Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.6 LAccepted-AOC A 303 VEENA CGHS LTD PLOT NO 5D SECTOR 22 DWARKA NEW DELHI 110077 | NEW DELHI | SOUTH WEST DELHI | DELHI | 110077 | L1 | Accepted-AOC Accepted | |
| 2 | L2₹33.9 L+₹52,474.50 (1.57%)Rejected-Finance 205 PARSHAV VIHAR PLOT NO 50 1 P EXTN PATPARGANJ DELHI 110092 | DELHI | EAST DELHI | DELHI | 110092 | L2 | Rejected-Finance Other than lowest |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
23 Dec 2021, 6:00 pmClosed
CWE New Delhi
HQ CWE New Delhi, Rao Tula Ram Marg, Delhi Cantt-10
Repair/maint of HT installation and other misc external electrification works at AHRR under GE E/M RR Hospital Delhi Cantt -10
2021_MES_488301_1
CWE-ND/33/2021-22
Open Tender
Miscellaneous Works
Item Rate
270 days
Delhi Cantt
Please refer tender documents
9 documents required · 9 mandatory
₹500
GE E/M RR Hospital
₹70,000
Yes
23 Feb 2022
18 Nov 2021
25 Dec 2021
18 Nov 2021
23 Dec 2021
9 Dec 2021
Amount
Servicing, calibration and testing of 11KV HT relay provided with VCBs HT panel of any make and type such as instantaneous earth fault, auxiliary relay, earth fault, under voltage, over current relay and adjustment the time for proper tripping with respect of MES/BSES incoming tripping with the relay testing equipment by the authorized service engineer and shall submit necessary certificate for the same complete all as specified & directed.
Servicing of HT 11 KV 630 amps VCBs trolley complete taking out from HT panel, opening all covers and cleaning internally and externally all contacts, spring and motor charging mechanism, opening of tripping system including adjustment, tightening & setting of contact male and female & inserting it in its original position & VCB out put side connectivity busbars from CT to cable to be insulated by using HT heat shrinkable sleeve (11000 V grade ) and testing etc. complete including replacement of glass of inspection window complete all as specified & directed.
Servicing of SF-6 circuit breaker including cleaning all parts internally and externally checking of the proper tension of the springs mechanism, tightening of connection of moving/ fixed contract, floating contacts, charging system and checking of SF-6 gas for any leakage and re-fixing it on its original position and including testing by the authorized service engineer and shall submit necessary certificate for the same complete all as specified & directed. NOTE: The cost of new part if any required to replace is not included in quoted rate and the items are required to be provided by the department.
M&L for servicing and renewal/replacement of defective parts of oil type Transformer 1600 KVA, 11/0.433 KV indoor type/out door type by disconnecting of HT/LT bus bar/Cable connections, opening of doors etc. complete cleaning of the inside compartment, core and coils by vacuum cleaner incl lead supports, tap changer terminal boards, bushings, replacing gaskets and other insulated surfaces be wiped clean with a dry cloth and all connections must be checked for tightness after cleaning up to the satisfaction of Engr-in-Charge complete all as specified and as directed.
All as per srl item No. 4.00 here-in-before but for transformer capacity 1000 KVA.
All as per srl item No. 4.00 here-in-before but for transformer capacity 400 to 500 KVA.
All as per srl item No. 4.00 here-in-before but for transformer capacity 100 to 315 KVA. Note:- Ser item no. 4.00 to 7.00 includes the under mentioned scope of work:- (a) Transformer must be meggered (b) Cleaning of transformer from inside. (c) Testing the Transformer for IR Values (d) Checking/servicing/calibration of WTI for healthiness. (e) Disconnection of Transformer HV/LV terminations for testing work and re-connections after completion of repair work. (f) Commissioning and necessary testing of transformer after completion of work.
Attending breakdown /inspection of 1600KVA transformer by authorised service engineer to check and replacement of any spare parts related to breakdown complete all as specified and as directed.
Attending breakdown /inspection of 1000KVA transformer by authorised service engineer to check and replacement of any spare parts related to breakdown complete all as specified and as directed.
Attending breakdown /inspection of 400KVA-500KVA transformer by authorised service engineer to check and replacement of any spare parts related breakdown complete all as specified and as directed.
Attending breakdown /inspection of 100KVA-315KVA transformer by authorised service engineer to check and replacement of any spare parts related breakdown complete all as specified and as directed.
Attending breakdown /inspection of SF-6 panel circuit breakers by authorised service engineer to check and replacement of any spare parts related breakdown complete all as specified and as directed.
Attending breakdown /inspection of HT 11KV/12KV VCB by authorised service engineer to check and replacement of any spare parts related breakdown complete all as specified and as directed. Note for Ser item No. 1.00 to 13.00:- (i) Maintenance/repair shall be carried out by authorised service engineer. (ii) All Measuring equipments and T&P required shall be arranged by the contractor. (iii) any other activity/ minor items not listed/covered here above and required during /completing the work for smooth function of system will have to be arranged by Contractor himself and for this purpose no extra cost will be paid. (iv) Major Spare parts shall be paid separately under relative item as supply only. However fixing charges shall deemed to be included in this item (v) A sum of Rs. 5000/- will be recovered from the contractor for non rectification of breakdown/fault or replacement of any unserviceable spares after 12 hours from lodging of complaint telephonically or verbally. (vi) Thereafter Rs. 1000/- will be added every day till rectification of fault or replacement of unserviceable spares as directed .
Supply only in replacement Isolate contact assembly suitable for HT 11KV/12KV VCB 630 Amps as per existing make and model complete all as specified & directed.
Supply only in replacement Auxiliary switch suitable for HT 11KV/12KV VCB 630 Amps as per existing make and model complete all as specified & directed.
Supply only in replacement Earth contact assembly suitable for HT 11KV/12KV VCB 630 Amps as per existing make and model complete all as specified & directed.
Supply only in replacement limit switch assembly suitable for HT 11KV/ 12 KV VCB 630 Amps as per existing make and model complete all as specified & directed.
Supply only in replacement Closing coil assembly for 11 KV/ 12 KV HT VCB 630 Amp as per existing make and model complete all as specified & directed.
Supply only in replacement tripping coil assembly for 11 KV/ 12 KV HT VCB 630 Amp as per existing make and model complete all as specified & directed.
Supply only in replacement Tripping/ Closing push button suitable for HT 11KV/12KV VCB 630 Amps as per existing make and model complete all as specified & directed.
Supply only in replacement spring charged indicator suitable for HT 11KV/12KV VCB 630 Amps as per existing make and model complete all as specified & directed.
Supply only in replacement Main shaft inter lock assembly suitable for HT 11KV/12KV VCB 630 Amps as per existing make and model complete all as specified & directed.
Supply only in replacement Big cam with main shaft suitable for HT 11KV/12KV VCB 630 Amps as per existing make and model complete all as specified & directed.
Supply only in replacement Big gear assembly suitable for HT 11KV/12KV VCB 630 Amps as per existing make and model complete all as specified & directed.
Supply only in replacement Small gear assembly suitable for HT 11KV/12KV VCB 630 Amps as per existing make and model complete all as specified & directed.
Supply only in replacement motor & gear assembly fixing for charging system 220 volts AC/DC or as per new model including all necessary modification suitable for 630 Amps HT VCB as per existing make and model complete all as specified & directed.
Supply only in replacement copper fixed contact, 630 Amps, I-type suitable for 630 Amps HT VCB as per existing make and model complete all as specified & directed.
Supply only in replacement copper fixed contact, 630 Amps, T-type suitable for 630 Amps HT VCB as per existing make and model complete all as specified & directed.
Supply only in replacement TNC switch suitable for operation of VCB 630 Amp installed in HT panel 11 KV as per existing make and model complete all as specified & directed.
Supply only in replacement of old space heater, ISI marked suitable for 11KV HT panel, complete all as specified & directed.
Supply only in replacement of old thermostat suitable for 11 KV HT panel complete all as specified & directed.
Supply only in replacement of push button with NO/NC contact suitable for capacitor panel complete all as specified & directed.
Supply and fix HT/LT cable route indicator made out of round CI embossed plate 100 mm dia 6 mm thick duly riveted with angle of size 40 x 40 x 6 mm and 60 cm long incl PCC for embedding 1:4:8 type D2 of size 30cmx30cmx30cm complete all as specified & directed.
Supply only in replacement 11 KV resin cast epoxy type current transformers (CTs) of ratio 100-50/5-5 Amps and class accuracy 0.5/5P10 or as per existing capacity including testing complete all as specified & directed.
Supply only in replacement of electronic relay for HT breaker operating voltage 240 V AC/DC, 50/60 Hz with adjustable settings Model No. L / MiCOM P-111 of Schneider or equivalent including cutting drilling to fix relay in existing panel door as per site requirement complete all as specified & directed.
All as per ser item No 37.00 here in before but for HT VCB main incomer having part No P127BA0Z112FE1 of Schneider or equivalent .
Supply and fixing in replacement of electric hooter with all accessories suitable for working on HT Panel including 2.5 Sqmm, FRLS. Multistranded PVC insulated copper cable for connection, complete all as specified & directed.
Supply and fixing in replacement of 24V / 16 A battery charger with battery bank (2 x battery of cap 35 AH) for CTVS 11 KV HT panel as existing and site requirement complete all as specified & directed.
M&L for repairing and making serviceable 110V/ 100AH battery charger of make AMARA RAJA Johnson Controls installed in X- block sub station complete all as specified & directed.
Supply only transformer oil, low viscosity insulating oil for top up transformer of as per IS-335, complete all as specified & directed. (Note - The oil shall be supplied in sealed barrel only.)
Material and labour for testing the dielectric strength of transformer oil of the transformers installed at various sub station at/on floor/pole before dehydration and dehydrating and filtering the transformer oil with dehydration machine to achieve dielectric strength of the oil up to 60 KV at 2.5 mm gap as per IS standard, complete all as specified & directed. Note : The transformer dehydration machine and dielectric strength testing machine shall be arranged/brought by contractor at site and no extra cost shall be paid to the contractor in this effect.
Supply only in replacement HV bushing, suitable for transformer of capacity upto 1600 KVA complete with suitable gasket, complete all as specified & directed.
Supply only in replacement LV bushing, suitable for transformer of capacity upto 1600 KVA with copper strip along with suitable gasket, complete all as specified & directed.
Supply only in replacement of temperature gauge 0 C to 125 C for transformer installed at site with all accessories, complete all as specified & directed.
Supply only in replacement of Air breather assembly complete with fresh blue colour silica gel suitable for indoor/outdoor type transformer of 1000KVA to 1600 KVA capacity, complete all as specified & directed.
All as per srl item No. 47.00 here-in-before but for transformer capacity 400 to 500 KVA.
All as per srl item No. 47.00 here-in-before but for transformer capacity 100 to 315 KVA.
M&L for preparing old painted steel or iron surfaces of HT/ SF6 Panel any type, description by cleaning dirt, oil, grease etc, removing the old paint, rust by scratching with wire brush/emery paper etc., and apply two coat of synthetic enamel spray paint over a coat of red oxide of existing colour on out side body of the HT/ SF6 Panel and writing of letter SM/MES No etc. of 10 cm height and making all HT/LT electric connections and testing the same complete all as directed.
M&L for preparing old painted surface of transformer of outdoor / indoor type of capacity 1000 KVA to 1600 KVA, any type, description by cleaning dirt, oil, grease etc., removing the old paint, rust by scratching with wire brush / emery paper etc, after disconnecting HT/LT electric connection from both primary and secondary side of transformer and apply two coat of synthetic enamel spray paint of existing colour on out side body of the transformer and writing of letter HT/LT and SM MES No etc. of 10 cm height and making all HT/LT electric connections and testing the same, complete all as directed.
All as per srl item No. 51.00 here-in-before but for transformer capacity 400 to 500 KVA.
All as per srl item No. 51.00 here-in-before but for transformer capacity 100 KVA to 315 KVA. Note for Ser item No. 50.00 to 53.00:- (a) The compressor and spray machine etc. shall be arranged/ brought by contractor at site and no extra cost shall be paid to the contractor for this effect. (b) Volt meter, Ammeter, relays etc. on panel / Transformer should be covered properly at the time of painting and after painting if any damage to the existing display or any item then the same will be replaced by contractor with out any extra cost.
Fault detection by bringing fault detector machine with skilled tradesmen to detect the fault at site in the high potential HT cable of any sizes, including digging up to showing faults only and marking the place where fault detected complete all as directed.
M&L for jointing and testing Indoor type cable end termination joint (heat shrinkable) suitable for HT aluminium conductor cable of size 400 Sqmm x 3 Core, 11 KV (earthed) Volts grade, complete all as specified & directed.
All as per srl item No. 55.00 here-in-before but suitable for cable size of 240 Sqmm to 300 sqmm.
All as per srl item No. 55.00 here-in-before but suitable for cable size of 120 Sqmm to 185 Sqmm.
M&L for jointing and testing Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for HT 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm to 185 Sqmm x 3 Core, 11 KV (earthed) Volts grade, complete all as specified & directed.
M&L for jointing and testing Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 Sqmm to 400 Sqmm complete all as specified & directed.
All as per srl item No. 59.00 here-in-before but suitable for cable size of 120 Sqmm to 185 Sqmm.
Excavation in trenches in soft/loose soil not exceeding 1.5 meter depth and not exceeding 1.5 meter wide and getting out including trimming of sides complete all as specified & directed.
All as per srl items No. 61.00 here-in-before but hard/ dense soil.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm thick complete all as specified & directed.
Removal excavated material (soil) not exc 50m and depositing where directed at a level not exc 1.5m above the starting point complete all as specified & directed.
M&L for sand cushioning with a layer of fine sand 8 cm thick before laying the cable and 15 cm after laying the cable in trenches to cover under ground cable, complete all as specified & directed.
Supplying and laying reinforced precast concrete cable cover , class HV, type 1, flat, size 300mmx180mmx40mm for cable protection complete all as specified & directed.
M&L in replacement for laying, testing and commissioning of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts Earthed, grade cross sectional area 400 Sqmm x 3 core confirming to IS 7098 Part-II, complete all as specified & directed. Notes : - 1. The end termination joint shall be measured and paid separately under respective items. 2. Excavation, earth work, sand cushioning and protection cover will be measured and paid off separately.
All as per srl items No. 67.00 here-in-before but for cable size of 240 Sqmm x 3 core.
All as per srl items No. 67.00 here-in-before but for cable size of 185 Sqmm x 3 core.
All as per srl items No. 67.00 here-in-before but for cable size of 150 Sqmm x 3 core.
All as per srl items No. 67.00 here-in-before but for cable size of 120 Sqmm x 3 core.
All as per srl items No. 67.00 here-in-before but for cable size of 95 Sqmm x 3 core.
M&L for Tubes, 'light grade, galvanised, with all fitting, laid in trenches/ poles/ road crossing of size 100 mm dia for protection of power cables complete all as specified & directed.
M&L for cross arms, bracings, supports, clamps, angle iron, flats and back plates fabricated from MS structural steel sections including nuts, bolts and washers of suitable sizes including welding, bending (cold or hot), drilling holes for bolts in any shape or size as indicated or directed and inclusive of two coats of aluminium paint over one coat of red oxide primer, complete all as specified & directed.
M & L in replacement for Earthing complete with galvanized steel earth plate electrode 60cmx60cmx6 mm thick buried directly in ground(earth) pit not less than 2.25 meter deep below normal ground level) with top edge of earth plate not less than 1.5 mtr below normal ground level connected to galvanized iron or wire of size 4 mm earthing lead by means of bolts, nuts check nuts and washers of galvanized iron or steel all as shown in electrical plate No 3 of SSR Pt-I connected earthing test point/panel complete including PCC earth chamber using PCC(1:3:6) Type C-2 using, graded stone aggregate, 50mm thick cast iron frame with CI cover, Funnel with watering pipe, wire mesh, copper lugs, excavation and earth work etc. complete all as specified and directed Note: i) Rate included for Adequate quantity of charcoal dust, common salt and Testing commissioning including checking of earth continuity and earth result complete all as specified and as directed. ii) Rates for Main earthing lead from earth electrode to test point upto 7.5 metre will deemed to be included in quoted rates. iii) On testing after completion if the desired earth resistance is not obtained the earthing will be redone at no extra cost.
All as per ser item No. 75.00 but using copper plate 60×60cm ×3.15mm thick electrode and 20×3mm copper strip as earthing lead.
Supply, spread, rolled and consolidated to gradient and camber of gravels 100 mm thick, including clearance of existing surface along with making clearance of 2 mtr surface side by side of HT fencing before spreading of gravels complete all as specified & directed.
Dismantling air break gang operated with drop out unit off capacities switches vertical/horizontal mounted including insulators and operating mechanism for repair/ replacement of broken/worn out components and insulators complete all as specified & directed.
Supply and Install, test and commission HT 11KV suitable for out door type, three phase gang operated air break switch having 3 nos Silicon rubber polymeric insulator on each phase and suitable for working for three phase suitable for vertical mounting fixed type of rating up to 400 A including square bar and GI pipe with suitable length to operate from ground including locking arrangement complete all as specified & directed.
Supply and Install test and commission 160 Amps for suitable for three phase 11 KV HT system with silicon rubber polymeric insulator type drop out fuses with necessary GI nut, bolts and washers complete all as specified & directed.
M&L for 1.2 m x 1.8 m flex board and drawing of substation schematic diagram using standard drafting tool AutoCAD. One set of drawing shall be submitted to the Deptt for scrutiny of drawing and final prints of drawing shall be submitted thereafter complete all as specified and directed. this item includes the under mentioned scope of work:- i. Preparation of drawing of Substation schematic diagram using standard drafting tools AutoCAD. ii. Duly printed Flex board with MS frame of size 1.2 m x 1.8 m and other fixing accessories. iii. Submission of soft copy. iv. Submission of three hard copies of drawing prepared on A3 size paper.
Taking shut down of HT electric supply, disconnecting all electric connection from the main HT Panel and taking out HT XLPE cable of existing size carefully without damaging it from ducts / trenches. Cleaning of ducts, shifting/ Relaying of serviceable HT cable of any size and making all electric connection in HT panel complete all as specified and directed.
M&L for dismantling concrete poles/ struts of any size and transporting to store and stacking complete all as specified & directed.
M&L for rough excavation not exceeding 1.5 m deep and getting out soft/loose soil complete all as specified & directed.
M&L for Cement concrete in foundations, filling and mass concrete type D2, 1:4:8 (40 mm graded aggregate) complete all as specified & directed.
M&L for brick work with sub class 'B' old sized bricks, straight or curved on plan exc 6m mean radius built in CM 1:6 complete all as specified & directed.
M&L for 40 mm thick cement concrete type B-0, 1:2:4 (12.5mm graded aggregate) complete all as specified & directed.
M&L for 15 mm thick screed bed or bedding layer of cement mortar 1:4 for laying floor finishes complete all as specified & directed.
M&L for rendering 15 mm thick cement plaster in 1:4 on fair faces of brick work or concrete surfaces, finished even and smooth without using extra cement complete all as specified & directed.
Taking shutdown, Disconnecting all electrical and earthing connections and carefully lifting existing serviceable transformer of capacity 315 KVA, outdoor type from old/ damaged foundation and shifting & mounting of the same at new foundation whereas directed by Engr In Charge and making all necessary electrical HT/LT and earthing connections incl replacement of worn out nut & bolts as required and testing of transformer to the satisfaction of engr-in-Charge complete all as specified and directed. Note:- 1. Quoted rate is deemed to include cost of T&P/crane/Hydra machine and necessary manpower to shift the transformer without damaging at a place whereas directed, if any damage to the transformer or its part then the same will be replaced by contractor with out any extra cost. 2. Necessary arrangement/ electrical items/equipments and electric connections on temporary basis will be made by the contractor to provide uninterrupted power supply to the hospital. No extra payment will be made against the same.
M&L for demolition of old brickwork of foundation built in cement mortar of transformer after shifting of transformer from foundation and removing all the debris, broken bricks etc obtained from demolished foundation and making the soil surface flat and clean by using the loader complete all as directed. [Note :- All the T&P required for the above jobs shall be arranged by the contractor at site and cost of the same is deemed to be included in the quoted rate]
Note for item No 1.00 to 91.00:- (i) It is not mandatory to hand over the work site/ bldg to the Contractor in one stretch. (ii) It may be handed over in peace-meal as and when the site/ bldg are vacated by the user including Sunday/ Holiday/ Night Hrs. Contractor shall make/ changes the execution plan accordingly. Any claim what so ever on this account shall not be admissible. (iii) Rate quoted by the Contractor shall be deemed to include on this account.
SANJEEV ENTERPRISES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .