| 1.00Schedule 'A' Part - I (BUILDINGS AND STRUCTURES) This Schedule (contains under mentioned Sl. item No. 1.01 is not prepriced by MES and the prepriced rate indicated in Col - 5 as `0.00 indicates this fact only. The tenderer is required to quote their rates in Column 6. | |||||
| 1.01 | Lumpsum price worked out by the contractor for Construction of building for "AHU and AC Plant" complete all as specified and shown on drawings. | 1 | EACH BLOCK | 25,00,000 ₹25,00,000 Lowest | 25,00,000 ₹25,00,000 Lowest |
| 2.00 | Lump sum price worked out by the Contractor for “ADDN/ALTN TO BLDG" as listed in Schedule ‘A’ Part - II representing _______ % ______________ percent Above / Below the lump sum price of Rs.28,21,374.67 inserted by the MES in Schedule ‘A’ Part - II | 1 | JOB | 24,50,000 ₹24,50,000 | 23,98,168.5 ₹23,98,168.5 Lowest |
| 3.00 | Lump sum price worked out by the Contractor for “ROAD / PATH / CULVERTS / HARD STANDING” as listed in Schedule ‘A’ Part - III representing __________ % ____________ percent Above / Below the lump sum price of Rs.2,38,441.64 inserted by the MES in Schedule ‘A’ Part - III | 1 | JOB | 2,25,000 ₹2,25,000 | 2,02,675.5 ₹2,02,675.5 Lowest |
| 4.00 | Lump sum price worked out by the Contractor for “INTERNAL ELECTRIFICATION” as listed in Schedule ‘A’ Part - IV representing __________ % ____________ percent Above / Below the lump sum price of ₹295403.00 inserted by the MES in Schedule ‘A’ Part - IV | 1 | JOB | 2,85,000 ₹2,85,000 | 2,59,954.64 ₹2,59,954.64 Lowest |
| 5.00 | Lump sum price worked out by the Contractor for "INTERNAL FIRE FIGHTING SYSTEM” as listed in Schedule ‘A’ Part - V representing _______ % __________________ percent Above / Below the lump sum price of Rs.1,34,016.00 inserted by the MES in Schedule ‘A’ Part - V | 1 | JOB | 1,50,000 ₹1,50,000 | 1,27,315.2 ₹1,27,315.2 Lowest |
| 6.00 | Lump sum price worked out by the Contractor for “EXTERNAL WATER SUPPLY” as listed in Schedule ‘A’ Part - VI representing _______ % _________________ percent Above / Below the lump sum price of Rs.19383.50 inserted by the MES in Schedule ‘A’ Part - VI | 1 | JOB | 19,383.5 ₹19,383.5 Lowest | 24,229.38 ₹24,229.38 |
| 7.00Schedule 'A' Part - VII This Schedule is not prepriced by MES and the prepriced rate indicated in Col - 5 as ₹0.00 indicates this fact only. The tenderer is required to quote their rates in Column 6. | |||||
| 8.00 | ADDN/ALTN OF BLDG
Providing and fixing toughened glass 5 mm thickness in aluminium door and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per directions of Engineer-in-Charge | 15 | SQUARE METRE | 1,000 ₹15,000 | 800 ₹12,000 Lowest |
| 9.00 | Providing & Fixing of Armstrong Soft Fibre Acoustical Suspended Ceiling System with Optra (Bevelled Tegular) Edge Tiles With Armstrong 15mmExposed Grid. The tiles should have Humidity Resistance (RH) of 95%, NRC 0.9 - 1.0, Light Reflectance ≥85%, Colour White, Fire Performance UK Class 0 / Class 1 (BS 476 pt - 6 &7) in module size of 600 x 600 x 15mm , suitable for Green Building application, with Recycled content of 66% GW & 74% RW. The tile shall be laid on Armstrong silhouette 15mm faceexposed grid colour white having rotary stitching on all T sections i.e. the Main Runner, 1200 mm & 600 mm Cross Tees with a web height of 32mm and a load carrying capacity of 7.5Kgs/M2 with a minimum pull out strength of 100 kgs. The T Sections have a Galvanizing of 90 grams per M2 and need to be installed with Suspension system of Armstrong make. The Tile & Grid system used together should carry a 10 year warranty. | 200 | SQUARE METRE | 1,500 ₹3,00,000 | 850 ₹1,70,000 Lowest |
Tender Value
Refer Docs
EMD Value
₹2.9 L
Closing Date
19 Jul 2025, 6:00 pmClosed
GE RnD Pashan
GE RnD Pashan
ADDITION/ALTERATION OF CNS/CADAS BLDG FOR DATA CENTER AND IT INFRASTRUCTURE AT ARDE, PASHAN, PUNE
2025_MES_701219_2
GERD/PSN/TOKEN/64 OF 2024-2025
Open Tender
Civil Works
Lump-sum
365 days
GE RnD Pashan
As per tender Documents
10 documents required · 10 mandatory
₹2,000
GE RnD Pashan
₹2.9 L
Yes
17 Sept 2025
16 Jun 2025
26 Jul 2025
16 Jun 2025
19 Jul 2025
30 Jun 2025
16 Jun 2025 - 23 Jun 2025
Amount
Schedule 'A' Part - I (BUILDINGS AND STRUCTURES) This Schedule (contains under mentioned Sl. item No. 1.01 is not prepriced by MES and the prepriced rate indicated in Col - 5 as `0.00 indicates this fact only. The tenderer is required to quote their rates in Column 6.
Lumpsum price worked out by the contractor for Construction of building for "AHU and AC Plant" complete all as specified and shown on drawings.
Lump sum price worked out by the Contractor for “ADDN/ALTN TO BLDG" as listed in Schedule ‘A’ Part - II representing _______ % ______________ percent Above / Below the lump sum price of Rs.28,21,374.67 inserted by the MES in Schedule ‘A’ Part - II
Lump sum price worked out by the Contractor for “ROAD / PATH / CULVERTS / HARD STANDING” as listed in Schedule ‘A’ Part - III representing __________ % ____________ percent Above / Below the lump sum price of Rs.2,38,441.64 inserted by the MES in Schedule ‘A’ Part - III
Lump sum price worked out by the Contractor for “INTERNAL ELECTRIFICATION” as listed in Schedule ‘A’ Part - IV representing __________ % ____________ percent Above / Below the lump sum price of ₹295403.00 inserted by the MES in Schedule ‘A’ Part - IV
Lump sum price worked out by the Contractor for "INTERNAL FIRE FIGHTING SYSTEM” as listed in Schedule ‘A’ Part - V representing _______ % __________________ percent Above / Below the lump sum price of Rs.1,34,016.00 inserted by the MES in Schedule ‘A’ Part - V
Lump sum price worked out by the Contractor for “EXTERNAL WATER SUPPLY” as listed in Schedule ‘A’ Part - VI representing _______ % _________________ percent Above / Below the lump sum price of Rs.19383.50 inserted by the MES in Schedule ‘A’ Part - VI
Schedule 'A' Part - VII This Schedule is not prepriced by MES and the prepriced rate indicated in Col - 5 as ₹0.00 indicates this fact only. The tenderer is required to quote their rates in Column 6.
ADDN/ALTN OF BLDG Providing and fixing toughened glass 5 mm thickness in aluminium door and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per directions of Engineer-in-Charge
Providing & Fixing of Armstrong Soft Fibre Acoustical Suspended Ceiling System with Optra (Bevelled Tegular) Edge Tiles With Armstrong 15mmExposed Grid. The tiles should have Humidity Resistance (RH) of 95%, NRC 0.9 - 1.0, Light Reflectance ≥85%, Colour White, Fire Performance UK Class 0 / Class 1 (BS 476 pt - 6 &7) in module size of 600 x 600 x 15mm , suitable for Green Building application, with Recycled content of 66% GW & 74% RW. The tile shall be laid on Armstrong silhouette 15mm faceexposed grid colour white having rotary stitching on all T sections i.e. the Main Runner, 1200 mm & 600 mm Cross Tees with a web height of 32mm and a load carrying capacity of 7.5Kgs/M2 with a minimum pull out strength of 100 kgs. The T Sections have a Galvanizing of 90 grams per M2 and need to be installed with Suspension system of Armstrong make. The Tile & Grid system used together should carry a 10 year warranty.
Material and labour for preparation of newly plaster surfaces of wall and applying two coats of fire resistance paint over and including a coat of primer on wall surfaces including 1 mm thick wall care putty complete all as specified and directed.
Material and labour for complete removal of existing treatment of wall surfaces including preparation and applying of two coat of fire resistance paint over and including a coat of alkali resisting primer on wall surfaces over plaster of paris puttyof 1 mm thickness over plastered surface to prepare the surface even and smooth. complete all as specified and directed.
Material and labour for preparation of new steel surfaces and applying two coats of fire resistance paint complete all as specified and directed.
Material and Labour for applying water based polyurethane modified dispersion (single component, cold applied, non toxic, VOC complaint) in 03 coats including 01 coat of epoxy primer @ .15 Kg per Sqm followed by two coats of polyurethane coating with 1.5 Kg per sqm in two coats etc complete per manufacturer specificationComplete all as specified and directed by Garrison Engineer/Engr-in-Charge. Notes : 1. Properties of Polyurethane based chemical shall confirm to following Technical Parameters:- (i) Highly Elastic and shall have crack bridging ability of upto 3mm as per AS NZ 4548 (ii) UV Resistance. (iii) Adhesion to concrete and shall resist 7 bars of hydrostatic pressure. (iv) Tensile strength should not less than 2.0 N/sq.mm for free film & 60 % solid content as per ASTM C 1250 (v) Elongation should not less than 300% as per ASTM D2370 (vi) Solid content by weight should not less than 60%. (vii) Air/water permeability BSEN 12390 AT 5 bar -72 hours should be NIL and minimum dry film thickness of water proofing membrane must be 1.0mm. (viii) Accelerated weathering (ASTM453) should Pass 1000 hours. (ix) Reaction to fire – non inflammable
INTERNAL ELECTRIFICATION Taking down copper/aluminimum point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling rose, pendants, regulators, sockets , light fitting etc removing materials to store for keeeping in safe custody for taking credit(credit for above items should be made as per conditions separately) and making good disturbed surfaces for walls, floors, etc.
Taking down sub main wiring of any size including PVC conduit/casing caping complete and making good the disturbed surfaces all as specified and as directed.
Point wiring with 1.5 Sq.mmm copper conductor FRLS (multistranded) PVC insulated ISI marked unsheathed cable of any length drawn in and including concealed metallic rigid instove enamelled steel conduit of not less than 20mm dia ISI marked with all fitting and other accessories and also including PVC insulated ISI marked unsheathed FRLS cable size 1.5 sqmm copper conductor as earth wire to common earth dolly including galvanised terminal boxes ISI marked fixing into the wall of sizes as required at site and modular plates and frame suitable for fixing switches / sockets / fan regulators etc, and matching to the existing surface for :- one light point/fan point/bell point controlled by one way modular switch 5 Amps 240 volts, complete all as specified and directed
One 3 pin 5 Amps switch socket outlet point on independent board
One 3 pin socket outlet 5 Amps on the same board with other switches.
All as per SI Item No. 16 here-in-before but wiring with 2.5 Sqmm for 15 Amps modular 3 pin socket outlet on independent board / two pin earth plug and socket including providing 2.5 Sq.mm PVC insulated multistranded unsheathed FRLS copper earth continuity conductor and connected to common earth dolly, complete all as specified and directed.
Supply & fix LED down lighter, 24 Watt, 6500K, Unique slimmest recess / surface panel, with extruded aluminium housing with inbuilt electronic driver, polycarbonate diffuser and connecting up with twin core twisted flexible copper condctor cable from ceiling rose to fitting all as specified.
S&F 1x20W,230V, 6500K CCT surface mounted integral LED box type with extruded aluminium housing with inbuilt electronic driver, polycarbonate diffuser including LED tube rod 20 W and connecting up with twin core twisted flexible copper condctor cable from ceiling rose to fitting all as specified.
Supply & Fix recess mounted LED luminaire 36W 2'x2' , 5700K CCT, luminous efficacy of not less than 120lm/watt designed for false ceiling type or alongwith frame suitable for Grid ceiling or similar mounting system with concealed or exposed 'T' sections, with high efficiency PMMA diffuser softGlare free light alongwith electronic driver complete with all accessories prewired and connecting up with three core twister flexible copper conductor cable with suitable size including making good to the disturbed portion of ceiling complete all specified and directed.
Supply & Fix Security light fitting 35 W IP 66 protection, color temp (Cool White) pressure die cost aluminium body with high power LEDs as light source and tranparent diffuser, inbuilt electronic driver and luminous efficacy of 120lm/watt fixing on the GI bracket of not less than 25mm dia bend to shape as required at site and fixing with nexcessary GI clamps on the wall including connecting up with three core copper cable all as specified and directed.
Supply & fix Air Circulator fans 230 volts single phase oscillating 450 mm sweep, heavy duty suitable for wall mounting complete all as specified and directed.
Supply , Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service V alue (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V , 50 Hz, single phase AC complete all as specified and directed by Engr-in-Charge.
Supply and fix exhaust fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding of sweep 300mm complete all as specified and directed by Engr-in-Charge
M&L for sub main wiring complete with 2 single core cable 2.5 sqmm PVC insulated FRLS stranded copper conductor cable 1100 volts grade drawn through and including ERW steel conduit 20mm dia and conduit accessories in concealed with one run of PVC insulated FRLS cable 2.5 sqmm copper conductor cable (green in colour) for earth continuity conductor connected to main earth dolly complete all as specified and directed Note : 3 runs of 2.5sqmm cabe alongwith one run of steel conduit shall be measured as one unit length
M&L for sub main wiring complete with 2 single core cable 6 sqmm PVC insulated FRLS stranded copper conductor cable 1100 volts grade drawn through and including ERW steel conduit 25mm dia and conduit accessories in concealed with one run of PVC insulated FRLS cable 6 sqmm copper conductor cable ( green in colour) for earth continuity conductor connected to main earth dolly complete complete all as specified and directed Note : 3 runs of 6.0sqmm cable alongwith one run of steel conduit shall be measured as one unit length
M&L for sub main wiring complete with 4 single core cable 10 sqmm PVC insulated FRLS stranded copper conductor cable 1100 volts grade drawn through and including ERW steel conduit 32mm dia and conduit accessories in concealed with two run of PVC insulated FRLS cable 10 sqmm copper conductor cable ( green in colour ) for earth continuity conductor connected to main earth dolly complete complete all as specified and directed Note : 6 runs of 10.0sqmm cable alongwith one run of steel conduit shall be measured as one unit length
Supply and fixing factory made epoxy powder coated Distribution Board SPN 08 way double door ( MCB DB ) MCB DP as In comer, with 100 Amp bus bar, metal door (IP-43 protection, IK-09)as per IES-61439-3 fabricated from CRCA sheet and fixed semi flush to wall and suitable for universal mounting and neutral bar, standard DIN rail, Earth bar and cable ties for cable management, top and bottom removable gland plates with Knockout semi flush to wall and making good disturbed surface and touch up with the same finishes complete complete all as specified Note: MCBs will be measured and paid seperately under respective Sch A item in the schedule
Supply and fixing 240V, 10 KA 'c' curve miniature circuit breaker (MCB) of single pole and neutral of current carrying capacity 5 to 32 AMP, in the MCB DB Complete with connection testing and commissioning.
Supply and fixing 240V, 10 KA 'c' curve miniature circuit breaker (MCB) of single poles and current carrying capacity 5 to 32 AMP, in the MCB DB Complete with connection testing and commissioning.
M&L for earthing complete with galvanised steel, earth plate electrode 600x600mm x 6mm thick burried directly in ground verticaly (earth pit not less than 2.25 mtrs below ground level ) with top edge of the plate not less than 1.5 mtrs below normal ground level connected to galvanised iron 32 x 6 mm strip as earth lead by means of bolts, nuts, check nuts and washers of galvanised iron/steel all as shown in electrical plate No 3 on page 497 of MES schedule 2009 part - I connected to main switch board/main DBs/earthing test point including all necessary excavation and earth work in hard/dense soil common salt and charcoal dust mixed and packed 150mm thick all round the GI earth plate, watering pipe 20mm dia GI medium grade. GI sheet 0.63 mm thick funnel, wire gauge, 50mm thick RCC cover in PCC 1:2:4 type B1 duly reinforced with MS round bars 6mm dia @ 150c/c both ways and pit/chamber in PCC 1:3:6 type C1 with suitable lifting handle to cover, GI protection pipe 40mm dia light grade up to 7.5mtr from electrode GI pipe to be fixed with complete all as specified and directed.
INTERNAL FIRE FIGHTING SYSTEM Material and labour for 80 Ltr seamless Cylinder with master brass valve assembly with pressure gauge CCOE approved and tested for 25 Bar (360 psi) to maintain health of cylinder pressure complete all as specified and directed
Material and labour for 34 Ltr seamless Cylinder with master brass valve assembly with pressure gauge CCOE approved and tested for 25 Bar (360 PSi) to maintain health of cylinder pressure complete all as specified and directed
Material and labour for FK1230 (FK-5-12) gas UL listed/ FM approved 25 bar fire suppression agent environment friendly all as specified and directed
Supply and fixing of Electrical Pneumatic Actuator to control valves ON/OFF complete all as specified and directed
Supply and fixing of 50mm nominal bore flexible discharge hose pipe with minimum 7.5Kg pressure rating complete all as specified and directed
Supply and fixing Manual actuator to control valves ON/OFF complete all as specified and directed by Engr-in-charge.
Supply and fixing of discharge pressure switch with capacity minimum activation limit 10 bar complete all as specified and directed
Material and labour for discharge brass nozzles 360 degree gas flow direction size up to 1" complete all as specified and directed
Supply and fixing of master cylinder adapter kit of brass 1/4" male NPT suitable to connect acuation hose to cylinder assembly complete all as specified and directed by Engr-in-Charge
Material and labour for cylinder protection strap suitable size to hold master cylinder safely complete all as specified and directed
Supply and fixing of NRV / Check Valve up to 50mm nominal bore complete all as specified and directed
Supply and fixing of Inter Connection Hose complete all as specified and directed
Supply and fixing of Pressure operated control head (pneumatic actuator) of brass made female NPT 1"-1/4" UNC-2B threaded complete all as specified and directed
Material and labour Piping Seamless M.S. Pipe line of schedule grade 40 size 25NB, 40NB & 50 NB with required forged fittings, M.S. Supports with bolts, U Clamp etc duly painted in red and fixing Pipe (S) : M.S.Seamless ASTM A-106, SCH. 401 and manfold pipe with 50NB complete all as specified and directed by Engr-in-Charge.
Supply and fixing of 02 Zone Gas Release Panel AC 220V, 50Hz & DC 12 Volt weight 5.2 Kg made of CRCA sheet duly powder coated with dimensions (H-362mmxW-403mmxD-122mm) with Module complete all as specified and directed
Supply and fixing of Manual gas release unit (Green) complete all as specified and directed
Supply and fixing of Manual gas abort unit (Yellow) complete all as specified and directed
Supply and fixing of Battery for Panel 12 Volts DC supply complete all as specified and directed
Supply and fixing of DRY Chemical powder (ABC) fire extinguisher (Map 50 Based portable stored Pressure capacity of 4.5 Kg)complete all as specified and directed
Supply and fixing of CO2 fire extinguisher portable stored Pressure capacity of 4.5 Kg.complete all as specified and directed
Supply and fixing of portable water fire extinguisher of capacity 9 Ltr stored pressure complete all as specified and directed
Supply and fixing of clean agent fore extinguisher (HFC236FA based portable stored pressure) capacity 4KGcomplete all as specified and directed
Supply and fixing of Siren battery operated 6000 RPM, DC voltage 12/24 Volts, Audible 1.0 KM complete all as specified and directed
Supply and laying or fixing or passing through pipe, 1100 volts grade heavy duty cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC service connections 3 core 6 Sqmm complete all as specified and directed by Engr-in-Charge.
LIGHTNING PROTECTION SYSTEM Supply & fixing Aluminium strip 25 x 3.15mm with saddles and fixing screws etc. for roof conductorsand down conductors above ground complete all as specified and directed Note : (i) Epoxy base insulator with nut bolts & washers and PCC block only will be measured and paid seperately
Supply and fixing Test point terminal block made of gun metal or phosphorus bronze size 75x75x25 mm, drilled and screwed including, 3 NOS, 8 mm dia 25mm long hexagonal head screw complete all as specified and directed by Engineer-in-Charge
Supply and fixing Air termination, single pointed aluminium rod 12mm dia and 300mm longcomplete all as specified and directed
Supply and fixing PCC block of size 150x150x150mm in PCC 1:3:6 Type C1 with 20mm graded aggregte for fixing on roof conductor / air terminal rod / GI Strip etc all as directed by Engr-in-charge
Supply & fix galvanised iron strip of size 32x6 mm burried in ground or "fixed on wall'' with all neccesary fixing arrangements complete all as specified and directed by Engineer-in-Charge including dismantling taking out old galvanised iron strip. Note : 1. Epoxy base insulator only will be measured and paid separately. 2. All GI strip joints should be butt welded atleast 50 mm long.
M&L Earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtrs deep below normal ground level) with the top edges of plate not less than 1.5 mtrs below normal ground level connected to GI earth strip 32x6mm by means of GI nuts, bolts check nuts and washers earth lead protected by 40mm dia GI pipe light grade and connected to main distribution board/earthing test point all as shown in electrical plate No 3 and all as specified including testing on completion. Notes : The unit rate also including for excavation, earth work in any type of strata, plain cement concrete 1:3:6 mix, Type C1 pit, 40mm thick RCC 1:2:4 mix, type B1 cover reinforced with 8mm dia TMT bars @150mm C/C both ways, GI funnel with GI watering pipe 20mm dia med gde, wire mesh, protection pipe 40mm dia GI pipe light gde for earth lead upto 7.50m long with charcoal / coke and salt as required complete all as specified and directed by Engr-in-Charge.
Supply only of epoxy base insulator of suitable size, 35mm height fixed on PCC blocks/ wall or MS angle/ Pipe or on traverse/ Galavalume sheet etc
EXTERNAL WATER SUPPLY Excavation in trenches not. exceeding 1.5 mtr wide and not exc 1.5 mtr in depth and getting out for GI pipes and getting out excavated material all as directed in hard/dense soil
Returning filling in trenches including spreading leveling watering and well ramming in layers not exceeding 25 cm all as directed.
Removing of surplus soil and depositing to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point all as directed by Engr-in-Chagre.
M&L for in galvanized iron water tubing medium grade ISI marked in trenches complete with all accessories such as Tees union,bend,elbow nipple reducer etc all as required at site for branch connection including cutting threading all as directed for the following :- (A) 25 MM DIA
All as per Sl item No 68 but 50 mm dia complete all as specified and directed by engr-in-charge
Supply and fix gun metal gate / globe valve with iron wheel head screwed both ends for iron pipe fixed of following sizes :- (a) 25 mm dia
All as per Sl item No 70 but 50 mm dia complete all as specified and directed by Engr-in-Charge
M& L for boring to exisitng CI/ DI pipe line 150mm including insertion of Tee and necessary cutting and coneection to 50 mm GI pipe line complete all as specified and directed.
M&L for PCC in 1:2:4 type B 1 by using 20 mm graded stone aggregate for making good road/foot path/hard standing/drain/ bldg plinth protection and foundation for motors, pumps and starters all as per site requirement and as directed by Engr-in-Charge.
EXTERNAL ELECTRIC SUPPLY Supply, laying and testing LT UG cable, XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables including necessary lugs and glands as required (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sqmm x 3.5 core all as speified and directed. Note : Earthwork and excavation shall be measured and paid separately.
M&L PCC in 1:2:4 type B 1 by using 20 mm graded stone aggregate for making good road/foot path/hard standing/drain/ bldg plinth protection and foundation for motors, pumps and starters all as per site requirement and as directed by Engr-in-Charge.
Excavation in trenches not exc.1.5 mtr wide and not exc.1.5 m in depth for foundation of poles, stay assembly and laying of LT/HT cable as in any type of soil and getting out, complete all as specified and directed.
Returning, filling, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm in any type of soil, complete all as specified and directed.
Removal of excavated material to a distance not exc.50 m and depositing where directed at a level not exceeding 1.5 mtr above starting point.
Material and labour for riddle earth under floors or in foundations including watering, well ramming and consolidation complete all as specified and directed
Supplying and laying un-reinforced precast concrete cable cover, Class LV, Type I, flat, size 250 mm x 150mm x 40mm complete all as specified and directed
S&F GI pipe light grade 50 mm bore for cable protection fixed on poles or laid in trenches under floor, ducts etc with fixing clamps, nuts bolts etc for cable protection all as specified.
AIR CONDITIONING WATER COOLED CHILLER PLANT Supply, installation, testing and connection of 21 tonne capacity water-cooled package air conditioning unit, complete with hermetic scroll compressors, water-cooled condensers, evaporator, and fully integrated control systems. Centrifugal forward-curved evaporator fans for optimal airflow. Water inlet/outlet size: 11/4” BSP, flow rate per condenser as per specifications. Fully factory gas-charged condenser units for standard connection distances. Maintenance friendly design ensuring easy access and serviceability. Refrigerant type R407C complete all as specified and directed by Engr-in-charge. Make : Voltas, Bluestar, Daikin
FRP INDUCED DRAUGHT COOLING TOWER Supply, installation, testing and commissioning of FRP rectangular/round shape, vertical, induced draught counter flow cooling tower of 26 TR size with uniform water distribution and optimal heat transfer, having tough fiberglass reinforced plastic (FRP) casing of sufficient structural strength to withstand vibrations and wind velocity upto 60 m/s, FRP basin, rigid honeycomb type PVC fill of suitable thickness, SS sprinklers and non-clogging sprinkler pipes, FRP drift eliminator, energy efficient induced draught axial type fans with factory set and dynamically balanced blades pitch, IE3 TEFC squirrel cage induction motor, suitable for operation on 3- Ph, 415 V, 50 Hz AC supply with IP 65 protection for enclosure, conforming to IS 12615: 2018, inlet, outlet, drain and over-flow nozzle connections, etc. complete with accessories including necessary civil work viz. foundation, supporting structure, etc. for placement of cooling tower complete all as specified and directed by Engr-in-Charge. Make: Advance, Delta, Paharpur, Mihir
Motor Pumps Supply, installation, testing and commissioning of monoblock, self-priming, single-stage centrifugal pump of 3.0 HP power, 3 phase, 430 Volts, water pump cooling tower to condenser (1W + 1S), capable of 5.0 LPS discharge at 40 MWC head, having cast iron casing, enclosed type dynamically balanced cast iron impeller, carbon steel pump shaft, gland packed sealing, deep groove ball bearings, etc. with TEFC squirrel cage induction motor having class 'B' insulation, IE3 efficiency, conforming to IS 12615: 2018 and suitable for operation on 3-Ph, 415 V±10%, 50 Hz AC supply, base plate, mounting channel frame, accessories and fittings, viz. pressure gauges, thermometers, drains, coupling, coupling guard, vibration isolation arrangement by means of spring / rubber type mounting duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of apppropriate thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories complete all as specified and directed by Engineer-in-Charge. Make: Kirloskar, Mather & Platt, Crompton Greaves
CONDENSER Water Piping & Ancillary MS ERW CLASS- C PIPE (HEAVY DUTY) WITH INSULATION Supply, laying / fixing, testing and commissioning of MS ERW Class- C (heavy duty) pipe of dia 40mm chilled water circulation piping including necessary fittings viz. bends, tees, reducers, flanges, air purge valves, drain valves, structural support, necessary clamps, vibration isolators, etc. including painting and supporting / fixing the pipe in excavated trenches or on floor / wall / ceiling with clamps, hangers, angles, channels (using anchor fastners) with necessary accessories duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of apppropriate thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories including MS pipe insulation 25MM Nitrile rubber adehsive and monsoon tape complete all as specified and directed by engineer-in-charge.
Valves Supply, installation, testing and commissioning of water type PN 1.6 rated short pattern CI butterfly valve 40mm dia having Gr. FG-200 CI body conforming to IS 210: 2009, seat having EPDM rubber lining, CF 8 stainless steel disc, AISI- 410 stainless steel stem, 2.4 MPa body test pressure & 1.6 MPa seat test pressure and standard flange end conforming to BS 10 Table D/E & ANSI B 16.1 CI- 125 duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of apppropriate thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories complete all as specified and directed by engineer-in-charge. Make: Advance, Sant, Hindustan for strainer & Armacell, K-Flex, Aeroflex for insulation
(a) Y- Stainer 40mm
(b) Providing & fitting Air vent ( Ball Valve) valves 20mm
(c) Pressure guages
(d) S & F Thermometers of 4" dual scale (°F/°C), lower mount (radial), bimetal thernometer having 0.5 NPT process connection, Grade A accuracy class as per ASME B40.200, stem diameter 6.35 mm, laminated safety glass window, stainless steel 304 case, steam, process connection & joint, aluminium dial & pointer, IP67 protection, scale range 0- 60 °C complete with accessories, etc. as specified and directed by engineer-in-charge.
Hard PVC Drain Piping with Insulation 4mm Thick Hitlon and Black Tape (a) 40MM Pipe
Electrical cablling (a) S & F XLPE insulated, armoured, heavy duty Copper Conductor industrial cable, 1100 Volt, conforming to IS 694 of size 4 Core, 4.0 Sq.mm including clamping with saddles on floor/walls complete all as specified and directed
(b) S & F XLPE insulated, armoured, heavy duty Copper Conductor industrial cable, 1100 Volt, conforming to IS 694 of size 4 Core, 25.0 Sq.mm including clamping with saddles on floor/walls complete all as specified and directed
GALVANIZED STEEL SHEET DUCTING Supply, installation, balancing and commissioning of galvanized steel sheet metal round / rectangular ducting of following sheet thickness having zinc coating of 80 g/m² total on both sides and complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, volume control dampers, hangers, supports, etc. as per approved drawings and conforming to the latest edition of IS 655: 2006 & HVAC Duct Construction Standards - Metal and Flexible of SMACNA along with required scaffolding work, tools and plants etc to install the ducts at site complete all as specified and directed by Engr-in-Charge
(a) 22 Gauge
(b) 24 Gauge
INSULATION S & F of FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR), water absorption by volume 0.2% as per ASTM C 1763 & ASTM C 209, Class 0 fire performance as per BS 476 Part 6: 1989, Class 1 surface spread of flame as per BS 476 7: 1997, flammability HB, V-0 as per UL- 94, having good resistance to mechanical impact, excellent resistance to ozone, oil and chemicals, zero ozone depletion potential along with adhesives and other necessary accessories complete all as specified and directed by engineer-in-charge. Make: Armacell, K-Flex, Aeroflex
(a) 9mm Insulation
Diffusers, Grills & Dampers (a) Supply installation and testing powder coated extruded aluminium return air grills 7" powder coated as per design with removable core and damper
(b) Square Diffuser--Supply Type--12" x 12"
(c) Square Diffuser--Return Type--12" x 12"
SUPPLY CANVAS
REFRIGERANT TOP UP Gas Charging for all the above units as per the CU Piping length and the Indoor unit capacity. (a) R407C / R410-A
DX TYPE FLUSHING, PRESSURE TESTING, COMMISSIONING Each circuit to be flushed with Nitrogen, Purging and pressure testing of complete refrigerant pipe of each circuit, complete vaccum of each system under 400 Microns, Commissioing of system with system report for the complete AC Plant of 21 TR capacity all as directed.
Incomer: (i) MCCB thermal magnetic setting 4 pole 400 amps 50 KA breaking cap-01 No (ii) Aluminium bus bar 600 amps capacity for RYBN duly colour coaded PVC insulation mounted on procelian insulators suitable size complete. Outgoing: (i) MCCB thermal magnetic setting 4 pole 100 amps 36 KA breaking cap -03 Nos (for Condenser -02, Cooling tower - 01), (ii) MCCB thermal magnetic setting 4 pole 63 Amps, 25 KA breaking capacity -02 Nos ( Indoor unit - 01 + Standby - 01 No) (iii) MCCB thermal magnetic setting 4 pole 40 Amps, 25 KA breaking capacity -2 Nos ((Condenser pumps - 02 Nos) (iv) Basic digital multifunction meters CI 0.5 - 01 No. (v) Surface mounted LED (R,Y,B) indication lamp for all MCCBs suitable for 415V (vi) Spreader terminals 400A - 01 Set of 08 Nos, (vii) Spreader terminals for all incoming and outgoing MCCBs. (viii) Extended Rotary handle for all MCCBs (ix) Control MCB, 'C' Curve, SP, 6A, 10 KA - 01 No
Materail and labour for dismantling / taking down of old GI ducting form existing bldg (Red Zone area) including taking down false ceilling any type and insulating material and connected accessories and deposite to MES store complete all as specified and directed.
SPECIAL ITEM (SPLIT AC) Supply, Install, testing and commissioning of Energy rating BEE 5 star inverter Split Air conditioning capadity 2.0 TR with indoor and outdoor unit having comprising of the following (a) Multistranded copper conductor wire 3 core 4 sqmm with copper lugs not less than 3.0 mtrs b) Incoming and outgoing quality copper pipe with foam insulation duly whiled taped of each size not less than 3.0 mtrs c) Having 2 Nos of bracket duly powder coated with anchor fasterners, nut, washers set -01 d) Key features (i) Multi adjustable mode (ii) High ambient cooling (iii) Super dry (iv) Turbo cooling (v) ECO friendly Refrigerant R-#@/R-410A (V=vii) 100% copper (viii) Sleep mode (ix) Wide Voltage range operation (x) The ISEER value of Air conditoner shall be 4.5 (Minimum) (xi) Cordless remote -01 No.
Notes: 1. Extra copper pipe and multistranded copper conductor wire required for Air Conditoner to be installed on wall of building roof top shall deemed to be included in quoted rate. 2. Rate for Scafolding/Ladder/Tools and plants required to install Air conditiner i.e for making of holes to wall, drilleing making of holes to wall, drilling, making good distrubed surfaces and matching with the existing colour shall deemed to be included in quoted rate. 3. Outdoor unit should be kept above the level of indoor unit for installatin of AC in ground floor and to be on installed on outside wall/ parapet wall of roof top of the building with out extra cost. 4. The MES Number be painted on indoor and Outdoorunit with navy blue colour letters of size not less than 15mm height. Drain pipe fromindoor unit to plinth portection of Outside the building. 5.The quoted rates are also inclusive of making holes in brick/stone wall for installation of Air Conditioner and make good to the esxisting surface withputty and paint complete all as specified and directed.
Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 5 KVA.
M&L for sub main wiring with two single core 6 Sqmm FRLS PVC insulated stranded flexible copper conductor cable 660/1100 volts grade down in through rigid flexible where applicable non metalic PVC conduit with and including PVC insulated 6 Sqmm one single core multi strand copper conductor as continuous earth wire in green colour connected to common earth dolly, including taking down of old sub main all as specified and as directed Note : 1. Two runs of cable and one run of earth wire and one run of PVC conduit will be measured and paid as one unit.
M&L for sub main wiring with four single core 16 Sqmm FRLS PVC insulated stranded flexible copper conductor cable 660/1100 volts grade down in through rigid flexible where applicable non metalic PVC casing caping with and including PVC insulated 16 Sqmm 2 runs of single core multi strand copper conductor as continuous earth wire in green colour connected to common earth dolly, including taking down of old sub main all as specified and as directed. Note : 1. Four runs of cable and two run of earth wire and one run of PVC casing caping will be measured and paid as one unit.
Supplying and fix 4 way MCB distribution board, horizontal type three pole and neutral, sheet steel enclosure, 415 V, on surface/recess, complete with tinned copper bus bar, neutral bus bar, earth bar, interconnections, powder painted all as specfied and directed
Supplying and fix 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve MCB complete with connections, testing and commissioninq all as specfied and directed
Supplying and fix 4Pole 63 Amps, 415 V, MCB complete with connections, testing and commissioning all as specfied and directed
Material and labour for sheet Metal enclosure with socket plug top & MCB with a two pin and earth plug and socket complete with one single pole MCB SP 20A' to 32 Amp 'C Curve all as specfied and directed
DG SUPPLY Supply, installation, commissioning & testing of silent, Diesel engine driven factory assemble, generating set of capacity 400 KVA, 3 phase, 4 wire, 50 Hz, 1500 RPM complete with Engine and alternator mounted on a common MS fabricated base frame with AVM pads, Acoustic enclosure, relay panel for automatic starting on mains failure safety control and metering equipment mounted on & including common base frame and installed on PCC/RCC foundation as recommended by manufacturer and approved by GE and suitable for ambient conditions at Pune, environmental eco-friendly as per CPCB IV norms including the following all as specified and directed. Note:Provision of PCC foundation work as per manufacture instructions, anti-vibration pads and other standard accessories and comprising of the following complete all as specified and directed
Diesel Engine: No of Cylinders 06, Inline arrangement, Gross Engine power (HP) 303.4 and (KWm) 223, water cooled turbocharged with after cooled, rated output 1500 RPM and overspeed trip 1650 RPM, Engine Is with electric start, compression ignition, stroke cycle designed to run continuously at 1500 RPM conforming to IS 2002, ISO-3046, BS 5514 standards. Diesel engines should comply with CPCB IV norms. The Diesel Engine are comprising of followings: (1) Radiator with Fan (2) Fuel Injection equipment with Electronic Governor having CRS (Common Rail system) and DG performance class G3 (3) Dry type air cleaner (4) Exhaust silencer type NA, Max allowable backpressure (kPa) 17, Exhaust temperature (Deg C) 550, (5) Lub oil filter (Spin on type), (6) Fuel oil filter (Spin on type), (7) 24V electric starting system, (8) Battery charging alternator, (9) Stop Solenoid, (10) Lube Oil pressure Gauge, (11) Water Temperature Gauge, (12) lube oil temperature Gauge, (13) Battery voltage, (14) Extended life coolant, (15) First fill lube Oil
Alternator: Alternator type 4P, rotating field, automatic voltage regulator and voltage regulation + 1%, suitable for continuous duty operations rated at 1500 RPM, 415V, 0.8PF, 50 Hz, current (3Ph) Amps-347.8 in SPDP enclosure, Self-Excited & Self-regulated, Brushless, ‘H’ class insulation, temperature rise (Deg C) 125, coupling type Fle Disc, unbalanced load capability 25% of rated amps, Floor mounted with anti-friction Sealed ball bearing on end. Alternator charging 12V DC/35A, the alternator conforms to IS: 13364 (Part-II) suitable for tropical condition including making cable connection. Acoustic Enclosure: (a) Specially designed to meet stringent MoEF / CPCB norms of 75 dBA @ 1 Mtr at 75% Load under free field conditions. (b) The followings are some technical features of Acoustic Enclosure: (1) The Enclosure is modular in construction. (2) Base Frame is made of Sheet metal. (3) Durable industrial locking system is provided on Doors. (4) Door Gaskets are made in high quality EPDM material. (c) Corrosion Resistance: To make the Enclosure weather proof:-
(1) All sheet metal parts/components are hot dipped in seven tanks process, Pretreated and Passivated (2) Sheet metal components are with Pretreated and Passivated Base Powder Coated. (3) Base Frame is Epoxy Coated/Powder Coated. (4) Zinc Passivated Hardwares are used to avoid rusting. acoustic insulation: (1) Sound proofing of the Enclosure is done with Quality Rockwool confirming to IS:8183 Standard. (2) Acoustic foam shall be fire retardant and fire resistant. (3) Attenuates are provided to control sound at entry and exit of container. (4) Specially designed Residential Silencer is provided. (d) Ventilation And Air Circulation: Exhaust pipe inside Enclosure is thoroughly insulated by Cladding of Rock wool and Sheet. (e) ELECTRICAL: Neutral Body Earthing points at the sides of enclosure are isolated through Moulded compound. (f) SAFETIES: Emergency Push button to Stop the DG set from outside, Low Fuel oil level, Low Lube oil pressure, Low Coolant Level, High Engine Temperature. The canopies being offered are for output of Noise Level ≤ 75 dbA at a distance of 1-meter average, as per the CPCB IV Norms. Batteries: 2 Nos. 12V 180Ah batteries with leads for electric starting.
Paint: DG set and panel package will be painted with powder coated type paint. STANDARD GENSET CONTROLLER UNIT WITH CONTROL PANEL: - Genset Controller unit with totally enclosed, Steel Construction Control Panel suitable for indoor floor /wall mounting installation having standard safeties and display parameters.” AMF PANEL: Supply, install, testing and commissioning of AMF Panel for 400 KVA DG Set factory made, outdoor cubical type as per IE/CPRI rules with IP-54 protection, dust and vermin proof, compartmentalised, made of 3.15 mm thick CRCA sheet, fixed on MS angle iron frame of 50 x 50 x 6 mm thick of required type for supporting double door both sides open type with necessary locking arrangement with slope roof on top duly painted with two coats of powder coated siemens grey paint with seven tank process complete and having separate doors inside for accommodating all incoming/outgoing cables and other relevant standards mounted on and including provision of necessary plinth in PCC 1:3:6, type C1 for foundation and PCC pillars with suitable size of nut, bolts & washers grouted as required at site and as per manufacturer's instructions including provision of the following items complete all as specified and directed.
Earthing complete with copper earth plate electrode 600 × 600mm × 3.15mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to copper strip 20X3 mm as earthing lead by means of bolts, nuts, check nuts and washers of copper, earth lead protected by 40mm dia GI pipe light grade watering pipe 20mm dia GI Light grade GI wire meshed funnel alternate layer of charcoal and salt, PCC chamber type C1 (1:3:6) including RCC cover 40mm thick type B1 (1:2:40 reinforced with 8mm dia TMT bars 100mm c/c both ways including necessary excavation and earth work in any type of soil, disposal of surplus soil to a distance not exceeding 50 Metre all as specified and as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion all as specified and directed.
Earth continuity conductor or main earthing lead fixed to wall on recessed or burried in ground or drawn in conduit/pipe fixed to poles or any other indicated situation for loop earthing as required of size 20X3mm copper strip.
i) Incomer (a) Bus bar chamber with electrolytic aluminium bus bar 4 Nos suitable for 1000 amps capacity for 3 phase and neutral (all connection inside the panel shall be through aluminium strip) connected duly supported with FRP insulators including colour code heat shrinked insulation sleeves - (b) MCCB 4 pole thermal/magnetic setting, 630 Amp, 415 Volts 70 KA– 01 No (II) Outgoing (a) MCCB thermal magnetic setting 4 pole 200 Amps 36 KA -02 Nos (b) MCCB thermal magnetic setting 4 pole 100 Amps 36KA - 02 Nos (c) TPN 63 Amp 10 KA -04 Nos (d) SPN 32 Amp - 04 Nos (e) Digital voltmeter AC 50 Hz , Indicaton of Parameters: V, A,F,PF, KW, KAV of size 96 X 96 sq mm flush mounted three phase energy accuracy class 1.0 (f) PCC 1:2:4 for foundation (g) LED type indicating lamp for phases and neutral (h) All MCCB & must have extended rotary handle and sprider links for incoming and outgoing.
UNIQUE ENGINEERS (BID ID -3349058)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .