Executive Engineer ETD Hardoi
220KV sub station Lucknow Road Hardoi
Overhauling of 145KV circuit breaker at 132KV sub station Shrimau and 36KV circuit breakers at 132KV sub station Sandila Baghauli and Shrimau
2023_UPTCL_850099_3
07/ETDH/2023-24
Open Tender
Electrical Works
Fixed-rate
60 days
Shrimau
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
Executive Engineer ETD Hardoi
₹2,000
17 Nov 2023
9 Nov 2023
17 Nov 2023
9 Nov 2023
17 Nov 2023
9 Nov 2023
Amount
Major overhauling of 145 KV SF-6 Circuit Breaker of ABB make spring type installed at bays at 132 KV Sub-station, Shrimaui. The work includes overhauling of control block assembly. Opening latch, anti pumping assembly. Opening, cleaning & greasing of motor charging system, replacement of worn out parts. Checking of shock absorber, closing damper etc. adjustment of all gaps, cleaning & greasing of leavers, connecting rods, CAM, Disc. CAM etc, checking of machanism assembly for wear & tear, rectification/ repairing of worn out parts. Chcking of limit switch, power contact, auxiliary contractors for proper functioning. Checking and re-tighting of all electrical connections, checking of gas leakage from copper pipe assembly of gas system, measurement of closing tripping time of Circuit Breaker, measurement of contact resistance of Circuit Breaker. (i) 132KV Shrimau-APJPL line
Repairing/Rectification and general overhauling of 36 KV VCB of CGL/ABB /STELMEC/SIEMENS make circuit breakers at 132 KV Substations:- Work consists of repairing/ Rectification of non functioning and general overhauling of Complete spring charging mechanism assembly of 36 KV VCB of CGL/Shreem/Siemens/ Stelmec/ ABB make C.B., cleaning, greasing of horizontal rod assembly, checking and tightening of all electrical connection in the terminal block, dismantling of spring charging mechanism parts, cleaning, greasing and its proper adjustment, opening close/trip coil assembly, cleaning its plunger and adjustment its plunger air gap, checking spring charging motor, replacement of its carbon brushes wherever required, finally checking smooth operation of closing/tripping of the breaker both by local and remote. (i) Following 33KV feeders at 132KV sub station Sandila 33KV Sandila town, 33KV Malhera, 33KV Behendar, 33KV UPSIDC-I, 33KV UPSIDC-II, 33KV SAF Yeast, 33KV LV side of 40MVA T/F-I, 33KV LV side of 40MVA T/F-II
(ii) Following 33KV feeders at 132KV sub station Baghauli 33KV Chhibramau, 33KV Ruiya
(ii) Following 33KV feeders at 132KV sub station Shrimau 33KV Sawaijpur Tehsil, 33KV Sawaijpur R/L
Verma Enterprises
vivaan enterprises
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .