Electrical work in connection with the work of "Replacement of Old FOB by new FOB at Manauri (MRE) (3.05 M wide) and Bharwari (BRE) (6.1 M wide) of PRYJ Division. Replacement of old FOB by 6.10 M wide new FOB with ramp at Sirathu (SRO)."Replacement of old Fob by new FOB at ULD under Ambiapur- Tundla Section.
ELG-23-2627
ELG-23-2627
Open
6 Months
Budaun, Uttar Pradesh
₹0
₹1.9 L
23 May 2026
23 May 2026
2 Jun 2026
Item Breakup - 1-NS Schedule
Supply and recessing/fixing of PVC Conduit pipe 25 mm Metre (Medium) conforming to IS 9537/ Part III/1983 (Latest version) with accessories,junction box, etc including making chase, plastering/ clamping etc as per technical specifications.Inspection by- Consignee.
Supply of PVC insulated multi stranded copper conductor Metre single core FRLSH cable 2.5 Sq. mm conforming to IS: 694 (latest version), and drawing in laid (recessed /surface) PVC conduit pipe for wiring of point wiring/ circuit wiring/sub main/ Main as required as per technical specification including connections, testing and commissioning.Inspection by- Consignee.
Supply of PVC insulated multi stranded copper conductor Metre single core FRLSH cable 4.0 Sq. mm conforming to IS: 694(latest version), and drawing in laid (recessed /surface) PVC conduit pipe for wiring of point wiring/ circuit wiring/sub main/ Main as required as per technical specification including connections, testing and commissioning.Inspection by- Consignee. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply of PVC insulated multi stranded copper conductor Metre single core FRLSH cable 6.0 Sq. mm conforming to IS: 694 (latest version), and drawing in laid (recessed /surface) PVC conduit pipe for wiring of point wiring/ circuit wiring/sub main/ Main as required as per technical specification including connections, testing and commissioning.Inspection by- Consignee.
Supply of PVC insulated multi stranded copper conductor Metre single core HRFR cable 1.5 Sq. mm conforming to IS: 694 (latest version), and drawing in laid (recessed /surface) PVC conduit pipe for Earth wire as required as per technical specification including connections, testing and commissioning.Inspection by- Consignee.
Supply and Installation of Ceiling rose 3 plate as per IS No. Numbers 700.00 371/1999 (Latest Version) including connections, Testing and commissioning as per Tech. Specification. Inspection by- Consignee.
Supply and recessing/fixing on surface of 6 SWG GI wire Metre conforming to IS: 280/2006 (Latest Version) for loop earthing as required for earthing of installation as per IE Rule.Inspection by- Consignee.
Supply, installation, testing, connecting and commissioning of Numbers LED base name board of different stations (01 set includes 01 No Hindi, 01 No English & 01 No Urdu name board) with power LEDs, Drivers & wiring of board. The signage board should have alphabet of vertical peak height of 600 mm and proportionate horizontal span. Approximate size of Hindi, English signage panel shall have Length 6400 mm, Height- 912 mm. Note - 01 set includes, a. Hindi board 01 No, b. English board 01 No, c. Urdu board 01 No. Inspection by-Consignee.
Supply, Installation, Testing and Commissioning of 1200 mm Numbers sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. Inspection by- Consignee.
Termination of LT XLPE cables of various sizes (One Job means Job all 4 cores of cables)
Supply and laying of B class, 50 mm dia, GI pipe of for cable Metre riser/road crossing as required and as per relevant technical specification. Inspection by- Consignee.
Collecting, Transporting from SSE/PS/ store to site, laying, Metre testing, and commissioning of above LT cable . Laying direct in ground (Including excavation, sand cushioning, protection brick covering and refilling the trench etc.), direct in RCC/Metal pipes in rod/track crossings and on surface/required in wall/in concrete floor by cutting recessed and finished originally as required as per relevant technical specifications.
Drilling of bituminous road/track and laying charges of cable in Metre road crossing for laying 110 mm dia HDPE pipe through it.
Supply and laying of HDPE Pipes (Upto PN 8.0 Pressure Rating Metre Material Grade: PE 63, Pressure Rating: PN 8.0, Nominal Dia(mm): 110) as per IS-4984:2016 suitable for HT/LT XLPE cable & as required and as per relevant technical specification. Inspection by- Consignee
Excavation of cable duct by horizontal boring method 1.4 to Metre 2.1 mtr depths from the bottom of sleeper for trench less track crossing and laying of 120 mm outer dia. DWC pipe. The work shall be done as per extent practice and instruction of site engineer. It includes supply of DWC/DHPE pipes conforming to IS : 14930 (Part 2, 2001).( Rex Poly Extrusion or similar make
Design, Manufacturing, Supply, Erection, testing and Numbers commissioning of LT switchgear panel board of 02 mm Tk. Dia pressed CRS steel sheet panel shall be treated for anti corrosion treatment and finished with smoke gray paint as per technicalspecification no. Sr.DEE/G/ALD/Panel-94/113 Comprising with as under:-........MCCB of 400 A, 36 kA Standard breaking capacity, 415 volt, 3 Phase 4 Pole current rating 400 Amp. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
MCCB of 125A, 36 kA Standard breaking capacity, 415 volt, 3 Numbers Phase 4 Pole currentrating 125 Amp.
MCCB of 63A, 36 kA Standard breaking capacity, 415 volt, 3 Numbers Phase 4 Pole current rating 63 Amp.
Supply of Indicator lamps with suitable holder.
Supply, fixing, testing, connecting and commissioning of Numbers Outgoing/Feeder Panel Mounted Multi-function Mtrs. with Accuracy Class 1 as per IEC 62053-21 or Class 0.5, 0.5S as per IEC 62053-22.LED Mtrs. Cl 1 with RS485: Mtrs. should have following features built-in LED • Flush mounting 96 x 96 mm • True RMS measurement • Password protection provision for security • Site selectable for 3 Phase 4 wire, 3 Phase 3 wire, 1 Phase, CT Secondary 1A/5A, Universal Auxiliary Supply 80-300 VAC/DC, Input Voltage Measurement 50-500 VAC, 64 samples/ cycle The Mtrs. should be able to read/display following paraMtrs.s Instantaneous ParaMtrs.s (V1, V2, V3, V12, V23, V31, Avg (VLN, VLL), A1, A2, A3, Aavg, F, PF-1, PF-2, PF-3, PF (Avg) W1, W2, W3, W (total) VA1, VA2, VA3, VA (total) Cumulative ParaMtrs.s (Import Wh, Import Vah, Import load hours, Reset (old) Cumulative paraMtrs.s (Import Wh, Import load hours, Communication (RS485 Modus RTU).complete with all accessories.
Fabrication works and insulated Aluminum bus bars of 800A Numbers capacity for phases & 800A capacity for neutral Bus bar shall be suitably insulated with heat shrinkable sleeves/ epoxy coating/insulating tap to withstand the test voltage of 2.5 KV Copper strip for connection outgoing as well as incoming with suitable size be provided. Item no. 16 to 21 Inspection by consignee.
Supply, replacement, fixing, testing, connecting and Numbers 750.00 commissioning of energy efficient luminaries complete with all accessries of capacity 18/20 watt, 4 feet length, T8 LED lamps with sutable current control driver circuit ,suitable for surface/recessed mounting.LED Luminaries:-(1) A complete LED lighting unit consisting of a light source and potted driver together with parts of distribute light,to position and protect the light source,and to connect the light source to a branch circuit.The light source itself may be an LED array and LED module, or an LED lamp. (2):-Supplied LED luminaries shall confirm to IS:16101(2012) IS :16106(2012) .Light Source (LED) in the Luminaries should be of make:- (1):-NICHIA/ CREE/OSRAM/ SEOUL/ PHILIPS/LUMILEDS /LEDNIUM. (2):-LEDs to IS: 16105(2012). IS:16108(2012), IEC:62471.1.Input operating voltage :-105-295 V AC. 2:-Normal Voltage-220V AC.3.Driver type: constant current driver with short circuit protection(For tube light). 4.Control of distribution:-Full cut off. 5.Drive component :Industrial grade only .6.Efficiency of driver electronic: > 85% (For tube light).7.Colour temperature:5000- 6500K(For tube light). 8.Colour rendering index(CRI):>75(For tube light). 9.Ingress protection :IP-20. 10.Lumen output: >100 lumens/[email protected] drive current(For tube light). 11.Power factor:->0.90(For tube light). 12.Total hormonics distrotion(THD):-<20% (For tube light). 13. Lamp cover :Acrylic cover which does not result in loss of lumens. 14. Finishing:Power coated /Anodized. 15.Secondry optics:poly corbonate reflector/ poly carbonate lens. 16. Construction of housing: extruded aluminum/CRCA/Pressure die cast aluminum. 17.Mounting :Suitable for surface mounting/recessed mounting. 18. Certificate: Firm to submit LM80(In respect of LED used) & LM79 (In respect of luminare used) test certificate from National/International accredited Laboratory and OEM certificate for complience of BIS/IEC. 19.Warranty:Firm to submit warranty certificate for five year along with the supply.All fittings shall be fitted as surface mounting/recessed mounting with twisted twin flexible cord of minimum size 16/0.2 mm copper conductor as per relevant technical specification. Materials praMtrs.s must remain unchanged during entire warranty period. 1x18/20 watt. Inspection by- Consignee.
Supply, erection, testing and commissioning of One phase Numbers distribution board comprising of one no. 32/40 amps DP MCB with 40 A ELCB/RCCB as incoming and 4 nos. 10 amps SP MCB , 4 nos. 20 A SP MCB as outgoing complete with copper bus bars, neutral link and other accessories housed in CRCA sheet enclosure with double door type. Inspection by- Consignee. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply, replacement, fixing, testing, connecting and Numbers 100.00 commissioning of 72 Watt or above LED street lights fittings as per IS:10322. LED Luminaries:-(1) A complete LED lighting unit consisting of a light source and potted driver together with parts of distribute lights,to position and protect the light source,and to connect the light source to a branch circuit. The light source itself may be an LED array and LED module, or an LED lamp.(2):-Supplied LED luminaries shall confirm to IS:16101 (2012) IS :16106(2012). Light Source(LED) in the Luminaries should be of make:- (1):-NICHIA/ CREE/OSRAM/ SEOUL/ PHILIPS/LUMILEDS /LEDNIUM. (2):-LEDs to IS:16105(2012). IS:16108(2012), IEC:62471. Type LED:- High power LED,SMD(Surface Mounting device)/COB(Clip on board). 1.Input operating voltage :-105-295 V AC.2:- Normal Voltage- 220V AC,3.Driver type: constant current driver with short circuit protection. 4.LED life:- >50000 burning hours. 5.Depreciation:- 30% max.after 50000 burning hours.6.Control of distribution:-Full cut off. 7.Surge protection:4KV. 8.Drive component :Industrial grade only.9.Efficiency of driver electronic: > 85%.10.Beam angle:>=140 degree along with road and >=80 degree across the road.11.Colour temperature:5000-6500K. 12.Colour rendering index(CRI):>=75. 13.Ingress protection :IP-66.14.Lumen output: >120 lumens/watt.15.Power factor:->0.95. 16.Total harmonics distortion(THD):-<15%.17.Lamp cover :Toughened glass or UV stabilised poly carbonate. 18.Finishing:Power coated/Anodized. 19.Secondry optics:poly carbonate reflector/ poly carbonates lens. 20.Construction of housing: extruded aluminum/ CRCA/Pressure die cast aluminum. 21.Mounting :Suitable for existing pole/ Truss/ Lantern mounted. 22.Certificate:Firm to submit LM 80(In respect of LED used) & LM79 (In respect of luminare used) test certificate from National/ International accredited Laboratory and OEM certificate for compliance of BIS/IEC. 23.Warranty:Firm to submit warranty certificate for five year along with the supply. All fittings shall be fitted with new suitable bend/elbow with clamp and proper nut and bolt and connection with twisted twin flexible cord of minimum size 16/1 mm copper conductor as per relevant technical specification. Material paraMtrs.s must remain unchanged during entire warranty period. Inspection by- Consignee.
Supply and erection of 6 Mtr. Galvanized (as per BS EN ISO Numbers 1461) octagonal pole with base plate 220x220x12mm, top 70mm and bottom 130mm of 3mm thick sheet suitable for maximum wind speed upto 160 Km/Hr. including foundation bolts and foundation with M 20 grade RCC and FE 415 grade reinforcement (450x450x800 mm deep ) (foundation should be as per design approved by pole manufacturer) GI base plate G.I. anchor plate etc.as required including supplying and fixing of double arm hot dipped galvanized bracket suitable for street light fittings and supplying and drawing of 3x2.5Sq.mm FRLS copper conductor single core cable from junction box with two Nos 6/10AMP MCB to luminaire complete including termination with copper lugs as required.Inspection by- Consignee.
Supply, erection, testing and commissioning ofsingle earth Numbers electrode of 50 mm. dia 4000mmlong GI pipe class B complete with earth boxwith CI cover hinged to CI frame includingconnection from earth electrode toMDB/SDB/poles/with 8 swg GI wire/strip as perattached drawing. Inspection by-Consignee.
Supply and instalation of 1-phase 5KVA, 120/96Volt DC input Numbers UPS with Battery Bank of 12V, 10 Nos tubular battereies of Okaya or any superior approved make each of 150AH for Emergency Supply of Metring system and sub-station lightings .After completion of the works all materials to be deposited to the concern SSEs stores. Inspection by- RITES.
Supply of heavy duty aluminium stool type folding ladder Numbers having "C" shapes section of size 16"x12" on top suitable for height upto 12 feet complete similar to Sumer make design no. AL-201/8818 (heavy duty) or equivalent. Inspection by- Consignee
Supply, laying, fixing, testing and commissioning of 10.0 sq Metre mm FRLS, PVC insulated multi stranded copper conductor single core cable 1100 Volts confirming to IS-694 (latest version) of approved make in the existing PVC conduit for wiring of point wiring/circuit wiring/sub main/main as per Tech Spec-I attached, IS & IE rules.Inspection by- Consignee. . PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply, fabricating and installing of G.I.perforated type cables Metre trays with perforation not more than 17.5%)including suspending from ceiling with MSangle, rods connection pieces, (L pieces, T pieces, 90/45 degree any other fitting required) G.I. nutbolts, G.I. washers,fasteners etc.complete in all respects required at site andas per PCEE/NR specification at Tech Spec-I. 150 mmwide, 50mm depth 2mm thick with protective cover. Inspection by- RITES.
Supply, fixing, testing, connecting and commissioning of Numbers storage type water cooler similar to Model SDLX 100, Cooling Capacity-170 litre per hour, 380/400 litre Storage with foundation/platform & cage. Inspection by- Consignee.
Electric Pole cutting (Pole to be deposited in Consigence's Numbers office.)
Supply, fixing, testing and commissioning of wall mounted LT Numbers distribution board made up of steel sheet, phosphatised powder painted complete with neutral link,earth point, Din rail and prewired confirming to IS:13032 & 8623:1991 withfollowing items to be fixed in distribution board, confirming to IS:8828 :1996 orlatest, IE rules and site requirement. 4P, MCCB 125 Amps. 10 kA 'C' series= 01 No.(Incoming) DP RCCB (25, 40 Amps., three nos. each) 10 kA 'C' series = 06 Nos. (Outgoing). Inspection by- Consignee.
Supply, fixing, testing and commissioning of wall mounted LT Numbers distribution board made up of steel sheet, phosphatised powder painted complete with neutral link,earth point, Din rail and prewired confirming to IS:13032 & 8623:1991 with following items to be fixed in distribution board, confirming to IS:8828 :1996 orlatest, IE rules and site requirement. 4P, MCCB 125 Amps. 10 kA 'C' series= 01 No.(Incoming) DP RCCB (40 & 63 Amps., two nos. each) 10 kA 'C' series = 04 Nos.(Outgoing). Inspection by- Consignee.
Supply erection, testing & commissioning of basic Earthing Kit Set 1set as per RDSO spec. No RDSO/PE/SPEC /PS/0109(REV.0)- 2008, Amendment '1' or latest specification.Inspection by- Consignee.
Supply, mounted/recessed LT Double door 4Way distribution board made up of steel sheet, phosphatised powder painted complete with neutral link, earth point, Din rail and prewired with following items to be fixed in distribution board and site requirement. Inspection by-Consignee.
Supply, mounted/recessed LT Double door 6Way distribution board made up of steel sheet, phosphatised powder painted complete with neutral link, earth point, Din rail and prewired with following items to be fixed in distribution board and site requirement. Inspection by-Consignee.
Supply, fixing, testing, connecting and commissioning o f 750 Numbers mm heavy duty wall mountedair circulator Fan suitable for 230 volts, 5 0 H z - ACsupply, >=1400 RPM, with wiring i n flexible PVC pipe as required. Inspection by- Consignee
Supply, fixing, testing and commissioning of DP RCBO's 10 (2P, Numbers 30 mA) Amp outgoing confirming to IS: 12640-2,IEC-61009-1 or latest. Inspection by-Consignee.
Supply, fixing, testing and commissioning of DP RCBO's 16 (2P, Numbers 30 mA) Amp outgoing confirming to IS: 12640-2,IEC-61009-1 or latest. Inspection by-Consignee.
Supply, fixing, testing and commissioning of DP RCBO's 20 (2P, Numbers 30 mA) Amp outgoing confirming to IS: 12640-2, IEC-61009-1 or latest. Inspection by-Consignee.
Supply, fixing, testing and commissioning of DP RCBO's 25 (2P, Numbers 30 mA) Amp outgoing confirming to IS: 12640-2, IEC-61009-1 or latest. Inspection by-Consignee.
Supply ,of Auto change Over pannel for CLS 25KVA 150A Numbers capacity as per RDSO specification no.TI/SPC/PSI/CLS/0023.Inspection by- Consignee.
Erection ,Testing commissioning of Auto change Over pannel Numbers for CLS 25KVA 150A capacity as per RDSO specification no.TI/SPC/PSI/CLS/0023 PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Design, Survey, Proposal with Technical Elevation Drawings & Square 3D layout, Supply,Manufacture, Erection, Installation, testing Foot and Display of wall / hanging / floor /pole mounting type LED illuminated, Modular, Changeable Aluminium extrudedprofile signage / direction board in full/half Parabolic and Elliptical square and multiangle shape and flat, with die molded internal structural brackets (Nylon/SS) andaluminium extruded heat sink. Suitable size end cap PC/ SS304 should be providedwith provision of illuminated Logo. The display sheet shall be of unbreakable 040 translucent polycarbonate sheet of 2-3 mm thickness. The text / graphics mattervision angle shall not be less than 160 degree and visibility not be less than 75%.The approved color text and graphics shall be printed / router cut on monomericcalendered vinyl of 100 um thickness and shall be firmly pasted on display sheets.A pole with grooves for tricolor LED/Neon light installation. The mountingarrangement shall be hanging, wall mounting, ceiling mounting, pole mounting orfloor mounting and as per site requirement. The signage shall have the integralmounting arrangements with sturdy structural frame and ACP cladding on the backside of the signage to avoid rusting and entry of dust. The LED board shall haveuniform illumination with 4-8 W / sq. ft and with brightness more than ambientlight. It shall confirm the latest specification issued by railway board (alsouploaded). Specification to be read with explanatory Note uploaded. Inspection by- Consignee.
Design, supply, fixing, testing andcommissioning of front Numbers operateddouble door type weather proof feederpillar feeder (MCCB - Incoming & MCCB- Outgoing) comprising with thefollowing MCCB's fixed in it conformingto IS-60947:2 with digital measuringinstrument & bus-bar arrangement asper IS, IE rules and site requirement.4P MCCB 250 Amps 36 kA withadjustable thermal & fixed magneticrelease = 01 No. (Incoming), 4P MCCB125Amps 36 kA with adjustablethermal & fixed magnetic release = 02No. (Outgoing) 4P MCCB 63 Amps 36kA with adjustable thermal & fixedmagnetic release = 04 No. (outgoing) Inspection by- Consignee
"Design, fabrication, supply and fixing of GI perforated Numbers 1000.00 horizontal cable- tray with all connected accessories viz- bend, tree, cross, reducer, 4 5 ° horizontal bend, coupler plates etc. including painting besides clamping, shifting of existing cables into t h e trenches along w ith tagging a n d labling o f shifted cables with numbering sleeve sfot easy identification. size 300 m m width, 1 5 0 mm depth, 2 m m thickness. Inspection by- RITES. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply, fixing, testing, connecting andcommissioning of 120 Numbers Watt or above Highbay LEDlight fittings.LED Luminaries:-(1) A complete LEDlighting unit consisting of a light source anddriver together with parts of distribute lights,toposition and protect the light source,and toconnect the light source to a branch circuit.Thelight source itself may be an LED array and LEDmodule, or an LED lamp.(2):-Supplied LEDluminaries shall confirm to IS:16101(2012) IS:16106(2012).Light Source(LED) in theLuminaries should be of make:- (1):-NICHIA/CREE/OSRAM/ SEOUL/ PHILIPS/LUMILEDS/LEDNIUM. (2):-LEDs toIS:16105(2012).IS:16108(2012),IEC:62471.TypeLED:- High power LED,SMD(Surface Mountingdevice)/COB(Clip on board).1.Input operatingvoltage :-105-295 V AC.2:- Normal Voltage-220VAC, 3.Driver type: constant current driver withshort circuit protection. 4.LED life:- >50000burning hours.5.Depreciation:- 30% max.after50000 burning hours. 6.Control of distribution:-Full cut off. 7.Surge protection:4KV.8.Drivecomponent :Industrial grade only. 9.Efficiency ofdriver electronic: > 85%. 10.Beam angle:>=140degree along with road and >=80 degree acrossthe road. 11.Colour temperature:5000-6500K.12.Colour rendering index(CRI):>=75.13.Ingressprotection :IP- 66.14.Lumen output: >120 lumens/watt.15.Power factor:- >0.95. 16.Totalhormonics distrotion(THD):-<15%. 17.Lampcover:Toughened glass or UV stabilsed polycarbonate.18.Finishing:Powercoated/Anodized.19.Secondry optics:polycorbonate reflector/ poly carbonateslens.20.Construction of housing: extrudedaluminum/CRCA/Pressure die castaluminum.21.Mounting:Suitable for existingpole/Truss/Lantern mounted.22.Certificate:Firmto submit LM80(In respect of LED used)&LM79(In respect of luminare used) test certificatefrom National/International accredited Laboratoryand OEM certificate for compliance ofBIS/IEC.23.Warranty:Firm to submit warrantycertificate for five year along with the supply.Allfittings shall be fitted with new suitablebend/elbow with clamp and proper nut and boltand connection with twisted twin flexible cord ofminimum size 16/1 mm copper conductor as perrelevant technical specification. Materialsprameters must remain unchanged during entirewarranty period. Inspection by-Consignee.
Supply, Erection, Testing and Commissioning o f following Numbers 250.00 Modular Type switch 1 0 A (1-way) complete i n a l l respect. Inspection by- Consignee.
Supply, Erection, Testing and Commissioning o f following Numbers Modular type Plug socket outlet 2/3 Pin 1 0 A complete in all respect. Inspection by- Consignee.
Supply, Erection, Testing and Commissioning o f following Numbers M o d u l a r Type switch 20 A (1-way)complete i n all respect.Inspection by- Consignee.
Supply, Erection, Testing and Commissioning of following Numbers Modular type Plug socket outlet 5/3 Pin 2 0 A complete in all respect.Inspection by- Consignee.
Supply and Erection of Modular type switch blanking set t o fill Numbers the blank space White finished mounting cover plate complete in all respect.Inspection by- Consignee.
Supply and Erection of white finish single mounting cover plate Numbers with base frame suitable 3 module suitable f o r mounting of Modular type piano switches/ plug Socket, fan regulator and connection to wiring. Inspection by- Consignee.
"Supply and Erection of Junction Box cover POP type complete Numbers 160.00 in all respect including hardware material for fixing. Inspection by-Consignee."
Supply and Erection of white finish single mounting cover plate Numbers with base frame suitable 8 module suitable f o r mounting of Modular type piano switches/ plug Socket, fan regulator and connection to wiring. Inspection by- Consignee.
Supply and Erection of white finish single mounting cover plate Numbers with base frame suitable 1 2 module suitable f o r mounting of Modular type piano switches/ plug Socket, fan regulator and connection to wiring. Inspection by- Consignee.
Supply and Erection of Modular Metal boxes concealed Boards Numbers suitable for mounting of 3 module white finish single mounting cover plate with Frame and Modular type piano switches/ plug Socket, fan regulators. Metal board boxes are to be concealed in wall. Inspection by- Consignee. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply and Erection of Modular Metal boxes concealed Boards Numbers suitable for mounting of 8 module white finish single mounting cover plate with Frame and Modular type piano switches/ plug Socket, fan regulators. Metal board boxes are to be concealed in wall. Inspection by- Consignee.
Supply and Erection of Modular Metal boxes concealed Boards Numbers suitable for mounting of 12 module white finish single mounting cover plate with Frame and Modular type piano switches/ plug Socket, fan regulators. Metal board boxes are to be concealed in wall. Inspection by- Consignee.
"Supply, fixing, testing, connecting and commissioning o f 300 Numbers mm sweep Exhaust Fan suitable for 230 volts, 50 Hz AC supply, 1400 R P M heavy duty w ith wiring and flexible P V C pipe as required. Inspection by Consignee." Total 9433669.35
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
GCC_April-2022_2022__27_04_227.pdf
ATTACHMENT
GCC CORRECTION
ATTACHMENT
CTIndianRailwaysStandardGeneralConditionsofContractApril-
ATTACHMENT
CTIndianRailwayStandardGeneralConditionsofContractApril-
ATTACHMENT
CTIndianRailwayStandardGeneralConditionsofContractApril-
ATTACHMENT
GCC CORRECTION
ATTACHMENT
2024_05_14ClarificationregardingsubmissionofAnnexure-VofGCC.pdf
ATTACHMENT
2022_12_13RBCE_CE-I-CTIndianRailwaysStandardGeneralConditionsofContractApril2022ACSNo_2.pdf
ATTACHMENT
2023_04_26RBCE_CE-I-CTIndianRailwaysStandardGeneralConditionsofContractApril-2022AdvanceCorrectionSlipNo_3ACS-3113.pdf
ATTACHMENT
2023_08_07RBCE_CE-I-CTIndianRailwayStandardGeneralConditionsofContractApril-2022AdvanceCorrectionSlipNo_4ACS-4.pdf
ATTACHMENT
2023_10_20RBCE_CE-I-CTIndianRailwayStandardGeneralConditionsofContractApril-2022AdvanceCorrectionSlipNo_5ACS-5.pdf
ATTACHMENT
2023_12_21IndianRailwaysStandardGeneralConditionsofContractApril-2022AdvanceCorrectionSlipNo_6ACS-6.pdf
ATTACHMENT
Annexure-VA.pdf
ATTACHMENT
AnnxVIB.pdf
ATTACHMENT
GCCACS2022CORRECTION1.pdf
ATTACHMENT
Likelysourceofsupply.pdf
ATTACHMENT
TNDoclatest.pdf
ATTACHMENT
2026_03_13AdvanceCorrectionSlipNo_111.pdf
ATTACHMENT
QTYBifurecation23.pdf
ATTACHMENT
Download all tender documents and submit your bid