Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | FIRST₹36.5 LAccepted-AOC | ₹36.5 L Quoted ₹36.1 L | FIRST | Accepted-AOC BEING LOWEST |
| 2 | SECOND₹39.5 LRejected-Finance | ₹39.5 L | SECOND | Rejected-Finance BEING NOT LOWEST |
| 3 | THIRD₹39.6 LRejected-Finance | ₹39.6 L | THIRD | Rejected-Finance BEING NOT LOWEST |
| 4 | FORTH₹40.5 LRejected-Finance | ₹40.5 L | FORTH | Rejected-Finance BEING NOT LOWEST |
| 5 | FIFTH₹40.8 LRejected-Finance 704 SILVER DEAL DAFFODIL WING 1 B T KAWADE ROAD PUNE 411 001 | PUNE | PUNE | MAHARASHTRA | 411001 | ₹40.8 L | FIFTH | Rejected-Finance BEING NOT LOWEST |
Tender Value
₹39 L
EMD Value
₹78,000
Closing Date
13 Jun 2022, 6:00 pmClosed
GE (AF) MARATHAHALLI
GE AF MARATHAHALLI WIND TUNNEL ROAD, KEMPAPURA, YEMALUR POST, BANGALORE. PIN- 560037
SPECIAL REPAIR REPLACEMENT OF UG CABLE IN AKASH VIHAR AND PROVN OF SECURITY LIGHTS AT SDI UNDER GE AF MARATHAHALLI
2022_MES_523889_1
8943/E8
Open Tender
Civil Works
Item Rate
180 days
GE (AF) MARATHAHALLI
ALL A PER ENIT
10 documents required · 10 mandatory
₹500
GE (AF) MARATHAHALLI
₹78,000
Yes
11 Aug 2022
13 May 2022
18 Jun 2022
13 May 2022
13 Jun 2022
31 May 2022
Amount
Taking down of old unserviceable LT panel board of size 1.80 X 1.80 X 1.00 Mtrs and Supply, installation, testing and commissioning of outdoor type cubicle panel board suitable for 3 phase 4 wire 415 V, 50 Hz CPRI approved for 415 volts factory fabricated in an approved factory having modern fabrication process, powder coating in approved shade having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS : 8623/93 comprising. The outer shell shall be made out of 3 mm thick CRCA sheet and MS angle section 50x50x6 mm base frame factory fabricated of height not less than 60 cm completewith PCC with front openable, double door system lockable/openable. The bottom of the outer shell contains a detachable plate having size with glands. The outer shell shall be mounted on suitable mild steel stand having zinc coating not less than 80 microns. Provision of threaded earthing stud at bottom and lifting lugs of suitable size at top to lift the panel safely shall be made. The degree of protection of outer shell shall be IP - 56. Inner shell shall be made out of 2.0 mm thick CRCA sheet duly compartmentalized for each control gear, TPN aluminum bus bar of rating not less than the 1.5 times the rated capacity of the incomer MCCB. The TPN bus bar shall be insulated with colour coded heat shrinkable sleave. All control wires shall be with 2.5 sqmm multi strand copper conductor and shall be propely bunched, tied, ferruled for proper identification and crimped with adequate size of lugs all as specified and directed by Engr in charge. (For outdoor LT panel MAP near 500 KVA transformer ) Make:Peptek/Dollar/Lotus
INCOMING :
(a) Air circuit breaker 4P 800 Amp 50 KA Manual fixed type connecting from bus bar to ACB (1 No) Making provn to accommodate MCCBs, MCCBs with suitable size Aluminium bus bar and separate chamber each MCCBs with doors fixed on hinges,Make:ABB/ Legrand / Schneider
(b) LED indication lamp RYB/RRR with control MCB -01 set
OUTGOING :
(a) MCCB TPN 400 Amps 4 pole with breaking capacity 35 KA with adjustable thermal magnetic release - 4 Nos, Make:ABB/ Legrand / Schneider
(b) MCCB TPN 250 Amps 4 pole with breaking capacity 25 KA with adjustable thermal magnetic release-1 NoMake:ABB/ Legrand / Schneider
(d) 1200 A TPN+E Aluminium Busbar with Heat Shrinkable Sleeves
(e) Multi-functional digital meter (VFA+W/VA/PF/WH) . NOTE :- above job includes jointing of all incommer/ outgoing cables along with suitable lugs
Taking down of old unserviceable LT panel board of size 1.80 X 1.80 X 0.60 Mtrs and Supply, installation, testing and commissioning of outdoor type cubicle panel board suitable for 3 phase 4 wire 415 V, 50 Hz CPRI approved for 415 volts factory fabricated in an approved factory having modern fabrication process powder coating in approved shade having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS : 8623/93 comprising. The outer shell shall be made out of 3 mm thick CRCA sheet and MS angle section 50x50x6 mm base frame factory fabricated of height not less than 60 cm complete with PCC with front openable, double door system Front and back openable along with locking arrangements. The bottom of the outer shell contains a detachable plate having size with glands. The outer shell shall be mounted on mild steel stand having zinc coating not less than 80 microns. Provision of threaded earthing stud at bottom and lifting lugs of suitable size at top to lift the panel safely shall be made. The degree of protection of outer shell shall be IP - 56. Inner shell shall be made out of 2.0 mm thick CRCA sheet duly compartmentalized for each control gear, TPN aluminum bus bar of rating not less than the 1.5 times the rated capacity of the incomer MCCB. The TPN bus bar shall be insulated with colour coded heat shrinkable sleave. All control wires shall be with 2.5 sqmm multi strand copper conductor and shall be propely bunched, tied, ferruled for proper identification and crimped with adequate size of lugs all as specified and directed by Engr in charge. (For outdoor LT panel ) Make:Peptek/Dollar/Lotus
INCOMING :
(a) MCCB 4 pole 400 Amp 36 KA 415 Volt -1 No Make: - ABB/ Legrand / schneider
Bus Bar : 600 Amps capacity Aluminium bus bar with sleeves -4 Nos
OUTGOING
(a) MCCB 3 pole 250 Amps 4 pole 25 KA 415 Volt (incommer)-01 No. Make:ABB/ Legrand / Schneider
(b) MCCB 3 pole 63 Amps 16 KA 415 Volt- 9 Nos. Make: ABB/ Legrand / Schneider
(c) MCCB 3 pole 32 Amps 16 KA 415 Volt- 2Nos. Make:ABB/ Legrand / Schneider
(e) Indication lamp RYB/RRR-set of 03 -01 No
Taking down of old unserviceable LT panel board of size 1.80 X 1.20 X 0.60 Mtrs and Supply, installation, testing and commissioning of outdoor type cubicle panel board suitable for 3 phase 4 wire 415 V, 50 Hz CPRI approved for 415 volts factory fabricated in an approved factory having modern fabrication process powder coating in approved shade having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS : 8623/93 comprising. The outer shell shall be made out of 3 mm thick CRCA sheet and MS angle section 50x50x6 mm base frame factory fabricated of height not less than 60 cm complete with PCC with front openable, double door system Front and back openable along with locking arrangements. The bottom of the outer shell contains a detachable plate having size with glands. The outer shell shall be mounted on mild steel stand having zinc coating not less than 80 microns. Provision of threaded earthing stud at bottom and lifting lugs of suitable size at top to lift the panel safely shall be made. The degree of protection of outer shell shall be IP - 56 .Inner shell shall be made out of 2.0 mm thick CRCA sheet duly compartmentalized for each control gear, TPN aluminum bus bar of rating not less than the 1.5 times the rated capacity of the incomer MCCB. The TPN bus bar shall be insulated with colour coded heat shrinkable sleave. All control wires shall be with 2.5 sqmm multi strand copper conductor and shall be propely bunched, tied, ferruled for proper identification and crimped with adequate size of lugs all as specified and directed by Engr in charge. (For outdoor LT panel ) Make:Peptek/Dollar/Lotus
(a) MCCB 4 pole 100 Amps 25 KA 415 V -1 No.thermal adjustable - 08 to 1 in magnetic. Make:ABB/ Legrand / Schneider
BUS Bar :- 150 Ampscapacity alunimum bus bar with RYB N sleeves -4 Nos
OUTGOING :
(b) MCCB 3 pole 63 Amps 16 KA 415 Volt- 4 Nos. Make : ABB/ Legrand / Schneider
(c) Multi-functional digital meter (VFA+W/VA/PF/WH) . NOTE :- Above job includes jointing of all incommer/ outgoing cables along with suitable lugs
(d) Indication lamp RYB/RRR-set of 03 Nos - 01 set
M & L excavation in trenches in hard/dense soil not exc 1.5 mtr wide and not exc 1.5 mtr in depth for laying of cables/errection of pole etc complete all as specified and as directed.
M & L for returning, filling in trenches incl spreading leveling watering and well ramming in layers with hard/dense soil not exc 25 cm thick each in each layer complete as specified and as directed
M & L for removing excavated soil to a distance not exc 50 metres and depositing where directed at a level n. exc.1.5 mtr above the starting point complete all as specified and as directed
M & L for sand cushioning with a layer of M-Sand 23 cm thick under and above the cable complete all as specified and as directed
M & L sub class burnt bricks for cable protection complete as specified as directed
Taking down of old UG cable and Supply and laying cable XLPE insulated screened PVC bedded galvanised steel strip or wire armored,electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 240 Sqmm 3½ core connected with suitable lugs including taking out the existing unserviceable cable complete as specified and as directed .
Taking down of old UG cable and Supply and laying cable XLPE insulated screened PVC bedded galvanised steel strip or wire armored,electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 185Sqmm 3½ core connected with suitable lugs including taking out the existing unserviceable cable complete as specified and as directed .
Taking down of old UG cable and Supply and laying cable XLPE insulated screened PVC bedded galvanised steel strip or wire armored,electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 Sqmm 3½ core connected with suitable lugs including taking out the existing unserviceable cable complete as specified and as directed .
Taking down of old UG cable and Supply and laying cable XLPE insulated screened PVC bedded galvanised steel strip or wire armored,electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 Sqmm 3½ core connected with suitable lugs including taking out the existing unserviceable cable complete as specified and as directed .
Taking down of old UG cable and Supply and laying cable XLPE insulated screened PVC bedded galvanised steel strip or wire armored,electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 Sqmm 3½ core connected with suitable lugs including taking out the existing unserviceable cable complete as specified and as directed .
Taking down of old UG cable and Supply and laying cable XLPE insulated screened PVC bedded galvanised steel strip or wire armored,electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 Sqmm 3½ core connected with suitable lugs including taking out the existing unserviceable cable complete as specified and as directed .
Taking down of old UG cable and Supply and laying cable XLPE insulated screened PVC bedded galvanised steel strip or wire armored,electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 Sqmm 4 core connected with suitable legs including taking out the existing unserviceable cable complete as specified and as directed .
Taking down of old UG cable and Supply and laying cable XLPE insulated screened PVC bedded galvanised steel strip or wire armored,electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 Sqmm 4 core connected with suitable lugs including taking out the existing unserviceable cable complete as specified and as directed .
Boring of holes under road ,pavement hard standing by trenchless technology using ultra sounding,technique including HDPE pipe 110 mm dia complete as specified and as directed
M & L for GI tubing light grade 80mm with all accessories for cable protection fixed on poles/bldgs of laid in trenches incl necessary MS clamps, bolts and nuts etc all as specified and as directed.
M & L for GI tubing light grade 50mm with all accessories for cable protection fixed on poles/bldgs of laid in trenches incl necessary MS clamps, bolts and nuts etc all as specified and as directed.
M & L for PCC 1:2:4 type C1 with 20mm graded crushed stone aggregate in copping of poles/filling road cutting, stays,including necessary form work all as specified and as directed
S&F steel tublar swaged pole 9 meter long complete with cast iron base plate finial plug ,bolt, nuts and screw as specified type 410 SP-31 including excavation, copping with PCC up to existing poles including demolition old RCC poles all as specified and as directed
Material and labour for earthing including testing, commissioning complete with galvanized steel earth plate electrode 600X600X6mm thick buried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5M below normal ground level connected to GI earth lead wire 4.0mmdia by means of nuts, bolts, check nuts and washer of GI steel and connecting to testing point including provision of test point and all as shown in electrical plate No. 3 of SSR Pt I. The work is inclusive of necessary earth work and PCC chamber in type B1 (1:2:4) with 8 CTD bar reinforcement both ways at 140 mm bents to centre complete including taken out old earthing complete all as directed . Note: (i) The earth resistance shall be below 1 ohms during testing.
Material and labour for earthing including testing, commissioning complete with galvanized steel earth plate electrode 600X600X6mm thick buried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5M below normal ground level connected to GI earth strip wire 25 X 4 mm dia by means of nuts, bolts, check nuts and washer of GI steel and connecting to testing point including provision of test point and all as shown in electrical plate No. 3 of SSR Pt I. The work is inclusive of necessary earth work and PCC chamber in type B1 (1:2:4) with 8 CTD bar reinforcement both ways at 140 mm bents to centre complete including taken out old earthing complete all as directed . Note: (i) The earth resistance shall be below 1 ohms during testing.
Supply and fixing LED street light fitting 35 Watts, 230V AC out door type with high pressure die cast aluminium housing and heat ressistant complete with driver lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/ 66 protection , built-in control gear complete with LED 35 watts, connector block with all accessories pre wired including necessary electric connection all as specified and as directed.
M&L terminal box and Supply and fixing moulded PVC / SMC Junction boxes out door type, weather proof, of size 240 x 130 x 95 mm to be fixed at the bottom of street light pole complete with suitable clamp , nut, bolt, washers and suitable glands ,to accommodate 01 No MCB SP 2.5 Amps 10 KA, with suitable connectors for incoming and outgoing connections , complete all as specified and directed by Engr-in-Charge. Make :- Cat No GSJB 2817 of Sintex or Hensel or Polycon or its equivalent .
Supply and laying 25 sqmm, 4 core LT UG cable XLPE insulated screened PVC bedded, galvanised steel strip wounded ,electric power cable of size 25 Sqmm 4 core 1100volts with stranded aluminium conductor and making connection with suitable lugs complete all as specified and directed.
M& L House service bracket by sing 25 mm dia 1. 2 mtrs long GI pipe light grade bent to shape and necessary fixing arrangements to existing steel tubular pole for fixing of street light and fixing the bracket with two no of U clamps with necessary bolts nuts washers etc all as specified.
S&F LED flood light 170 watt 230V, AC outdoor type with terminal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp including removal of existing unserviceable fittings and making wall surface good to match existing wall surface complete all as specified and as directed. Make : Havells, Crompton Greaves, Phillips
Vishwas Enterprises
RAMSON TRADERS
Pacific Enterprises
M/S - KRUPA ELECTRICALS
Charms Engineers Inc
VSHVAS CIVIL AND ELECTRICAL SERVICES PRIVATE LIMITED
kamadhenu Electricals
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .