Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.8 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹36.6 L+₹4.2 L (13.0%)Rejected-AOC 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | L2 | Rejected-AOC L2 | |
| 3 | L3₹36.8 L+₹4.4 L (13.7%)Rejected-AOC 195 MAHESH NAGAR AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | L3 | Rejected-AOC L3 | |
| 4 | L4₹37.6 L+₹5.2 L (16.0%)Rejected-AOC | L4 | Rejected-AOC L4 | |
| 5 | L5₹39.6 L+₹7.2 L (22.4%)Rejected-AOC | L5 | Rejected-AOC L5 |
Tender Value
₹50 L
EMD Value
₹1 L
Closing Date
31 Jul 2020, 6:00 pmClosed
Sh AP Singh, IDSE, SE
HQ CWE Chandimandir
CA NO CWE/CHM(U)-30/2020-21 REPAIR/MAINT OF LT PANEL, LT FEEDER PILLER BOX AND ALLIED WORKS AT VARIOUS LOCATION IN CHANDIMANDIR MIL STN UNDER GE (U) CHANDIMANDIR
2020_MES_358190_1
CWE/CHM(U)-30/2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
HQ CWE Chandimandir
Class D, Cat b(i)
7 documents required · 7 mandatory
₹500
Yes
GE (U) Chandimandir
₹1 L
Yes
27 Oct 2020
4 Jul 2020
3 Aug 2020
4 Jul 2020
31 Jul 2020
18 Jul 2020
Amount
Excavation in trenches in hard/dense soil n. exc. 1.5m wide and n. exc. 1.5m in depth for laying of cables, or for poles, struts,stay etc. n exc 10 sqm on plan and n exc 1.5 m in depth and getting out including dressing/trimming sides and bottom complete all as specified and as directed.
Returning filling in soil including spreading, levelling, watering and well ramming in layers not exc 25 cm thick after the cable, cable cushioning and cable protection are laid complete all as specified and as directed.
Removal of surplus soil to a distance n. exc. 50m and depositing where directed at a level n.exc. 1.5m above the starting point complete all as specified and as directed.
Taking out old unserviceable LT UG Cable of size 10 sqmm 2 core to 25 sqmm 4 core including cable protection connected items of bricks/cable cover from trenches (wall/pole /duct) complete all as specified and directed by Engr-in Charge.
All as per item No 04 here-in-before but of size 3.5 core 50 sqmm to 70 sqmm complete all as specified and directed.
All as per item No 04 here-in-before but of size 3.5 core 95 sqmm to 185 sqmm complete all as specified and directed.
All as per item No 04 here-in-before but of size 3.5 core 240 sqmm to 400 sqmm complete all as specified and directed.
Supply, laying, jointing and testing LT under ground cable XLPE insulated and armoured and PVC sheathed 1100 volts grade, heavy duty with multistranded aluminum conductor of size 400 sqmm 3.5 core laid in trenches/ducts/ along poles/through pipe under road etc with new aluminum lugs complete all as specified and directed.
Supply, laying, jointing and testing LT under ground cable XLPE insulated and armoured and PVC sheathed 1100 volts grade, heavy duty with multistranded aluminum conductor of size 300 sqmm 3.5 core laid in trenches/ducts/ along poles/through pipe under road etc with new aluminum lugs complete all as specified and directed.
Supply, laying, jointing and testing LT under ground cable XLPE insulated and armoured and PVC sheathed 1100 volts grade, heavy duty with multistranded aluminum conductor of size 240 sqmm 3.5 core laid in trenches/ducts/ along poles/through pipe under road etc with new aluminum lugs complete all as specified and directed
Supply, laying, jointing and testing LT under ground cable XLPE insulated and armoured and PVC sheathed 1100 volts grade, heavy duty with multistranded aluminum conductor of size 185 sqmm 3.5 core laid in trenches/ducts /along poles/through pipe under road etc with new aluminum lugs complete all as specified and directed
Supply, laying, jointing and testing LT under ground cable XLPE insulated and armoured and PVC sheathed 1100 volts grade, heavy duty with multistranded aluminum conductor of size 150 sqmm 3.5 core laid in trenches/ducts/ along poles/through pipe under road etc with new aluminum lugs complete all as specified and directed
Supply, laying, jointing and testing LT under ground cable XLPE insulated and armoured and PVC sheathed 1100 volts grade, heavy duty with multistranded aluminum conductor of size 120 sqmm 3.5 core laid in trenches/ducts/ along poles/through pipe under road etc with new aluminum lugs complete all as specified and directed
Supply, laying, jointing and testing LT under ground cable XLPE insulated and armoured and PVC sheathed 1100 volts grade, heavy duty with multistranded aluminum conductor of size 70 sqmm 3.5 core laid in trenches/ducts/ along poles/through pipe under road etc with new aluminum lugs complete all as specified and directed
Laying only, jointing and testing LT cable PVC insulated armoured heavy duty 1100 volts grade with aluminium conductor of size not exceeding 10 sqmm 2 core laid in trenches/ducts/along poles/wall/ through pipe under road, jointing to OH conductor, LT panels, main switches etc with new cable size aluminium lugs complete all as specified and as directed. Note : (i) Cable will be issued under Sch 'B' from AGE E/M - store to contractor. (ii) Cutting chases in walls/ floor if required at site shall be deemed included in the quoted rate. (iii) Excavation & Earth work, pipe if required shall be measured and paid for separately.
All as per item No 15 here-in-before but of size 4 core 16 Sqmm complete all as specified and as directed.
All as per item No 15 here-in-before but of size 4 core 25 Sqmm complete all as specified and as directed.
All as per item No 15 here-in-before but of size 3.5 core 50 Sqmm complete all as specified and as directed.
All as per item No 15 here-in-before but of size 3.5 core 70 Sqmm complete all as specified and as directed.
All as per item No 15 here-in-before but of size 3.5 core 95 Sqmm complete all as specified and as directed.
All as per item No 15 here-in-before but of size 3.5 core 120 Sqmm complete all as specified and as directed.
All as per item No 15 here-in-before but of size 3.5 core 185 Sqmm complete all as specified and as directed.
All as per item No 15 here-in-before but of size 3.5 core 240 Sqmm complete all as specified and as directed.
All as per item No 15 here-in-before but of size 3.5 core 300 Sqmm complete all as specified and as directed.
All as per item No 15 here-in-before but of size 3.5 core 400 Sqmm complete all as specified and as directed.
M&L for straight throught joints heat shrinkable for XLPE/PVC insulated and sheathed aluminum conductor under ground cable 1100 volts 3.5/4 core 400 sqmm and testing after jointing complete all as specified and directed.
M&L for straight throught joints heat shrinkable for XLPE/PVC insulated and sheathed aluminum conductor under ground cable 1100 volts 3.5/4 core 240 sqmm to 300 sqmm and testing after jointing complete all as specified and directed.
M&L for straight throught joints heat shrinkable for XLPE/PVC insulated and sheathed aluminum conductor under ground cable 1100 volts 3.5/4 core 185 sqmm and testing after jointing complete all as specified and directed.
M&L for straight throught joints heat shrinkable for XLPE/PVC insulated and sheathed aluminum conductor under ground cable 1100 volts 3.5/4 core 95 sqmm to 120 sqmm and testing after jointing complete all as specified and directed.
M&L for straight throught joints heat shrinkable for XLPE/PVC insulated and sheathed aluminum conductor under ground cable 1100 volts 3.5/4 core 50 sqmm to 70 sqmm and testing after jointing complete all as specified and directed.
M&L for straight throught joints heat shrinkable for XLPE/PVC insulated and sheathed aluminum conductor under ground cable 1100 volts 3.5/4 core 25 sqmm to 35 sqmm and testing after jointing complete all as specified and directed.
Supply and laying 50mm outer dia, double walled, corrugated HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
Supply and laying 100mm outer dia, double walled, corrugated HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
Supply and laying 80 mm bore tube "light grade" galvanised iron pipe laid in trenches or fixed along poles with mild steel clamps or protection to GI earth strip/cable, complete all as specified and directed.
Supply and laying 100 mm bore tube "light grade" galvanised iron pipe laid in trenches or fixed along poles with mild steel clamps or protection to GI earth strip/cable, complete all as specified and directed.
Supply and laying 150 mm bore tube "light grade" galvanised iron pipe laid in trenches or fixed along poles with mild steel clamps or protection to GI earth strip/cable, complete all as specified and directed.
M&L for cutting of Road/boring underneath the road for passing the cable/pipe and making good with RCC 1:2:4 type B-1 where road cutting done to make the road surface fair and level complete all as specified and directed.
M&L plain cement concrete 1:2:4 type B-1 using 20 mm graded curshed stone aggregate in coping to pedestal of poles including necessay from work, fair finished surface, chamfered or rounded edges complete all as specified and directed.
M&L plain cement concrete 1:3:6 type C-2 using 40 mm graded curshed stone aggregate in foundation filling & mass concrete for poles/struts/stays assembly complete all as specified and directed.
Taking down old unserviceable LT Panel of any size/capacity including all accessories from the existing position after disconnecting all electric connections complete all as specified and directed.
supply, installation, testing and commissioning of out door type LT feeder pillar box of size not less than 1.8m x1.2m x 0.40 m, factory made CPRI approved ; openable from front & rear, double door with flush type hinges and flush cylindrical locks, dust and vermin proof, fabricated with angle iron 40 x 40 x 6mm and 2.00 mm thick CRCA sheet, duly painted with two coats of synthetic enamel paint over a coat of red oxide primer complete with 4 Nos heat shrinkable insulated copper bus bars of 1000 Amp rating including all connections with copper busbar strip. LT panel /feeder pillar box shall be provided with danger notice plate with skull & bone sign, making all electrical incoming and out going electrical cable connection with new lugs, glands to be provided at cable entries, including 04 No. legs of not less than 50cm long each below the base of panel made of
angle iron support 50x50x6mm for grouting purpose and grouted in PCC (1:2:4) type B1 (using 20 mm graded stone aggregate) complete all as specified and as directed and comprising of following accessories:-
Incoming :- (i) MCCB four pole 415 volts, 50 Hz, 630 Amps, breaking capacity 35/36 KA with adjustable thermal & adjustable magnatic protection release = 01 No, (ii) Change over switch ON LOAD type, 415 Volt 50 Hz, AC, 4 pole I-O-II, open execution capacity 630 Amps - 01 No (iii) Phase indicator lamp RBY complete with copper control wiring = 01 set of three, (iv) Panel mounted multifunctional digital meter 3 lines LCD display in 96x96 Sqmm flush mounted case accuracy class-I. complete with all accessories including 3 Nos 200/5A CT =1 No. Outgoing :- (i) MCCB TP 415 volts, 250 Amps, breaking capacity 25 KA with adjustable thermal adjustable magnetic protection release = 01 Nos. (ii) MCCB, TP 160 Amp, 415 volt, 50 Hz breaking capacity not less than 25 KA with adjustable thermal and adjustable magnetic protection release complete = 03Nos (iii) MCCB, TP 100 Amp, 415 volt, 50 Hz breaking capacity not less than 25 KA with adjustable thermal and adjustable magnetic protection release complete = 04Nos
(a) Degree of protection. (b) Temperature rise. (c) Dielectric Properties. (d) Short circuit withstand current. (e) Effectiveness of protective circuits. (f) Clearance & creepage distance. (g) Mechanical operation. Polycarbonate enclosure shall be fire retardant & self extinguishing in accordance with IEC 60 695-2-11, DIN VDE 0304 part 3,UL subject 94 for Flammability V-2. It shall be tested at Glow wire test for 960 deg. Cent. The impact strength of polycarbonate enclosures/ boards i.e. the degree of protection against mechanical load shall be in accordance with EN 50298-98 for IK 08.
The lid closing and opening shall be done by quick fastering spring mechanism latches. Suitable accessories for armoured cable shall be supplied with the panel. These accessories shall not be fitted with screws, so that there is no loss of IP, but should be auto fit. The board manufacturer shall submit the copy of type test reports for polycarbonate thermoplastic board only. Each board shall have individual routine test report of the manufacture & the panel board will have the following accessories. (a) 4 Nos heat shrink insulated bus bar of 1.5 times of incoming MCCB including all connection with aluminum strip. (b) Incoming MCCB four pole, 415 Volts, 50 HZ, 400 Amps, breaking capacity 50 KA with adjustable thermal and adjustable magnetic release with Ics = 100% Icu -01 Nos. (c) Out going MCCB four pole, 415 Volts, 50Hz, 250 Amps breaking capacity 36 KA with adjustable thermal and adjustable magnetic release with Ics = 100% Icu -01 No. (d) MCCB four pole 415 Volts ,50 HZ, 160Amps, breaking capacity 25 KA adjustable thermal and adjustable magnetic release with Ics = 100% Icu - 03 Nos .
Supply, installation, testing and commissioning of out door type LT feeder pillar/ distribution boards thermoplastic polycarbonate IP 65 in accodance with EN 60 529, dust proof, rust proof, water proof & weatheproof, metering panel (1.10 X 1.875 X 0.60 m ) shock proof, rust proof, corrosion free, acid & chemical resistant, fire retardant & self extinguishing, UV resistant, Silica and halogen free recyclable material, glow wire tested at 9600 C in accordance with IEC 60 695-2-11. Type tested as per IEC 60 439-1. Total insulated with system. The manufacture of boar/panel shall submit a copy of CPRI test report of degree of ingress protection IP 65 in accordance with IEC 60529. The gasket material shall be Polyurethane ; while the gasket shall be internally embedded. The manufacture of board/ panel shall submit a copy of type test report of a board made out of polycarbonate thermoplastic panel in accordance with IEC60439-1.
Polycarbonate enclosure shall be fire retardant & self extinguishing in accordance with IEC 60 695-2-11, DIN VDE 0304 part 3,UL subject 94 for Flammability V-2. It shall be tested at Glow wire test for 960 deg. Cent. The impact strength of polycarbonate enclosures/ boards i.e. the degree of protection against mechanical load shall be in accordance with EN 50298-98 for IK 08. The lid closing and opening shall be done by quick fastering spring mechanism latches. Suitable accessories for armoured cable shall be supplied with the panel. These accessories shall not be fitted with screws, so that there is no loss of IP, but should be auto fit. The board manufacturer shall submit the copy of type test reports for polycarbonate thermoplastic board only. Each board shall have individual routine test report of the manufacture & the panel board will have the following accessories.
(a) 4 Nos heat shrink insulated bus bar of 1.5 times of incoming MCCB including all connection with aluminum strip. (b) Incoming MCCB four pole, 415 Volts, 50 HZ, 400 Amps, breaking capacity 50 KA with adjustable thermal and adjustable magnetic release with Ics = 100% Icu -01 Nos. (c) Out going MCCB four pole, 415 Volts, 50Hz, 200 Amps breaking capacity 36 KA with adjustable thermal and adjustable magnetic release with Ics = 100% Icu -01 No. (d) MCCB four pole 415 Volts ,50 HZ, 125 Amps, breaking capacity 25 KA adjustable thermal and adjustable magnetic release with Ics = 100% Icu - 04 Nos.
Taking down old unserviceable load bank/LT feeder pillar box of any size/capacity including all accessories from the existing position after disconnecting all electric connections complete all as specified and directed.
Supply, installation testing and commissioning of load bank/feeder pillar with incomer of 250 amps MCCB 4 pole and outgoing 100 amps MCCB 4 pole (4 nos) 4 way with copper bus bar of capacity 1.5 times of incoming MCCB double door type,dust and vermin proof, fabricated out of 2.00 mm CRCA sheet of size not less than 1250 x 1250 x 150 mm duly painted with two coats of synthetic enamel paint over a coat of red oxide primer and MS channel frame of ISMC 75 at base of panel only and 04 Nosegs of not less than 50 cm long each below the base of panel made of angle iron 50 x 50 x 6mm for grouting purpose and grouted in PCC 1:2:4 type B1( using 20 mm graded stone aggregate) complete all as specified and directed by Engr-in-Charge. Note:- Manufacture of load bank should be OEM of switch gear.
Taking down old unserviceable ACB any type and Supply, installation testing and commissioning new LT ACB of 630 Amps four pole mannual draw out microprocessor based, 415 Volts, 50 Hz suitable for existing location alongwith replacement of burnt aluminum bus bar with connected nut bolts and lugs with new aluminum bus bar /nut bolts/lugs complete all as specified and directed by Engr-in-charge.
Taking down old unserviceable ACB any type and Supply, installation testing and commissioning new LT ACB of 800 Amps four pole mannual draw out microprocessor based, 415 Volts, 50 Hz suitable for existing location alongwith replacement of burnt aluminum bus bar with connected nut bolts and lugs with new aluminum bus bar /nut bolts/lugs complete all as specified and directed.
Taking down old unserviceable ACB any type and Supply, installation testing and commissioning new LT ACB of 1000 Amps four pole mannual draw out microprocessor based, 415 Volts, 50 Hz suitable for existing location alongwith replacement of burnt aluminum bus bar with connected nut bolts and lugs with new aluminum bus bar /nut bolts/lugs complete all as specified and directed.
Taking down old unserviceable MCCB any size/capacity up to 400 amps complete all as specified and directed at site by Engr-in-charge.
Supply and fix MCCB four pole 400 amps 415 volt , 50 Hz breaking capacity not less than 36 KA with thermal magnetic release, adjustable thermal and adjustable magnetic setting with spreader links Ics=100 % of Icu complete all specified and directed.
Supply and fix MCCB four pole 320 amps 415 volts, 50 Hz breaking capacity not less than 36 KA with thermal magnetic release, adjustable thermal and adjustable magnetic setting with spreader links Ics=100 % of Icu complete all specified and directed.
Supply and fix MCCB four pole 250 amps 415 volts, 50 Hz breaking capacity not less than 36 KA with thermal magnetic release, adjustable thermal and adjustable magnetic setting with spreader links Ics=100 % of Icu complete all specified and directed.
Supply and fix MCCB four pole 200 amps 415 volts , 50 Hz breaking capacity not less than 25 KA with thermal magnetic release, adjustable thermal and adjustable magnetic setting with spreader links Ics=100 % of Icu complete all specified and directed.
Supply and fix MCCB four pole 160 amps 415 volts, 50 Hz breaking capacity not less than 25 KA with thermal magnetic release, adjustable thermal and adjustable magnetic setting with spreader links Ics=100 % of Icu complete all specified and directed.
Supply and fix MCCB four pole 125 amps 415 volts, 50 Hz breaking capacity not less than 25 KA with thermal magnetic release, adjustable thermal and adjustable magnetic setting with spreader links Ics=100 % of Icu complete all specified and directed.
Supply and fix MCCB four pole 100 amps 415 volts, 50 Hz breaking capacity not less than 25 KA with thermal magnetic release, adjustable thermal and adjustable magnetic setting with spreader links Ics=100 % of Icu complete all specified and directed.
M&L for painting of LT out door panel in front, top, rear and both sides above ground level with two coats of synthetic enamel paint as per existing colour after preparation of surface and writing panel number complete all as specified and directed by Engr-in-Charge.
M&L in repairs electric panel doors fabricated from MS sheet as per existing size and shape and fixed with hinges by properly welding and checking for proper opening and closing complete all as specified and directed.
Disconnecting of electric connection from LT Panels and dressing of cable including replacement of burnt out aluminum lugs with new lugs, nut bolts etc complete including necessay wiring of feeder pillar box with copper conductor cable, excavation and earth work all as directed by Engr-in-Charge.
Supply and fix multimeter flush mounitng type, digital type, 50 Hz, 96 x 96 mm complete all as specified and directed by Engr-in-Charge.
Supply and fix indicator lamp, LED type of colour red, bule and yellow (Set of three) complete all as specified and directed by Engr-in-Charge.
Supply and fix godreg type lock for LT panel matching with the existing complete all as specified and directed by Engr-in-Charge.
Supply and fix aluminum bus bar of different size and capacity required as per site including PVC insulating materials and cutting, welding, making holes etc complete all as specified and directed by Engr-in-Charge.
Supply and fix copper bus bar of different size and capacity required as per site including PVC insulating materials and cutting, welding, making holes etc complete all as specified and directed by Engr-in-Charge.
Removing wild grass, vegetation, creeper etc aroung LT panel/ installations, climbing up towards poles and stay assembly including cleaning bottom surface of pole, stay assemble of area not less than 1m x 1m by surface dressing not exceeding 0.5 m deep in soft/loose soil complete all as specified and directed by Engr-in-Charge.
Supply and fix APFC panel relay 8 steps, 415 volts, complete all as specified and directed. Make : L&T, Cat No- CS909020000 or equivalent as approved by GE.
Supply and fix APFC panel relay 12 steps, 415 volts, complete all as specified and directed. Make : L&T, Cat No - CS909030000 or equivalent as approved by GE.
Suppy and fix capacitor duty connector MO C12.5, 440 volt, 3 Ph, 50 Hz, detatching type early make contacts, seprate termination for damping resistors, encapsulated damping resistor assembly, built in surge suppressor, low pick up VA consumption complete all as specified and directed by Engr-in- Charge. Make : L&T, Cat No - CS96321 or equivalent as approved by GE.
Suppy and fix capacitor duty connector MO C25, 440 volt, 3 Ph, 50 Hz, detatching type early make contacts, seprate termination for damping resistors, encapsulated damping resistor assembly, built in surge suppressor, low pick up VA consumption complete all as specified and directed by Engr-in- Charge. Make : L&T, Cat No - CS96322 or equivalent as approved by GE.
Supply and fix heavy duty capacitors cylindrical series 12.5 kVAr rating, 440 volt complete all as specified and directed by Engr-in-Charge. Make : L&T or equivalent as approved by GE.
Supply and fix heavy duty capacitors cylindrical series 25 kVAr rating, 440 volt complete all as specified and directed by Engr-in-Charge. Make : L&T or equivalent as approved by GE.
Supply and fix MCB 40 Amps, D curve 3 pole, 415 volt complete all as specified and directed by Engr-in-Charge.
Supply and fix MCB 32 Amps, D curve 3 pole, 415 volt complete all as specified and directed by Engr-in-Charge.
Supply and fix MCB 63 Amps, C curve 4 pole, 415 volt complete all as specified and directed by Engr-in-Charge.
Supply and fix in replacement of high power LED street light fitting energy saving luminaire with lens, capacity 60 W with system efficacy (lm/w) not less than 90 W lumens per watt, total system lumen not less than 5400 lumens, PF not less than 0.95, CRI not less than 70, colour temp 5000K to 6500K, surge protection not less than 5KV, high pressure die cast alumimum alloy LM6 housing IP - 65/66 class 1 protection, toughened glass cover, driver efficency >85% with constant output of current and voltage against input voltage variation 120 to 270 volt at 50 Hz (+5%), THD<10% complete all as specified and directed by Engr-in-Charge.
Supply and fix in repair 1X 20 W LED tube light fitting TARA -Ei Series alongwith 20 W LED tube rod, MS powder coating white plastic end caps retrofitted with T8 LED tube complete all as specified and directed by Engr-in-Charge. Make - C&S, Ordering Code No - LTDC1220LED/WDI (LTDC161820WLED+LT4F20WLEDT8/WDI) or equivalant mentioned in Appx 'B'.
S&F in replacement change over switch ON LOAD type, 415 Volt 50 Hz, AC, 3 pole I-O-II Positon, door interlock feature, in Sheet Steel enclsoures, capacity 250 Amps rated current, manually operated conforming to IS:13947 of latest edition with high thermal and dynamic strength to withstand short circuit current level of 80 KA rms complete all as specifed and direcated.
S&F in replacement change over switch ON LOAD type, 415 Volt 50 Hz, AC, 3 pole I-O-II Position door interlock feature, in Sheet Steel enclosures, capacity 315 Amps rated current manually operated conforming to IS:13947 of latest edition with high thermal and dynamic strength to withstand short circuit current level of 80 KA rms complete all as specified and directed.
S&F in replacement change over switch ON LOAD type, 415 Volt 50 Hz, AC, 3 pole I-O-II Position door interlock feature, in Sheet Steel enclosures, capacity 400 Amps rated current manually operated conforming to IS:13947 of latest edition with high thermal and dynamic strength to with stamp short circuit current level of 80 KA rms complete all as specified and directed.
S&F in replacement change over switch ON LOAD type, 415 Volt 50 Hz, AC, 3 pole I-O-II Position door interlock feature, in Sheet Steel enclosures, capacity 600 Amps rated current manually operated conforming to IS:13947 of latest edition with high thermal and dynamic strength to with stamp short circuit current level of 80 KA rms complete all as specified and directed.
Taking down old u/s earthing with GI earth plate, GI strip earthing lead (where feasible and economical) with GI Strip, watering pipe and protection pipe and disposing of the material having scrap value and making good the spot all as specified and directed by Engineer-in-Charge.
M& L for providing earthing complete with galvanised steel earth electrode plate of size 600x 600 x6 mm thick burried directly in ground in a earth pit not lessthan 2.25 mtr deep below ground level with the top edge of the earth plate at a depth not less than 1.5 mtr below ground level , connected to and including galvanised iron strip of size 32 x6 mm earth strip by means of bolts & nuts ,check nuts and washers and connected to earth test point connected to earth point / transformer /panel / feeder pillor box all as specified and directed by Engr-in-charge including necessary earth work in any type of soil ,disposal of surplus soil not exceeding 50 m ( the rate also includes for cost of charcoal & salt in alternate layers of 15 cm thickness , providing suitable size of GI pipe( medium grade) for watering ,funnel, wirmesh, PCC sconnected PCC chamber(1:3:6) type C1 , RCC pit cover , charcoal ,salt including provision of earth lead protected by 40 mm dia light grade GI pipe and 20 mm medium gradeGI pipe for watering complete all as specified and directed by Engr-in-charge.
M&L for 40mm bore tube "light grade" galvanized laid in trenches or fixed along poles with mild steel clamps or protection to GI earth strip/cable, complete all as specified and directed by Engineer-in-Charge.
M&L for GI strip 32 x 6 mm for earthing complete all as specified and directed by Engr-in-Charge.
Dismantling of old vintage steel tubular poles alongwith insulators and disposing off from site complete all as specified and directed.
Supply, transporting to site, errecting and fixing in position 9 metre long, Steel tubular swaged poles complete with cast iron/mild steel base plate, finial taper plug, bolts, nuts washers & screws as specified, type 410, SP-31 IS 2713 marked, drilling of necessary hole including painting to steel tubular poles, with two coats of aluminium paint over a coat of red oxide primer on exposed surface of poles and with black bituminous paint on portion of pole embedded in concrete and painting 3 Nos bands/strips with fluorescent PO red synthetic enamel paint 30 cms wide strip at 30 cms spacing from plinth block and numbering of poles complete all as specified and directed by Engineer-in-Charge.
M&L for drawing out of LT ACB 4 pole 415 volts of capacity 630/800/1000/1200 amps form the LT panel and servicing/ repair the same for proper functioning, lightening the loose hardware part and loose connection and lubricating the all mechanism, clean all contacts with fine emery paper and CRC, replacement of burnt/defective parts applying petroleum jelly on the contacts, refixing in the original position and checking for proper functioning complete all as specified and directed by Engr -in-Charge. Note - Defective parts will be measured and paid seprately under the respective items.
Supply only fixed contacts as per sample suitable for 630/800/1000/1200 amps capacity of LT ACB of any make complete all as specified and directed by Engr-in-Charge.
Supply only moving contacts as per sample suitable for 630/800/1000/1200 amps capacity of LT ACB of any make complete all as specified and directed by Engr-in-Charge.
Supply only spring charging and operating mechanism as per sample suitable for 630/800/1000/1200 amps capacity of LT ACB of any make complete all as specified and directed by Engr-in-Charge.
Supply only shunt trip coil 240 volts as per sample suitable for 630/800/1000/1200 amps capacity of LT ACB of any make complete all as specified and directed by Engr-in-Charge.
Supply only CT as per sample suitable for 630/800/1000/1200 amps capacity of LT ACB of any make complete all as specified and directed by Engr-in-Charge.
R D Bansal
Raman Electric Trading Co
AK Construction Co
ELECTROMAX OF INDIA
Guru Kirpa Trading Company
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .