COMPLEX JANGAL MANGAL RAOD BHANDUP W MUMBAI 400078 | MUMBAI SUBURBAN | MAHARASHTRA | 400078 | L1 | Accepted-AOC BEING L1 | |
| 2 | L2₹36.8 L+₹12.9 L (54.0%)Rejected-Finance SHOP NO 12 KHOPKAR APARTMENT KUMBHARAWADA URAN DISTT RAIGAD 400 702 | URAN | RAIGAD | MAHARASHTRA | 400702 | L2 | Rejected-Finance BEING L2 |
Tender Value
₹33.5 L
EMD Value
₹67,000
Closing Date
28 Oct 2023, 6:00 pmClosed
GE AF THANE
Office of Military Engineer Services ,Garrison Engineer (AF) Thane, Kolshet Road, Sandoz Baugh Post, Thane 400607
REPAIR, MAINTENANCE CEILING FAN, EXHAUST FAN,WALL MOUNTED FAN, PEDESTRIAL FAN, METER, INTERNAL WIRING, FITTING FIXTURE,EARTHING,LIGHTNING ARRESTER ,SERVICE CONNECTION,and certain maintenance works at AFS Khills under GE AF Thane
2023_MES_621121_1
8304/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
THANE
AS PER NIT
8 documents required · 8 mandatory
₹500
GE AF THANE
₹67,000
Yes
10 Feb 2024
29 Sept 2023
30 Oct 2023
29 Sept 2023
28 Oct 2023
16 Oct 2023
29 Sept 2023 - 16 Oct 2023
Amount
Taking down carefully copper/aluminum point wiring (light, fan, socket or power) complete including fixture and fittings such as switches, sockets, light fittings, MCB DBs,out let boxes etc.removing material for taking credit and making good disturbed surfaces of walls, floors, ceilings etc,complete all as specified and as directed by Engr-in-charge.
M&L for point wiring with 1.5 Sqmm (nominal area) FRLSH insulated multi-stranded copper conductor confirming to IS 694 in and including Medium duty PVC casing capping (ISI marked)/PVC conduit including fitting & accessories, with MS concealed terminal boxes with 3mm thick laminated BakeliteHylum sheet top cover for mounting switch, socket etc including 1.5 Sqmm stranded copper conductor with green PVC insulated flame retardant copper conductor earth continuity conductor 1.5 Sqmm connected to the common earth dolly and controlled by one switch ,complete all as specified and as directed by Engr-in-charge. Of the following:-
One Light/Bell/ceiling fan & exhaust fan point controlled by one switch .
One 3 pin 5 Amps socket out let on independent board
One 3 pin 5 Amps socket out let on same board
Ditto-All as per Srl item No-2 above but with 2.5 Sqmm wire for 15 Amp socket outlet on independent board
Supply & Fix switch piano flush button single pole one way 5 Amps, 250 V ,complete all as specified and as directed by Engr-in-charge.
Supply and Fix Bell push button flush type 5 Amps ,complete all as specified and as directed by Engr-in-charge.
Supply and Fix switch piano flush button single pole one way 15 Amps, 250 V ,complete all as specified and as directed by Engr-in-charge.
Supply and Fix socket outlet 2 in 1,3 pin, 5A flush type 220 V ,complete all as specified and as directed by Engr-in-charge.
Supply and Fix switch socket combination 2 in 1,3 pin, 5 Amps flush type 220 V ,complete all as specified and as directed by Engr-in-charge.
Supply and Fix socket outlet 2 in 1,6 pin, 5/15Amps flush type 220 V ,complete all as specified and as directed by Engr-in-charge.
Supply and Fix switch socket combination 2 in 1,6 pin, 5/15Amps flush type 220 V ,complete all as specified and as directed by Engr-in-charge.
Supply and Fix and fix bell buzzer, Ding Dong AC 230 volt single pole ,complete all as specified and as directed by Engr-in-charge.
Supply and Fix fan regulator Electronic type step type for 400 watts ,complete all as specified and as directed by Engr-in-charge.
Supply and Fix Modular switch 1 way 6A,1 module, 220 V ,complete all as specified and as directed by Engr-in-charge.
S&F, in repair, Modular switch 1 way 16A,1 module, 220 V ,complete all as specified and as directed by Engr-in-charge.
S&F, in repair, Modular socket 6A-2/3 pin combined 2 module flush type 220 V ,complete all as specified and as directed by Engr-in-charge.
S&F, in repair, Modular socket 6A/16A-2/3 pin combined 2 module flush type 220 V ,complete all as specified and as directed by Engr-in-charge.
S&F, in repair, Modular switch socket combination 16A,6 pin.3 module flush type 220 V ,complete all as specified and as directed by Engr-in-charge.
S&F, in repair, Modular Bell push button flush type 5 Amps ,complete all as specified and as directed by Engr-in-charge.
S&F, in repair,Modular fan regulator Electronics step type 120 watts 2 module and connecting ,complete all as specified and as directed by Engr-in-charge.
S&F, in repair,Modular white cover plate with frame suitable for 1 module ,complete all as specified and as directed by Engr-in-charge.
S&F, in repair ,Modular white cover plate with frame suitable for 3 module ,complete all as specified and as directed by Engr-in-charge.
S&F, in repair , Modular Metal flush box suitable for 1/2 modul. ,complete all as specified and as directed by Engr-in-charge.
S&F, in repair ,Modular Metal flush box suitable for 3 module. ,complete all as specified and as directed by Engr-in-charge.
S & F ,in repair, Modular white cover plate with frame suitable for 4 module ,complete all as specified and as directed by Engr-in-charge.
S & F ,in repair, Modular white cover plate with frame suitable for 6 module ,complete all as specified and as directed by Engr-in-charge.
S & F ,in repair, Modular white cover plate with frame suitable for 8 module ,complete all as specified and as directed by Engr-in-charge.
S & F ,in repair, Modular Metal flush box suitable for 4 module ,complete all as specified and as directed by Engr-in-charge.
S & F ,in repair, Modular Metal flush box suitable for 6 module, complete all as specified and as directed by Engr-in-charge.
S & F ,in repair, Modular Metal flush box suitable for 8 module, complete all as specified and as directed by Engr-in-charge.
S&F, in repair ,Ceiling rose, surface bakelite, 65mm x 50mm two to three terminals. ,complete all as specified and as directed by Engr-in-charge.
S&F, in repair , capping casing 20mm width,complete all as specified and as directed by Engr-in-charge.
S&F, in repair , lamp holder,PVC/Polycarbonate type with back plate suitable for batten fitting ,complete all as specified and as directed by Engr-in-charge.
S&F in replacement of Batten type LED light fitting 1x18/20watt 4 feet long including LED tube with driver complete suitable for fixation on wall/roof with body robust, corrosion resistant, superior finish and without any cracks or through holes. The system wattage of fitting should not be more than 18 watt= 10%, surge protection of minimum 2 KV power factor should be more than 0.90 cool while colour, total hormonic distoration (THD) should not be more than 15% lumen output should not be less than 1700 lumens, total input voltage range 140-280V AC, colour rendering index should not be less than 80, Corelated colour should be minimum 6000 degree Kelvin. ,complete all as specified and as directed by Engr-in-charge.
S&F in replacement of Batten type LED light fitting 1x9/10 watt 2 feet long including LED tube with driver complete suitable for fixation on wall/roof with body robust, corrosion resistant, superior finish and without any cracks or through holes. The system wattage of fitting should not be more than 18 watt= 10%, surge protection of minimum 2 KV power factor should be more than 0.90 cool while colour, total hormonic distoration (THD) should not be more than 15% lumen output should not be less than 1700 lumens, total input voltage range 140-280V AC, colour rendering index should not be less than 80, Corelated colour should be minimum 6000 degree Kelvin. ,complete all as specified and as directed by Engr-in-charge.
S&F in replacement of Batten type LED decorative up to light fitting 15 watt round including LED bulb complete suitable for fixation on wall/roof with body robust, corrosion resistant, superior finish and without any cracks or through holes complete all as specified and as directed by Engr-in charge. ,complete all as specified and as directed by Engr-in-charge.
S&F in replacement of energy efficient square surface/ceiling mounted LED down 2x2 luminaire 34/36 watt white powder coated CRCA housing with LED seamless front frame with flat white high transmission acrylic cover complete all as specified and as directed by the Engr- in- Charge. ,complete all as specified and as directed by Engr-in-charge.
S&F in replacement of energy efficient LED mounted panel 12 watt white powder coated CRCA housing with LED seamless front frame with flat white high transmission acrylic cover complete all as specified and as directed by the Engr- in- Charge. ,complete all as specified and as directed by Engr-in-charge.
S&F in replacement of LED bulb 5/7/9 watt, 230 Volt, 50 Hz, complete all as specified and as directed by the Engr- in- Charge. complete all as specified and as directed by the Engr- in- Charge.
S&F in replacement of energy saver LED bulb 2.7 watt,E27/B-22 230 Volt, 50 Hz, complete all as specified and as directed by the Engr- in- Charge. complete all as specified and as directed by the Engr- in- Charge.
S&F in replacement of energy efficient DRONE LED 32 watt round complete suitable for fixation on wall/roof with body robust, corrosion resistant, superior finish and without any cracks or through holes complete all as specified and as directed by Engr-in charge. ,complete all as specified and as directed by Engr-in-charge.
S&F in replacement of Energy saving 9/10 watt environmental friendly, ultra modern, energy saving, surface mounted, decorative oval bulk head edge-lit LED luminaire comprising of high brightness LEDs, IP 65 protection fixed on wall complete all as specified and as directed by Engineer-in-charge.
Taking down the ceilling fan/wall mounted fan,Exhaust fan from ceilling,wall,cleaning the dust,drit ,greashing,servicing ,repairing and refixing the original position ,complete all as specified and as directed by Engr-in-charge. Note:- Necessary spare for repairing will be measured and paid in respective items.
Re winding ceilling fan with super enameled copper wire suitable gauge to get designed condition of speed for the particular make of fan including insulating, varnishing, providing sleeves to copper wire and testing for good running condition of sweep1200/1400 mm ,220 volt ,50 HZ,single phase ,complete all as specified and as directed by Engr-in-charge.
Re winding Exhaust fan with super enameled copper wire suitable gauge to get designed condition of speed for the particular make of fan including insulating, varnishing, providing sleeves to copper wire and testing for good running condition of sweep 230/300/400 mm ,220 volt ,50 HZ,single phase
Re winding wall mounted fan with super enameled copper wire suitable gauge to get designed condition of speed for the particular make of fan including insulating, varnishing, providing sleeves to copper wire and testing for good running condition of sweep 400 mm ,220 volt ,50 HZ,single phase ,complete all as specified and as directed by Engr-in-charge.
Supply only Gun metal bush suitable for particular make of fan of 1200mm /1400 mm sweep ,complete all as specified and as directed by Engr-in-charge.
Supply only metal bush suitable for particular make of exhaust fan of 300/380/400 mm sweep ,complete all as specified and as directed by Engr-in-charge.
Supply only ball bearing suitable for particular make of fan of 1200 mm /1400 mm sweep ,complete all as specified and as directed by Engr-in-charge.
Supply only ball bearing suitable for particular make of exhaust fan of sweep 300mm/450 mm complete all as directed
Supply only 2.5 Mfd/3.15 Mfd capacity ,complete all as specified and as directed by Engr-in-charge.
Supply only ceiling fan blade for 1200 mm /1400 mm sweep fan as per existing ceiling fan and all as directed by Engr-in-Charge.
Supply only Ceiling fan canopy as per existing and all as directed by Engr-in-Charge.
Supply only down rod suitable for ceiling fan of any sweep and all as directed by Engr-in-Charge.
Supply only Capacitor 4 Mfd suitable for exhaust fan of sweep 300mm/450mm complete all as directed.
Supply only Capacitor 1.5 Mfd suitable for exhaust fan of any size complete all as directed.
M&L for repair/replacement of cuircuit board of BDLC fan of 1200 mm/1400 mm sweep complete all as specified and directed.
Supply only stainless steel nut ,bolt with double washer,ruber reel & quarter pin complete all as specified and directed.
Supply and fixing in replacement of LED light fitting 1x16 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum hosing with heat resistant toughened glass with LED tube light fixtures driver, holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size ,complete all as specified and as directed by Engr-in-charge.
Material and labour for earth pit chember of size 0.6mx0.6mx0.6m made with PCC 1:2:4 type B-2 including HDPE earthing pit cover inspection chember of size 200 mm depth, 300mm length and300mm width ,complete all as specified and as directed by Engr-in-charge.
M&L Checking of any breaking in the Link of Earth Strip/Wire of Galvanised/ Copper/Aluminium any size and jointing them by Exothermic Welding or Brazing, complete all as specified and as directed.
Taking down unserviceable and dislocated Copper/aluminium strip of any size from floor of any size height ,complete all as specified and as directed by Engr-in-charge.
S&F copper strip of 20 x 3.15 mm as roof conductor and down conductor till test point all as directed. Note-Copper strip to be jointed through brazing only ,complete all as specified and as directed by Engr-in-charge.
S&F aluminium strip of 25 x 3.15 mm as roof conductor and down conductor till test point all as directed. Note-Galvanised strip to be jointed through brazing only
S&F GI strip of 32x6mm as roof conductor and down conductor till test point all as directed. Note-Galvanised strip to be jointed through brazing only
Taking down unserviceable and dislocated air termination rod of any type from floor of any size ,complete all as specified and as directed by Engr-in-charge.
S&F single pointed soild copper rod 300mm long and 12mm dia fixed on suitable flat mounted plate and connected with roof/down conductor ,complete all as specified and as directed by Engr-in-charge.
S&F single pointed soild Aluminium rod 300mm long and 12mm dia fixed on suitable flat mounted plate and connected with roof/down conductor ,complete all as specified and as directed by Engr-in-charge.
Re-Fixing Air Termination Single Pointed copper/aluminium Rod after taking down LA strip complete all as specified and as directed. NOTE : If threaded of the Rod is damaged then Contractor will be responsible for cutting of thread for fixing the Rod.
M&L for Cement Concrete 1:2:4 (20mm graded stone aggregate) Block 300x300x300mm and necessary Fixing Arrangement at Roof, complete all as specified and as directed.
S&F Porcealing insulators in replacement for fixing Copper strip on wall / Roof bldg with necessary screws washers and nut bolts etc all Specified . Note - Rates are inclusive of copper screws with washers for fixing copper strip on porciline insulator with minimum size 1 inch and maximum size 1.5 inch with max external dia of screw is 8mm and 2 nos of GI nut for fixing insulator on wall all as per site requirement ,complete all as specified and as directed by Engr-in-charge.
S&F,in repair, single pointed soild copper rod 1 m long and 12mm dia fixed on suitable flat mounted plate and connected with roof/down conductor ,complete all as specified and as directed by Engr-in-charge.
Taking down unserviceable test point terminals block and supply and fixing the same. The terminal block made with gun metal size 75x75x25mm drilled and screwed including 3 nos 8mm dia 25mm long hex head of gun metal screw ,complete all as specified and as directed by Engr-in-charge.
M&L for earthing complete with Copper earth plate electrode 600x 600x 3 mm buried directly in ground with top edge of the plate not less than 1.5 mtrs below normal gound level and connected to earth test point by means of copper Strip of size 20x3 mm all as specified and shown in electric plate No 3 of MES SSR Part-I 2009 including earthwork, PCC chamber, CI cover, protection and watering pipe, funnel, mesh etc all as required at site and all as directed. Note: (i). 7.5 RM Copper strip in deemed to be included in quoted rates beyond 7.5 RM strip shall be measured and paid separately. (ii). Earth resistance of earth pit should be less than 2 Ohms. On testing after completion if the desired earth resistance is not obtained the earthing will be redone at no extra cost. (iii) Rate quoted by the tenderer is deemed to include salt & Charcoal upto & above 450 mm top of Copper plate. (iv) Soil registance test if required shall be the responsbility of contractor without any extra cost.
M & L for Earthing complete with galvanised steel earth plate electrode of size 600 x 600 x 6mm thick burried directly in ground earth pit not less than 2.25 mtr deep below normal ground level with top edge of the plate vertically to a depth of not less than 1.5 mtr below ground level connection to and including GI strip 25×4mm from earth plate to main switch board including necessary GI bolts, nuts, check nuts, washers, thimble etc to the extend 7.5 mtr as earth lead by means of GI bolts & nuts etc, connecting to LT panel wlith provision of charcoal and salt all as per electrical plate No 3 of SSR Part-I including water arrangement with GI pipe 20mm dia (medium grade) excavation and earth work returning , filling, ramming and remove of soil to a distance not exc 50 mtr, make good to match with existing surface and testing on completion.Note:1.After completion if test results are nor satisfied, earthing should be redone by contractor without any extra cost. 2. Contractor should quote the rate deemed to be included with testing.
S&F,in repair, copper strip of 32 x 6 mm with saddles and fixing screws etc. for roof conductors and down conductors above ground Complete all as specified and directed by Engr-in-Charge.
S&F Bib taps, cast copper alloy with crutch or butterfly handle, screwed down, screwed for iron pipe or for brass ferrule and fixed on 15 Bore dia of pipe in mm complete all as specified and directed.
S&F Mild Steel Sheet of size approximate 300x200x1.6mm thick Sheet Egg type, Half round type, Rectangular type and Triangular type with welded 1ʺ (Inch) dia 2ʹ (Feet) long Mild Steel Pipe with duly different Synethic Enameled Paint cutting of Equipment Earthing/ Lighting Arrester Earthing/ Signal Earthing, etc. complete as specified duly painted as specified and marking of Earth Plate Number/ Description of Earthing/Type of Earthing on Plate with White Paint including Earth Plate No. and Earthing Resistance with Earthing Check Date and Earthing Check Due Date including taking down unserviceable one, complete all as specified and as directed.
Supply only MgSo4, complete all as specified and directed by Engr-in-Charge.
Supply only Funnel with wire mesh of size suitable for 20 mm dia watering pipe , complete all as specified and directed by Engr-in-Charge.
S&F Galvanised Iron Tubing/Pipe 40/50 mm bore (dia), light grade for Strip Protection, fixed in Walls/Floors with suitable type of Clamps, etc. including taking down unserviceable GI Tubing/Pipe, complete all as specified and as directed.
Supply only Hand Gloves suitable for operation of 33 KV HT Switch Gear complete all as specified and directed.
M&L for periodical testing and measuring the earth resistance value of the existing earthings / Down conductor / air terminal by means of wheat stone bridge method after disconnecting the earth continuity conductor from the test point , applying secondary voltage across the terminals, maintaining proper record of the measurement in presence of the users rep, MES rep, submitting the test records, pouring saline water in the earth pit to achieve low earth resistance, observing the same complete for Quarterly Building earthings,L2/L3 eqpts/E&M installations/Lightning arresters test ,complete all as specified and as directed by Engr-in-charge. (Note -(i) Item rate include the cleaning dust/dirt from earth pit chamber, common salt and funnel shall be measured and paid for separately under respective items as supply only (ii) Equipments used for measuring shall be arranged by contractor at his own cost nothing shall be paid extra)
Taking down sub main wiring of any size complete and making good disturbed surface of walls/floors etc ,complete all as specified and as directed by Engr-in-charge.
M&L Sub-main Wiring with 2-Runs of 6 Sqmm (nominal area) 1100 Volt, PVC insulated unsheathed FRLS multi-stranded Single Core Copper Conductor Cable and 1-Run of 6 Sqmm (nominal area) 1100 Volt, PVC insulated unsheathed FRLS multi-stranded Single Core Copper Conductor Cable (Green Colour) as Earth Continuty along with the Wiring drawn in EXISTING CONDUIT/PVC CASING & CAPING, complete all as specified and as directed. Note : (i) Three lenght of wire along with conduit will be measured as one Length.
All as per item no 84 herein before but of size 2X4 sq mm and 1X2.5 sqmm
All as per item no 84 herein before but of size 2X2.5 sq mm and 1X2.5 sqmm
All as per item no 84 herein before but of size 4X16 sq mm and 2X10 sqmm
M & L submain wiring with two single core through FRLSH PVC insulated unsheathed stranded copper conductor 6 sqmm (nominal area) drawing through PVC capping casing and 4 sqmm stranded copper conductor cable PVC insulated and unsheathed (green colour) 1100 volts grade for earth continuity conductor and connecting with main earth dolly Note : (i) Three lenght of wire along with conduit will be measured as one Length. (ii) Rates are deemed to included with cutting chases for conduit and sinking's for boxes and making good to walls, floors etc.
All as per item no 88 herein before but of size 2X4 sq mm and 1X2.5 sqmm
All as per item no 88 herein before but of size 2X10 sq mm and 1X6 sqmm
S&F PVC Conduit 25mm dia, medium grade with necessary Conduit Accessories such as Tee, Bend, Elbow, Junction Box, etc. ISI marked including taking down/out unserviceable PVC Conduit with Fittings, complete all as specified and as directed.
S&F PVC Casing & Cappings, ISI marked, heavy duty of size 25mm with all Fittings including taking down old unserviceable one, complete all as per specified and as directed.
Taking down & Supply and fixing, testing and commissioning Single phase electronic tamperproof energy meter LCD display, static Energy meter as per IS specifications IS 13779, CBIP 88, & IEC 62052-11, IEC 62052-21 suitable for range 10 to 60 Amps with optical port, class 1.0 accuracy duly encased in PVC housing in and including multi standard PVC insulated copper conductor cable of 6 Sqmm cross sectional area with bottel lugs for connections all as specified and directed by Engr-in-charge.
S&F in replacement of LED bulding security light fitting of 25/30 Watt including LED lamps complete with body robust,corrosion resistant,superior finish and without any cracks or through holes, made in a single piece by high pressure die cast aluminium alloy.The luminaries shall be monolithic construction totally enclosed dust and water proof with minimum IP -66 protection as per IS - 10322-1982(Part -I) with latest amendments and input voltage range 140 - 270 V, AC, frequency 50 - 60 Hz ,P.F should be more than 0.9 with Total Harmonic Distoration THD (I) less than 10%, cool white colour and lamp starting time should not be more than 10 second. Fitting should be provided with 10 KV surge protection Driver should be constant current constant voltage driver .Driver should have high voltage withstanding capacity upto 300 V, AC. Driver should also have double phase protection, no load , open circuit and short circuit protection. LED light fitting should be suitable for ambient temperature from -10 degreeCentrigrade to 50 degree Centrigrade and humidity level 10% to 90 % RH. Covers should be polycarbonate/toughened glass to ensure minimum IP 66 degree protection. Cover should not degrade due to heating and ageing. The efficiency of LED luminaries system shall be more than 85 lumens per watt and must be certified by the LM-79 test report. ,complete all as specified and as directed by Engr-in-charge.
Taking down unserviceable DB/MCCB/MCB of any capacity and making good disturbed surface of wall/floor complete all as specified all as directed.
S & F Loadline Distribution board, TP&N vertical, with Bus bars, 200A, 415V CapNetural links,blanking plates, double door 8 way, with MCCB 63 to 100 Amps as incommer and SP/DP/TP MCB as outgoing and electrically connecting up ,complete all as specified and as directed by Engr-in-charge.
S & F Loadline Distribution board, TP&N vertical ,with Bus bars, 200A, 415V Netural links,blanking plates, double door 4 way, with MCCB 63 to 100 Amps as incommer and SP/DP/TP MCB as outgoing and electrically connecting up ,complete all as specified and as directed by Engr-in-charge.
S & F Distribution board, SP&N ,Prewired ,Netural links,blanking plates, double door 4 way, with provision for MCB SP&N as incommer and SP/DP MCB as outgoing and electrically connecting up ,complete all as specified and as directed by Engr-in-charge.
S & F Distribution board, SP&N ,Prewired ,Netural links,blanking plates, double door 6 way, with provision for MCB SP&N as incommer and SP/DP MCB as outgoing and electrically connecting up ,complete all as specified and as directed by Engr-in-charge.
S & F Distribution board, SP&N ,Prewired ,Netural links,blanking plates, double door 8 way, with provision for MCB SP&N as incommer and SP/DP MCB as outgoing and electrically connecting up ,complete all as specified and as directed by Engr-in-charge.
S & F MCB SP 6 to 32 Amps 240 volts 50 HZ having 10 KA ,complete all as specified and as directed by Engr-in-charge.
S & F MCB SPN 40 Amps 240 volts 50 HZ having 10 KA ,complete all as specified and as directed by Engr-in-charge.
S&F MCB SPN 240 volt,50Hz,63 Amp,C Curve,10kA breaking capacity ,complete all as specified and as directed by Engr-in-charge.
S & F MCB TPN 40 Amps 240 volts 50 HZ having 10 KA ,complete all as specified and as directed by Engr-in-charge.
S&F MCB TPN 415 volt 63 Amp,"C" Curve 16kA breaking capacity ,complete all as specified and as directed by Engr-in-charge.
S&F DB box with protected power unit rating 16-25 Amps 240volt 50HZ as per Havells cat part no-DHDUCDP0253016-25 or equivalent as per Approved.
S & F RCCB DP 6 Amps 240 volts 50 HZ having ,complete all as specified and as directed by Engr-in-charge.
Taking down the unserviceable MCCB, Supply and fixing MCCB TP pole with thermal Release range 40/63 Amps, 18KA, 415V, 50 Hz including extension bar for connection cable, ,complete all as specified and as directed by Engr-in-charge.
Taking down the unserviceable MCCB, Supply and fixing MCCB TP pole with thermal Release range 100-125 Amps, 18KA, 415V, 50 Hz including extension bar for connection cable, ,complete all as specified and as directed by Engr-in-charge.
M & L for Earthing complete with galvanised steel earth plate electrode of size 600 x 600 x 6mm thick burried directly in ground earth pit not less than 2.25 mtr deep below normal ground level with top edge of the plate vertically to a depth of not less than 1.5 mtr below ground level connection to and including 4mm dia (8 SWG) GI earth wire from earth plate to main switch board including necessary GI bolts, nuts, check nuts, washers, thimble etc to the extend 7.5 mtr as earth lead by means of GI bolts & nuts etc, connecting to DBs /LT Panel wlith provision of charcoal and salt all as per electrical plate No 3 of SSR Part-I including water arrangement with GI pipe 20mm dia (medium grade) excavation and earth work returning , filling, ramming and remove of soil to a distance not exc 50 mtr, make good to match with existing surface and testing on completion.Note:1.After completion if test results are nor satisfied, earthing should be redone by contractor without any extra cost. 2. Contractor should quote the rate deemed to be included with testing.
S&F sheet metal plug & socket DB, SP, with a two pin and earth plug with socket, 230 Volts with & including one MCB SP ‘C’ Curve 10 kA, 20 Amps complete all as specified and directed by Engineer-in-charge.
AMC FOR DG set 500 KVA Make Kirloskar through authorise service agency of OEM. Location: Site AF Stn Kanheri Hills, Note:- spares required for above maint will be measured and paid separately under relevent items . Scope Of Work : Scope Of Work :- (a) Engine Cooling System :- Checking of radiator conditions (check for radiator clogging, cooling fins condition, V belts, etc. Checking of K-Cool Super level, piping corrosions & any sign of radiator leaks. Checking of hoses & connections deterioration / wear & tear. C Checking of fan pulley mis-alignment / deterioration, defective bearings, corroded surface, grease condition. Checking the water pump leaks, noisy operation, abnormal vibration, impeller defects, cracked housing, worn out shaft, etc Checking of belts tension & deterioration. Checking thermostat for proper functioning. Checking water level sensor in radiator for K-Series Engines . b)Engine Fuel System :- Checking fuel lines connections (any signs of fuel leak, loose connections, corroded piping, fuel restrictions, defective clamps, deteriorated hose, etc.). Checking governors & controls conditions (any sign of deterioration, loose connections & system malfunction/ not responding etc.). Checking governors & controls conditions (any sign of deterioration, loose connections & system malfunction/ not responding etc.) Checking actuator of electronic governing system. Checking priming pump condition. Checking fuel filter condition – replace the filters as found necessary. Checking water separator condition. Checking fuel tank condition (any sign of water contamination, no water drain, corrosions / deteriorations, etc. Checking exhaust smoke condition to identify health of the engine. (c) Engine Lubricating System Inspection :- Checking oil lines connections (any signs of oil leak, loose connections, corroded piping, defective clamps, deteriorated hose, etc. Checking oil pressure condition (any sign of erratic operation, defective gauges, defective pressure sensors, defective wiring harness, etc. Checking oil level & oil quality condition.Checking last oil change & oil filter replacement. Checking make up oil availability at site. (d) Engine Air Induction System :-Checking air filter indicator reading (any sign of defective sensor, erratic operation).Checking air filter (any sign of filter clogging, dirt accumulation, air obstruction, defective seal, damage/ deteriorated housing etc.Checking turbocharger condition (any sign of excessive end play, oil/ gas leak, abnormal operating noise, excessive vibration, overheating etc.)Checking hoses & connections deterioration / wear & tear.Checking Charge Air cooler condition- if any (sign of clogged core/ fins, air leaks at connections, damaged gaskets, etc.
(e) Engine Exhaust System :- Checking the exhaust manifold condition (any sign of gas leak, missing bolts and nuts, red hot manifold, oil leak, deterioration etc.Checking the flexible bellow/ hoses & connections deterioration / wear & tear.Checking muffler condition (any sign of support insufficiency, corrosion, drain pipe valve not installed, not shielded, etc). Checking exhaust pipe insulation condition / deterioration.Checking smoke emission quality (any sign of excessive black smoke, bluish smoke, white smoke, restricted gas flow etc.(f) Engine Electrical System :- Checking batteries condition (electrolyte level, distilled water level, defective plate, voltage drop during cranking-refer to manufacturer acceptable voltage drop, etc..), Battery capacity evaluation this can be done by battery discharge test. Replacement of batteries is to be planned. Checking the starting motor condition (any sign of defective solenoid, defective brushes, grounded / shorted connection, struck up rotor etc. Checking the wiring harness condition (any sign of defects, grounded, loose connections, shorted, open circuit, any deterioration. (g) Generator Control Panel System Inspection :- Checking “start / stop / manual switch condition & functionality. Checking “voltmeter”, “Ammeter”, “frequency “ meter for proper functionality.Checking “voltmeter”, “Ammeter”, “frequency “ meter for proper functionality. Checking “Contactors, ACB for proper functioning /operations. Checking “wiring termination for proper tightness. Checking indicating lamps for proper functioning. Checking if fault/tripping circuits are working satisfactory. Checking if doors are closing properly. Checking if there is no blockage of air from rear ducts. Checking if the front opening is directing the hot air outside room. (h) AMF Panel : Checking the all connection of contractor, MCCB, cable connection and rectify the defect if found any. NOTE:- any spare parts required for maintenance will be measured and paid separately in under relevent items.
Material and labour for Calibration of FIP and fuel injector from the authorized dealer, including petty repairs and replacing the suction & delivery valves, rollers to make the FIP and injectors functional for the capacities of DG set 500KVA ( calibration and repair to be carried out through authorized MICO test bench and test certificate to be submitted by the contractor) all as specified and directed.
Supply and filling in replacement/topping up engine oil multi grade 15W to 40W in engine all as specified and directed. (Make KEOL Oil / Castrol /HP)
Supply and filling Coolant for radiators , complete all as specified and directed by Engr-in-Charge.
Supply & fixing Fuel filter 500KVA Kirloskar P/N 4005400218 all as directed. Make : Kirloskar Green.
Supply & fixing Oil filter 500KVA Kirloskar P/N 65.05510.5020B all as directed. Make : Kirloskar Green.
Supply & fixing Air filter 500 KVA kirloskar P/N KV0.505.02.0.00 all as directed. Make : Kirloskar Green
Supply & fixing Fuel filer Prelimary 500 KVA 5 Ltr all as directed.Make: Kirloskar Green
Supply & fixing Belt Kirloskar 500 KVA P/N. 65.968001.0195A all as directed. Make Kirloskar Green
Supply & fixing Fuel Hose set Kirloskar 500 KVA all as directed . Make : Kirloskar
Supply & fixing Feed Pump as sly 500 KVA all as directed. Make : Kirloskar green
Supply & fixing Coolant Hose set Kirloskar 500 KVA all as directed. Make : Kirloskar Green
Supply & fixing return oil pipe with suitable size nozzle for DG 500 KVA Make Kirloskar set of any capacity.
Supply & fixing Lube oil pressure pipe with suitable size nozzle for DG Set 500 KVA Make Kirloskar
Supply & fixing Fuel pipe with suitable size nozzle for DG set 500 KVA capacity.
Supply & fixing Nut M-8 for DG set 500 KVA Make Kirloskar complete all as specified and as directed
Supply and fixing Stop solenoid switch 24 Volts suitable for 500 KVA Make Kirloskar .
Supply and fixing Oil pressure gauge 500 KVA Make Kirloskar complete all as directed
Taking down and Supply, Fixing, Testing AVR for DG Set 500 KVA, 3 phase 4 wire, AC 415 Volts, 50Hz to sense the voltage in the main generator winding and control the power fed to the exciter stator and the main rotor to maintain the generator output voltage with in the specified limits, compensating for load, speed, tempreture and power factor complete with existing make & specification all as specified and directed by Engg.in.Charge.
M&L for repair of self starter including replacement of burn field coil, replacement of armature and carbon bush holder and carbon bush point of 500 KVA DG set complete all as specified and directed by Engr-in-Charge.
Supply & fixing Digital Meter suitable for AMF panel for DG set 500 KVA Make Kirloskar
Supply & fixing Indicator lamp suitable for AMF panel for DG Set 500 KVA Make Kirloskar
Taking down unserviceable change over switch and Supply and fixing on load change over switch 630 amps ,415 volt AC complete all as directed.
Taking down and Supply and fixing Battery terminal made with brass for 24 volt battery for DG Set 500 KVA complete all as specified and as directed
Taking down silencer pipe of the DG set of any capacity and dismentling asbestous rope decarbonizing the sylincer and Supply and fixing heat proof asbestors rope 12mm dia on engine exhaust pipe including dismantling of worn out Asbestors rope and minor welding/tightening in leakage exhaust conforming to ISI specification fire proof/flame proof all as specified and directed.
Material with labour for taking down 500 KVA DG set radaitor from its position by removing fan pulley, fan belt , fan blade carefuly and refixing, testing & commisioning the same after cleaning of radaitor cooling coil using coil cleaning solution from inside,cleaning of blocked copper coil using mild pressure compete all as specified and directed by Engineer-in-Charge. (Note- The cost of transportation is included in this item nothing shall be paid extra in this account)
Material with labour for painting the aquistic enclosure, Diesel engine , alternator with two coat of synthatic enamel paint after necessary scrapping the old paint, denting the damage portion complete all as directed.
Taking down unserviceable change over switch and Supply and fixing on load change over switch 400 amps, 415 volt AC, complete all as directed.
Dismantling of alternator parts of DG set 500 KVA 3 phase 4 wire ,AC 415 Volts, such as stator & rotor cores, excitor & field coils rectrifies assy, fan etc. Rewinding of stator field,replacement of exciter assembly, carbon bush and automatic voltage regulator,varnising and damage worn out insulation, cleaning all part by blower, servicing rewiring & varnishing etc. grease of reqd grade to bearing reassembling and testing complete all as specified and directed by Engg.in.Charge
Supply, install, testing and commissioning and fire alarm control panel complying with BS EN 54 double loop panel of capacity from 99 detectors & 99 modules upto 200 detector and modules complete all as specified and as directed.
Disconnectining the incomming and outgoing connections,taking out mannualy operated draw out type air circuit bracker(ACB) of any type any make,3 pole 415 volt rating current up to 800Amps,including cleaning greasing all mechnical parts,replacement of defective accessories,and connection of all incomming and outgoing connection complete all as specified and as directed.Note:-Accessories required for repair of ACB will be measured and paid seperately in respective items.
Supply only Auxilary cantact suitable for 630/800 Amps ACB.
Supply only Trip alarm contact suitable for 630/800 Amps ACB.
Supply only Insulation barrier suitable for 630/800 Amps ACB.
Supply only Earthfault release suitable for 630/800 Amps ACB .
Supply only Racking Interlock suitable for 630/800 Amps ACB .
Supply only Extension Bar suitable for incomming and out going cable suitable for 630/800 Amps ACB .
Supply and fixing Mechnical lockable trip Push button kit suitable for 630/800 Amps ACB .
Supply and fixing Locking of ACB in isolated position suitable for 630/800 Amps ACB .
Supply and fixing Door interlock of ACB in any position suitable for 630/800 Amps ACB.
Supply and fixing Vertical terminal adaptors for draw out power suitable for 630/800 Amps ACB .
Supply and fixing Shunt Release suitable for 630/800 Amps ACB .
Supply and fixing Under voltage Release suitable for 630/800 Amps ACB .
Supply, install, testing and commissioning Detectors Complying with and type certified to EN-45 Addressable type smoke detector Photoelectric/Optical with base with self built intelligence as per IS:11360 complete all as specified and as directed.
Taking down unserviceable MS ERW pipe of any size complete as all specified and as directed.
Supply & laying MS ERW Tubing 80 mm bore (dia) with all Fittings for Firefighting Water Line, laid in Trenches or laid in Concealed in Walls or any other situation, complete as all specified and as directed.
Supply, install, testing and commissioning12 V, 7 AH battery for Fire alarm control panel complete all as specified and directed.
Supply, install Hose box made of 18 gauge MS Sheet 800mm X 600mm X 250mm with double door with 4 mm thick glasses and door frame made of 16 gauge MS sheet painted fire red out side and brilliant white inside yard complete all as specified and as directed.
Supply, install C P hose 15 m complete all as specified and as directed.
Supply, install Branch pipe gun metal 63mm instantaneous inlet, made threaded outlet, 15mm bore nozzle short complete all as specified and as directed.
Supply, install, testing and commissioning Addressable manual call point resettable type complete all as specified and as directed.
Supply, install Hydrant valve single headed complete all as specified and as directed.
Disconnecting Monoblock pump set 3 HP capacity from suction/delivery line. lifting and removing from its existing foundation (inside/outside building) , dismantling carefully the pump and motor completely checking and segregating serviceable and unserviceable parts, cleaning/washing and servicing the serviceable parts by approved method, replacing unsv parts,(new parts required to be measured and paid seperately in respective item of schedule) reassembling the pump completely. Dismantling , cutting and removing the burnt windings from motor, rewinding with existing size/gauge with super enameled/copper conductor and other approved insulating materials, heating, drying including varnishing, overhauling .Reassembling the pump and motor, including painting the pump and MS channel with two coats of synthetic enamel paint incl marking of SM, MES or Ser No. installing monoblock pump to its existing foundation, commissioning, connecting up and testing complete all as directed. Make : Crompton greaves
Disconnecting Monoblock pump set 10 HP capacity from suction/delivery line. lifting and removing from its existing foundation (inside/outside building) , dismantling carefully the pump and motor completely checking and segregating serviceable and unserviceable parts, cleaning/washing and servicing the serviceable parts by approved method, replacing unsv parts,(new parts required to be measured and paid seperately in respective schedule of item) reassembling the pump completely. Dismantling , cutting and removing the burnt windings from motor, rewinding with existing size/gauge with super enameled/copper conductor and other approved insulating materials, heating, drying including varnishing, overhauling .Reassembling the pump and motor, including painting the pump and MS channel with two coats of synthetic enamel paint incl marking of SM, MES or Ser No. installing monoblock pump to its existing foundation, commissioning, connecting up and testing complete all as directed. Make : Crompton greaves
Supply the Ball bearing suitable size for 3HP/10 HP pumpset complete all as directed.
Supply the Motor terminal box of sizes as per site complete all as directed.
M&L in replacement DOL starter suitable for 3HP, 3 Phase, 415 Volts motor including testing and commissioning all as directed
M&L in replacement DOL starter suitable for 10HP, 3 Phase, 415 Volts motor including testing and commissioning all as directed
M&L for repairing of fire alarm control panel including replacement of burnt wiring, Circuit board complete testing & commisioning of panel all as directed and specified by Engineer-in-Charge.
Excavation in trenches, not exceeding 1.5m wide and n.exc 10 sqm on plan and n.exc 1.5m depth and getting out in hard/dense soil complete all as specified and as directed.
Returning filling in including spreading levelling, watering & well ramming in layers not exceeding 25 cm in soil.complete all as specified and as directed.
Removing excavated soil to a distance n. exc 50 m and depositing where directed at a level n exc 1.5 metre above the starting point complete all as specified and as directed.
M&L Sand Cushioning (dry) in trenches/ducts for protection of UG Cables (below, above and around the UG Cable laid in Trenches) of 23 Cm Spread thickness (8 Cm in depth before laying the Cable and 15 Cm in depth after laying the Cable) and consolidated (punned) upto 180mm thickness, complete all as specified and as directed. NOTE : For the purpose of Payment, punned thickness of Sand Cushioning only will be Measured.
Taking up reinforced precast concrete cable cover obtained in ser No.167 any class any type with any size complete all as specified and directed by Engr-in-charge.
Supply and lay in trenches PCC cable cover class LV, type 1, flat of size 250 mmx150 mmx 40 mm for cable protection all as specified and directed.
Relaying old but serviceable PCC cover laid on sand cushioning of LT underground cables complete. Note : The PCC Cover removed during removal of cables be used based on serviceablity state.
Taking out old unserviceable underground cable PVC insulated, PVC sheathed armored heavy duty aluminum conductor LT 1100 v grade, fixed on pole, wall and trenches etc after disconnecting of any size ,complete all as specified and as directed
Excavation/Cutting Road/ Hardstanding in Trenches not exc. 1.50 Metre wide and not exc. 1.50 Metre in depth and getting out, complete all as specified and as directed. NOTE : Quoted Unit Rate shall deem to be included Materials and Labour required for repairing to damaged Road/ Hardstanding to match the existing Surfaces and Specifications.
Relaying XLPE Under Ground Cable of any description (Serviceable Cable obtained from Item No. 167.00 here-in-before) 1100 Volt grade, cross sectional area 25 Sqmm to 400 Sqmm 3½/4 Core after Fault rectification including necessary Aluminium Thimbles, jointing and Testing, complete all as specified and as directed.
Material and labour for carrying out repair/maintenance through manufacturer or authorised service center of oil cooled Auto servo control voltage stabilizer 300/400KVA capacity located at Tech area . (i)Opening of stabilizer and maintanance of spare parts,fixing of new/repaired parts after repair in place of defective parts,repairing the defective control system etc and assembling complet all as specified and directed. (ii) Testing of stabilizer after repair on existing/new location to desired and rated output. Note:- All defective parts maint and cost of labour for maint is deem too be included in unit rate .
Supply Synchronising(servo) motor low speed instant start,stop high torque input voltage 250 Volt single phase 50HZ,60RPM type of following capacity.
Supply electronic cuircuit Control relay card AC 230 Volt, 250 ohms, 1 pin with base plate 24V DC.
Supply Gun metal brush assembly for 300/400 KVA stabilizer.Make:-AE,ME,Vintec
Supply aluminuim casted gear for opearting Sync motor suitable for SVR 300/400 KVA
M&L for Re-winding of dimmer coil(variable transformer) SVR of capacity 300/400 KVA complete all as directed.
M&L for Re-winding of buck boost transformer for SVR of capacity 300/400 KVA complete all as directed.
Supply only carbon bush suitable for SVR 300/400 KVA complete all as directed.
Supply only finger set for mounting carbon bush suitable for SVR 300/400 KVA complete all as directed.
M&L dehydration/filtration of transformer oil by means of centrifugal filtration plant to achieve the specified dielectric strength of 35 to 40 KV at 2.5 mm gap in existing position of servo stabilizer of any capacity and transformer oil for topping up at various sub station all as directed. Note: Transformer oil used for TOP UP measured and paid separately.
Supply only RC(resister-capacitor) card suitable for SVR 300/400 KVA complete all as directed.
Supply and pouring of new transformer oil to achieve a di-electric strength up to 60 KV in 4 mm gap conform to IS-335-1983 complete all as specified and directed.
Excavation in Trenches not exc. 1.50 Metre wide and not exc. 3 Metre in depth for laying of UG Cable/Pole/Stays, etc., getting out including forming bottom surface to required level and gradient in Soft/ Loose Soil and getting out, complete all as specified and as directed.
M & L for PCC (1:2:4) type B-1 using 20 mm graded stone aggregate as in coping of poles etc including weathering, slightly rounded or chamfered angle and throating, necessary form work and fair finishing all exposed faces of concrete without using extra cement complete all as specified and directed by Engineer-in-charge.
M & L for PCC (1:4:8) type D-2 using 40mm graded stone aggregate as in foundation for poles, struts & mass concrete including necessary form work and fair finishing to exposed surfaces complete all as specified and directed by Engineer-in-charge.
Supply & Laying/Fixing XLPE insulated, armoured heavy duty Electric Cable with Aluminium Conductor Multi Stranded, 1100 Volt grade, Cross sectional area 10 Sqmm 4 Core including necessary Aluminium Thimbles, jointing and Testing, complete all as specified and as directed.
Supply & Laying/Fixing XLPE insulated, armoured heavy duty Electric Cable with Aluminium Conductor Multi Stranded, 1100 Volt grade, Cross sectional area 16 Sqmm 4 Core including necessary Aluminium Thimbles, jointing and Testing, complete all as specified and as directed.
Supply & Laying/Fixing XLPE insulated, armoured heavy duty Electric Cable with Aluminium Conductor Multi Stranded, 1100 Volt grade, Cross sectional area 25 Sqmm 3.5 Core including necessary Aluminium Thimbles, jointing and Testing, complete all as specified and as directed.
Supply & Laying/Fixing XLPE insulated, armoured heavy duty Electric Cable with Aluminium Conductor Multi Stranded, 1100 Volt grade, Cross sectional area 35 Sqmm 3.5 Core including necessary Aluminium Thimbles, jointing and Testing, complete all as specified and as directed.
Supply & Laying/Fixing XLPE insulated, armoured heavy duty Electric Cable with Aluminium Conductor Multi Stranded, 1100 Volt grade, Cross sectional area 50 Sqmm 3.5 Core including necessary Aluminium Thimbles, jointing and Testing, complete all as specified and as directed.
Supply & Laying/Fixing XLPE insulated, armoured heavy duty Electric Cable with Aluminium Conductor Multi Stranded, 1100 Volt grade, Cross sectional area 70 Sqmm 3.5 Core including necessary Aluminium Thimbles, jointing and Testing, complete all as specified and as directed.
Supply & Laying/Fixing XLPE insulated, armoured heavy duty Electric Cable with Aluminium Conductor Multi Stranded, 1100 Volt grade, Cross sectional area 95 Sqmm 3.5 Core including necessary Aluminium Thimbles, jointing and Testing, complete all as specified and as directed.
Supply & Laying/Fixing XLPE insulated, armoured heavy duty Electric Cable with Aluminium Conductor Multi Stranded, 1100 Volt grade, Cross sectional area 120 Sqmm 3.5 Core including necessary Aluminium Thimbles, jointing and Testing, complete all as specified and as directed.
Supply & Laying/Fixing XLPE insulated, armoured heavy duty Electric Cable with Aluminium Conductor Multi Stranded, 1100 Volt grade, Cross sectional area 185 Sqmm 3.5 Core including necessary Aluminium Thimbles, jointing and Testing, complete all as specified and as directed.
Supply & Laying/Fixing XLPE insulated, armoured heavy duty Electric Cable with Aluminium Conductor Multi Stranded, 1100 Volt grade, Cross sectional area 240 Sqmm 3.5 Core including necessary Aluminium Thimbles, jointing and Testing, complete all as specified and as directed.
Supply & Laying/Fixing XLPE insulated, armoured heavy duty Electric Cable with Aluminium Conductor Multi Stranded, 1100 Volt grade, Cross sectional area 300 Sqmm 3.5 Core including necessary Aluminium Thimbles, jointing and Testing, complete all as specified and as directed.
Supply & Laying/Fixing XLPE insulated, armoured heavy duty Electric Cable with Aluminium Conductor Multi Stranded, 1100 Volt grade, Cross sectional area 400 Sqmm 3.5 Core including necessary Aluminium Thimbles, jointing and Testing, complete all as specified and as directed.
Supply and Fixing aluminum lugs suitable for Cable of size 6 Sqmm to 16 Sqmm , complete all as specified and as directed.
Supply and Fixing aluminum lugs suitable for Cable of size 25 Sqmm , complete all as specified and as directed.
Supply and Fixing aluminum lugs suitable for Cable of size 35 Sqmm , complete all as specified and as directed.
Supply and Fixing aluminum lugs suitable for Cable of size 50 Sqmm, complete all as specified and as directed.
Supply and Fixing aluminum lugs suitable for Cable of size 70 Sqmm, complete all as specified and as directed.
Supply and Fixing aluminum lugs suitable for Cable of size 95 Sqmm, complete all as specified and as directed.
Supply and Fixing aluminum lugs suitable for Cable of size 120 to 185 Sqmm, complete all as specified and as directed.
Supply and Fixing aluminum lugs suitable for Cable of size 240 to 400 Sqmm, complete all as specified and as directed.
Supply and Fixing MCCB 4 pole 63 A , 415 V, 50Hz having breaking capacity 16 KA with adjustable thermal & magnetic setting complete all as spd and directed by Engg.in.Charge.
Supply and Fixing MCCB 4 pole 100 A , 415 V, 50Hz having breaking capacity 16 KA with adjustable thermal & magnetic setting complete all as spd and directed by Engg.in.Charge.
Supply and Fixing MCCB 4 pole 160 A , 415 V, 50Hz having breaking capacity 35 KA with adjustable thermal & magnetic setting complete all as spd and directed by Engg.in.Charge.
Supply and Fixing MCCB 4 pole 250 A , 415 V, 50Hz having breaking capacity 35 KA with adjustable thermal & magnetic setting complete all as spd and directed by Engg.in.Charge.
Supply and Fixing MCCB 4 pole 400 A , 415 V, 50Hz having breaking capacity 35 KA with adjustable thermal & magnetic setting complete all as spd and directed by Engg.in.Charge.
M&L for cable jointing kit hot shrink type,straight through joint, for 1100 volt (1.1 KV) grade cable for end termination suitable for underground PVC/XLPE armoured aluminium conductor heavy duty cable of sizes 10 to 35 Sqmm 2/3.5/4 core complete including testing/commissioning all as directed.
M&L for cable jointing kit hot shrink type,straight through joint, for 1100 volt (1.1 KV) grade cable for end termination suitable for underground PVC/XLPE armoured aluminium conductor heavy duty cable of sizes 3.5 core 50 Sqmm complete including testing/commissioning all as directed.
M&L for cable jointing kit hot shrink type,straight through joint,for 1100 volt (1.1 KV) grade cable for end termination suitable for underground PVC/XLPE armoured aluminium conductor heavy duty cable of sizes 3.5 core 70 Sqmm complete including testing/commissioning all as directed.
M&L for cable jointing kit hot shrink type,straight through joint, for 1100 volt (1.1 KV) grade cable for end termination suitable for underground PVC/XLPE armoured aluminium conductor heavy duty cable of sizes 3.5 core 95 to 120 Sqmm complete including testing/commissioning all as directed.
M&L for cable jointing kit hot shrink type,straight through joint, for 1100 volt (1.1 KV) grade cable for end termination suitable for underground PVC/XLPE armoured aluminium conductor heavy duty cable of sizes 3.5 core 185 to 240 Sqmm complete including testing/commissioning all as directed.
M&L for cable jointing kit hot shrink type,straight through joint, for 1100 volt (1.1 KV) grade cable for end termination suitable for underground PVC/XLPE armoured aluminium conductor heavy duty cable of sizes 3.5 core 300 to 400 Sqmm complete including testing/commissioning all as directed.
M&L for Galvanised Steel Tubing Pipe 40mm bore (dia), light grade with Bend, laid in Trenches or under Roads/ Flooring/ Culverts and/or fixing to Electric Poles with suitable size Mild Steel Flat Iron Clamps, Bolts, Nuts, Washers, etc., complete all as specified and as directed.
M&L for Galvanised Steel Tubing Pipe 50mm bore (dia), light grade with Bend, laid in Trenches or under Roads/ Flooring/ Culverts and/or fixing to Electric Poles with suitable size Mild Steel Flat Iron Clamps, Bolts, Nuts, Washers, etc., complete all as specified and as directed.
M&L Galvanised Steel Tubing Pipe 80mm bore (dia), light grade with Bend, laid in Trenches or under Roads/ Flooring/ Culverts and/or fixing to Electric Poles with suitable size Mild Steel Flat Iron Clamps, Bolts, Nuts, Washers, etc., complete all as specified and as directed.
S&F Electronic Driver with Input Voltage 220 to 240 Volt and Output Voltage suitable for LED Light Fitting of capacity 20 to 120 Watt, complete all as specified and as directed.
S&F Surge Protection Device suitable for LED Light Fitting of capacity 20 to 120 Watt Single Phase 50 Hz, complete all as specified and as directed.
S&F Multi LED Street Light Fitting of capacity 45 Watt IP 65, having Die-cast Aluminium Housing, Weather Proof with Accessories and connecting up with and including PVC insulated Copper Conductor Cable 1.5 Sqmm, Single Core including Taking down unserviceable Street Light Fittings from the Electric Pole, complete all as specified and as directed.
S&F Multi LED Street Light Fitting of capacity 60 Watt IP 65, having Die-cast Aluminium Housing, Weather Proof with Accessories and connecting up with and including PVC insulated Copper Conductor Cable 1.5 Sqmm, Single Core including Taking down unserviceable Street Light Fittings from the Electric Pole, complete all as specified and as directed.
M & L Integral Decorative LED 8 Watt Bollard Energy Saving, Environmental Friendly aesthetically designed with opal acrlylic with IP-65 Protection, providing electric connection with suitable PVC copper flexible conductor, providing PCC 1:3:6 (20mm graded aggregate) work of size 300x300x450mm including necessary formwork and earth work, complete all as specified and as directed. Cat Part No. Havells LHEVBDP7IN6K008 or equivalent.
Supply & fixing in replacement Integral LED aviation light 30 watt comprising of aluminium housing with polycarbonate enclosure with IP-65 protection complete all as specified and as directed by the Engr- in- Charge.
Supply, fixing and testing LED Flood light fitting of 400 Watt in repair/replacement of existing high mast lights including LED lamps complete with body robust,corrosion resistant,superior finish and without any cracks or through holes,made in a single piece by high pressure die cast aluminium alloy.The luminaries shall be monolithic construction totally enclosed dust and water proof with minimum IP -66 protection as per IS - 10322-1982(Part -I) with latest amendments and input voltage range 140 - 270 V, AC, frequency 50 - 60 Hz ,P.F should be more than 0.9 with Total Harmonic Distoration THD(I) less than 10% ,cool white colour and lamp starting time should not be more than 10 second. Fitting should be provided with 10 KV surge protection.Driver should be constant current constant voltage driver .Driver should have high voltage withstanding capacity upto 300 V, AC. Driver should also have double phase protection,no load , open circuit and short circuit protection .LED light fitting should be suitable for ambient temperature from -10 degreeCentrigrade to 50 degree Centrigrade and humidity level 10% to 90 % RH. Covers should be polycarbonate/toughened glass to ensure minimum IP 65 degree protection.Cover should not degrade due to heating and ageing.The efficiency of LED luminaries system shall be more than 85 lumens per watt and must be certified by the LM-79 test report .
Supply and fixing Polycarbonate gate light fixture, Moon opal shaped Havells Cat part No. LHFXB0N1TN5Q020 (Moon 250(Opal)) with 15 W LED bulb B22 Base suitable for fixing on 40/50 mm dia pipe complete all as specified and directed.
Supply, fixing and testing Post top lantern of 45 Watt in repair/replacement of existing lights including LED lamps, acrylic, canopy totally enclosed dust and water proof with minimum IP -66 protection as per IS - 10322-1982(Part -I) with latest amendments and input voltage range 140 - 270 V, AC, frequency 50 - 60 Hz ,P.F should be more than 0.9 with Total Harmonic Distoration THD(I) less than 10% ,cool white colour and lamp starting time should not be more than 10 second. Fitting should be provided with 10 KV surge protection.Driver should be constant current constant voltage driver .Driver should have high voltage withstanding capacity upto 300 V, AC. Driver should also have double phase protection,no load , open circuit and short circuit protection .LED light fitting should be suitable for ambient temperature from -10 degreeCentrigrade to 50 degree Centrigrade and humidity level 10% to 90 % RH. Covers should be polycarbonate/toughened glass to ensure minimum IP 65 degree protection.Cover should not degrade due to heating and ageing.The efficiency of LED luminaries system shall be more than 85 lumens per watt and must be certified by the LM-79 test report including suitable size of GI pipe for post with PCC 1:3:6 complete all as specified and as directed by the Engr- in- Charge.
All as per Srl Item No 216.00 above but Decorative gate light made up of high grade unbreakable polycarbonate material suitable for retrofit LED lamp base 20 Watt
S&F Lithium based Energy Efficient integrated Solar Street Light 32 Watt in Single FRP Body encases Solar PV Panel 64/66 Wp Monocrystalline, Lithium Battery 11.1/12.8 Volt, 33 AH with in-built BMS, High brightness Watt - LED (160 to 180 Lumen/Watt) Lamp, CRI>70, Color Temperature 6500 K, Micro Controller based Charge Controller cum Friver, Automatic Dimming function with PIR Motion Sensor, Dusk and Down Operation, Working Temperature : (-)10 °C to (+)55 °C, Weight 18-20 Kg with adjustable Mild Steel Clamp suitable for Pole/Wall mounting with protection: Short circuit, Overload, Reverse Polarity and Battery Protections. Maunfacturer should produce Vital Parameters Test Report from NABL or Accredited Lab and should be made in india with CE & ROHS Tested and Certified and connecting up with Copper Conductor Cable of suitable size including Taking down unserviceable Street Light Fittings from Pole, complete all as specified and as directed. MAKE :HAVELLS/BAJAJ/CROMPTON GREAVES/PHILIPS
Supply and fixing HOT moulded (FRP) junction box for street light pole with locking arrangement with IP 65 protection of size 280 x 200 with 32 Amp 4 way heavy duty terminal block with 10Amp MCB SP and two number of cable entry gland of standard size with suitable stainless steel bracket to fix with pole, including taking down existing ,complete all as specified and as directed by Engr-in-charge. .Make: Sintex/Hensel
M&L for for applying two coat of Cement based paint on PCC poles of street lights of ant description up to including 9 m overall length including preperation of old painted surface of PCC Poles all as specified and directed. Note :- Pole number shall be marked with white enamel paint over a base of size 20cm x 20cm prepared with two coats of black enamel paint on pole surfaces.
M&L for for applying two coat of Silver paint on GI poles of street lights of ant description up to including 9 m overall length including preperation of old painted surface of G I Poles all as specified and directed. Note :- Pole number shall be marked with white enamel paint over a base of size 20cm x 20cm prepared with two coats of black enamel paint on pole surfaces.
M&L Cement Concrete 1:2:4 (20mm graded stone aggregate) as in Copping of Electric Poles, etc. including weathering slightly rounded or chamfered angle and throating, finishing all exposed faces of Concrete with necessary Formwork including dismantling PCC Copping and/or removing damaged PCC Copping, complete all as specified and as directed.
M&L GI Pipe Bracket made out of Galvanised Iron Tubing 32/40mm bore (dia), light grade, 1.50 METRE long bent to shape as per specified for fixing Street Light Fitting including applying Two coats of Aluminium Paint over a coat of Aluminium Primer including taking down old unserviceable GI Pipe Bracket, complete all as specified and as directed.
S&F PVC insulated Multi Stranded Copper Conductor Cable 1.5 Sqmm 3 Core, Round Flexible for connection of Street Light Fitting including Taking down unserviceable Cable of any description, complete all as specified and as directed.
M&L for greasing, oiling,servicing & testing of 3 phase motor & winch of high mast light upto 25mtrs.Taking down the double drum winch with luminaire mounting arm, pulley assembly, aviation obstruction light, lightning arrester spike and replacement of unserviceable flood light, checking of electric cable connection,stainless steel wire rope, junction box complete all as specified and directed. (Note :-Necessary spare, other related work will be measured in respective items. (b) Necessary tools, ladder ,safty equiptment for electrician and helper will be arrange by the contractor in his own cost. (c) Taking down and refixing is also including the cost .
Replacement of three phase motor for high mast as per existing capacity and size to drive double drum winch complete all as specified and directed.
Supply only chain of suitable size & length as per existing for driving double drum winch of high mast complete all as specified and directed.
Supply only stainless steel wire rope for high mast upto 25 mtrs height of grade AISI 316, 7/19 construction, having minimum dia 6 mm, suitable for breaking load capacity 2350 Kgs complete all as specified and directed.
Supply only ERP/PCP trailing cable flexible type of size 2.5 sqmm 5 core complete all as specifed and directed.
Supply and cross arm, bracing, supports, clamps and back plate fabricated from structural steel section including nuts, bolts, washers,welding, bending, drillingholes for bolts in any shape and any size inclusive of one primer coat, two coats of aluminium paints as indicateed complete all as specified and as directed by Engineer in charge.
S&F in replacement of digital type street light timer with 24 Hrs opeartion setting single phase complete all as specified and directed.
S&F in replacment of ML-4 contractor 63 Amps Three phase 430 volt AC complete all as specified and directed
S&F in replacement of Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31(9 metres long )complying with requirements of IS-1678-1998 erecting truly in vertical position including painting of poles with two coats of synthetic enamel paint over a coat of primer in alternate strip of 30cm each in white and blue colour up to 1.5 metre height from top of PCC pedestal/coping of poles including numbering of poles with synthetic enamel paint black in 80mm high letters over 150mm x 230mm yellow base made from synthetic enamel paint complete all as specified and directed by Engineer-in-Charge. Note : PCC for foundation and earth work shall be measured and paid for separately.
ENJOY
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .