Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹83,750Accepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹84,000+₹250 (0.30%)Rejected-Finance NULL | L2 | Rejected-Finance L2 | |
| 3 | L3₹84,626+₹876 (1.05%)Rejected-Finance F 20 SHASTRI NAGAR DELHI52 | L3 | Rejected-Finance L3 | |
| 4 | L4₹89,280+₹5,530 (6.60%)Rejected-Finance | L4 | Rejected-Finance L4 | |
| 5 | L5₹99,515+₹15,765 (18.8%)Rejected-Finance | L5 | Rejected-Finance L5 |
Tender Value
₹99,230
EMD Value
₹2,100
Closing Date
20 Jul 2022, 11:00 amClosed
Ex. Engineer(Elect.)/CNZ
C-Block, Defence Colony, New Delhi 110024
Improvement of E.I and Fans and Rewiring of Malaria office, Near MLA office Tehkhand In ward No. 93-S under Central Zone.
2022_SDMC_122191_1
EE(Elect.)/CNZ/2022-23/15-03
Open Tender
Electrical Works
Item Rate
30 days
C-Block, Defence Colony, New Delhi
Please refer Tender documents.
2 documents required · 2 mandatory
₹500
₹2,100
16 Jan 2024
13 Jul 2022
20 Jul 2022
13 Jul 2022
20 Jul 2022
13 Jul 2022
Amount
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.(a)2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
Supplying and fixing suitable size GI box with modular plateand cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 modular switch, connections etc. as required.
Supplying and fixing suitable size GI box with modular plateand cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 5/6 &15/16A modular switch, connections etc. as required.
Installation of exhaust fan in the existing opening ,including making good the damage ,connection ,testing, commissioning etc.as required.(a) Up to 450 mm sweep
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)(a). 12 way, Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.(a) Single pole
Supplying and fixing following rating ,double pole,24o volt,isolator in the existing MCB DB complete with connections,testing and commissioning etc. as required.(a) 63 amps
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
P/F 6 SWG dia GI wire on surface or in recess for loop earthing along with existing surface / recess conduit/submain wiring cable as reqd.
Supplying and fixing call bell/ buzzer suitable for single phase,230 V, complete as required.
Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of following size on wall surface as reqd Upto 35 sq. mm (clamped with 1mm thick saddle)
Supply of 250 mm (10 inch) sweep 1250 rpm exhaust fan fresh Air complete with shutter blades etc functional as reqd.
S.I.T.C. of 1200 mm sweep, BEE 5 star rated Ceiling fan with Brush less direct current (BLDC) motor, class of insulation: B, 3 Nos.blades, 30 cm long downrod, 2 Nos canopies, shackle kit, safety rope, copper winding, Power factor not less then 0.9, service value (CMM/W) minimum 6.85, Air delivery minimum 215 6.85,350 rpm (tolerance as per IS :374-2019, THD less than 10% remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, earthing etc, complete as reqd.
S/I/T/C of LED Tube Type luminiare 20 Watt rating complete with polycarbonate housing batten integrated electronic driver prewired with high efficient LEDs with the following: (a) Total System Wattage 20 Watt +/- 5%. (b) Luminous Efficieny lumens/watt >= 95 (c ) Power Factor>= 0.95
SITC of single phase monoblock pumpset complete with all accessories workable of 240 volts 50 Hz AC supply 1.0 HP (0.75 KW) single phase pumpset head from 6-34 meter suction and delivery 25x25mm.
Supply of XLPE insulated and PVC sheathed Al. conductor armoured cable 1.1 KV grade confirming to IS 7098 as required. 2 x 6 sq.mm
S.N. Enterprises
Gautam Electrical
GURUNANAK ENTERPRISES
SHRIRAM SHARMA
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .