| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Others-Already exceed MAT limit, so technical e-bids rejected |
| 4 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Others-Uploaded EMD CDR which is already used in other tender of this division |
Tender Value
Refer Docs
EMD Value
₹44,600
Closing Date
14 Jul 2022, 4:00 pmClosed
Executive Engineer
Electric Division JPDCL Udhampur
creation of substations with poles
2022_PDD_175496_1
ED/UDH/26 of 2022-23, dt. 22-06-2022
Open Tender
Electrical Works
Turn-key
90 days
At Kote Padsar, Lower Meer and Makool SuriBakrobud
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
Executive Engineer Electric Division JPDCL
₹44,600
18 Aug 2022
24 Jun 2022
16 Jul 2022
24 Jun 2022
14 Jul 2022
24 Jun 2022
24 Jun 2022 - 30 Jun 2022
Survey, Design, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of 11 KV line on 9 mtr long ST poles, 30 mm sq. ACSR condcutor for installation of transformer 25 KVA at Kote Padsar.
9 mtr. Long ST Pole (ST-410 SP-33)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
0.03 ACSR Weasel conductor
11KV Disc Insulators (Polymeric 45KN ) creepage distance 320 mm with tension fittings
11KV Pin Insulator (Polymeric) with Pins (12kv, 5KN) Creepage Distance 320mm
Galvanized Nuts and Bolts
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Design, Supply, Transportation, Carriage, Erection, Testing and Commissioning for creation/Installation of 25 KVA Sub Station at Kote Padsar under PRI Grants.
11/0.433kV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Aluminium Gland plate
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 kV Horn Gap Fuse Set 3 Phase 200A
70 mm² Single Core Cable, 1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST-410 SP33)
11KV Disc Insulators (Polymeric 45KN ) creepage distance 320 mm with tension fittings
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
Painting of sub station ST poles/cross arms/clamps with one coat of Red oxide and two coats of aluminium paint
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts, refilled with earth enhancement materials and earth Chamber with RCC slab cover.
Survey, Design, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 1 phase 2 wire LT 30 mm sq. Line on 8 mtr ST poles installation/Creation of transformer 25 KVA at Kote Padsar.
8 mtr. Long ST Pole (ST-410 SP15)
GI M-Clamp for shackle insulator
0.03 ACSR Conductor Weasel.
16KN Shackle Insulators
Galvinized Nuts and Bolts.
Painting of 8 mtr ST poles including crossarms/clamps with one coat of Red oxide Paint.
Painting of 8 mtr ST poles including crossarms/clamps with two coat of Aluminium Paint.
Danger Plates with Clamps
Anti Climbing Device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Cement bottoming 1:2:4 mix as per REC standards, 0.5 cum per pole
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Design, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of 11 KV line on 9 mtr long ST poles, 30 mm sq. ACSR condcutor for Installation/Creation of transformer 25 KVA at Makool Seri Bakrubud and Kultyar Bala.
9 mtr. Long ST Pole (ST-410 SP-33)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
0.03 ACSR Weasel conductor
11KV Disc Insulators (Polymeric 45KN ) creepage distance 320 mm with tension fittings
11KV Pin Insulator (Polymeric) with Pins (12kv, 5KN) Creepage Distance 320mm
Galvanized Nuts and Bolts
Danger Plates with Clamps
Anti Climbing Device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 32X3 mm for LT
Painting of 8 mtr ST poles including crossarms/clamps with one coat of Red oxide Paint.
Painting of 8 mtr ST poles including crossarms/clamps with two coat of Aluminium Paint.
Cement bottoming 1:2:4 mix as per REC standards 0.5 cum per pole
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Design, Supply, Transportation, Carriage, Erection, Testing and Commissioning for creation/Installation of 25 KVA Sub Station at Makool Seri Bakrubud and Kultyar Bala under PRI Grants.
11/0.433kV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Aluminium Gland plate
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 kV Horn Gap Fuse Set 3 Phase 200A
70 mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST-410 SP33)
11KV Disc Insulators (Polymeric 45KN ) creepage distance 320 mm with tension fittings
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
Painting of sub station ST poles/cross arms/clamps with one coat of Red oxide and two coats of aluminium paint
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
Survey, Design, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 1 phase 2 wire LT 30 mm sq. Line on 8 mtr ST poles for Installation/Creation of transformer 25 KVA at Makool Seri Bakrubud and Kultyar Bala.
8 mtr. Long ST Pole (ST-410 SP15)
GI M-Clamp for shackle insulator
0.03 ACSR Conductor Weasel.
16KN Shackle Insulators
Galvinized Nuts and Bolts.
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Painting of 8 mtr ST poles including crossarms/clamps with two coat of Aluminium Paint.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Parbat and Sons
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .