Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.5 LAccepted-Finance BABU RAM THAKUR NIWAS BELOW UTTAM GAS AJANCY DISTT SHIMLA | SHIMLA | HIMACHAL PRADESH | 171001 | ₹13.5 L | L1 | Accepted-Finance accepted |
| 2 | L2₹13.8 LRejected-Finance VILLAGE KARASA TEHSIL ROHRU DISTT SHIMLA | SHIMLA | HIMACHAL PRADESH | ₹13.8 L | L2 | Rejected-Finance Rejected |
| 3 | L3₹14 LRejected-Finance | ₹14 L | L3 | Rejected-Finance Rejected |
| Sl No | Description | Qty | Unit | ZAFIR HUSSAIND L3 | NIKHIL TEGTA L2 | Babu Ram L1 |
|---|---|---|---|---|---|---|
| 1.00 | Supply, erection, testing & commissioning of horizontal spindle,horizontal split casing,radial split Single, /Multistages centrifugal pumps or combination of pumps, in series/parallel of recommended make such as Mather and Platt/KSB//Becon weir/Kirloskar/ BE/Jyoti or any other make approved from Jal Shakti Vibhag as per BIS 1520-1980 with upto date ammendments read with BIS 9137-1978 or latest edition to suitable for lifting clear water for under mentioned characteristics with bronze impellers/ priming funnels casing ring and shaft sleaves or bronze. shaft of steel grade-with cast iron casing coupled directly through a flexible coupling on a common C.I./Cast steel base platel (base plate to be from the manufacturers of the pumping unit only) to slip ring/squirrel cage screen protected drip proof induction motor of standard make such as Kirloskar/Crompton/Bhel/NGEF/ GEC/ Siemen/Jyoti/ABB or any other make approved from Jal Shakti Vibhag suitable for operation on 415(+) /-5% volts, 50 cycles/ second, 3 phase AC electric supply. The power of electric motor should be atleast 10% in excess of the maximum power required by the pump in the operation range of (+) 10% and (-)25% of the duty point head. The motor should be as per IS:325-1978 with upto date ammendments read with IS:900-1972. It should include cost of bearing nuts, bolts and pointing etc. and should meet the following requirements Pump Set 50HP Only. Per Set(50HP) Make- WKFI Modle-40/14/HWD | 1 | Per Set (50 HP ) Make -WKFI Model -40/14/HWD | 14,00,000 ₹14 L | 13,75,000 ₹13.8 L | 13,50,000 ₹13.5 L |
| 1.01i) Discharge (Q) 2.95 LPS each pump. ( 2 no. pumps working at a time Simultaneously) | ||||||
| 1.02ii) Total Dynamic head 420 mtrs. | ||||||
| 1.03a) LWL of sump well (h) 2200 mtr. | ||||||
| 1.04b) Shaft level 2200 mtr. | ||||||
| 1.05c) Level at discharge point 2350 mtr. | ||||||
| 1.06d) suction lift (+) head 372 mtr. | ||||||
| 1.07e) Discharge head 420 mtr. | ||||||
| 1.08f) Static head 470 mtr. | ||||||
| 1.09iii) Rising main | ||||||
Tender Value
₹4.5 L
EMD Value
₹9,000
Closing Date
25 Jun 2025, 11:00 amClosed
Executive Engineer
JSV Division Rohru
SH C o Replacement of old pump set of WKFI 40 14 HWD only Pump Set 50HP Stage 2nd
2025_HPIPH_107987_1
JSV-RD-AB-Tender/25-1844-1910
Open Tender
Civil Works - Others
90 days
Rohru
Tender Document
7 documents required · 7 mandatory
₹500
Yes
EE Rohru
₹9,000
Yes
7 Jan 2026
19 Jun 2025
25 Jun 2025
19 Jun 2025
25 Jun 2025
19 Jun 2025
Amount
Supply, erection, testing & commissioning of horizontal spindle,horizontal split casing,radial split Single, /Multistages centrifugal pumps or combination of pumps, in series/parallel of recommended make such as Mather and Platt/KSB//Becon weir/Kirloskar/ BE/Jyoti or any other make approved from Jal Shakti Vibhag as per BIS 1520-1980 with upto date ammendments read with BIS 9137-1978 or latest edition to suitable for lifting clear water for under mentioned characteristics with bronze impellers/ priming funnels casing ring and shaft sleaves or bronze. shaft of steel grade-with cast iron casing coupled directly through a flexible coupling on a common C.I./Cast steel base platel (base plate to be from the manufacturers of the pumping unit only) to slip ring/squirrel cage screen protected drip proof induction motor of standard make such as Kirloskar/Crompton/Bhel/NGEF/ GEC/ Siemen/Jyoti/ABB or any other make approved from Jal Shakti Vibhag suitable for operation on 415(+) /-5% volts, 50 cycles/ second, 3 phase AC electric supply. The power of electric motor should be atleast 10% in excess of the maximum power required by the pump in the operation range of (+) 10% and (-)25% of the duty point head. The motor should be as per IS:325-1978 with upto date ammendments read with IS:900-1972. It should include cost of bearing nuts, bolts and pointing etc. and should meet the following requirements Pump Set 50HP Only. Per Set(50HP) Make- WKFI Modle-40/14/HWD
i) Discharge (Q) 2.95 LPS each pump. ( 2 no. pumps working at a time Simultaneously)
ii) Total Dynamic head 420 mtrs.
a) LWL of sump well (h) 2200 mtr.
b) Shaft level 2200 mtr.
c) Level at discharge point 2350 mtr.
d) suction lift (+) head 372 mtr.
e) Discharge head 420 mtr.
f) Static head 470 mtr.
iii) Rising main
a) Length 950 mtr.
b) Dia 65mm.
iv) Pumping hour 8 hours.
v) Altitude of installation above MSL mtr.
vi) Characterstics of water. Clear cold water
a) Temperature 0C.
b) Ambient temp. 0C.
c) Turbiduty JTU
d) Alkanality
e) Size of the solid NIL mm.
f) Other
Providing and installation of fully/semi automatic star delta starter control pannel (powder coated) 415 V3 phase 50 HZ consists of contractors, motor relay coil voltage 200-400 V, LED indication Amber, Red and Green LED for various indication, current and voltage meter , over voltage protection , timer , fuse unit and push buttons (No and NC Type of reputed make such as L &T /ABB/Scheider , BCH or equivalent in accordance wtih latest IEC and IS Specification sluice valve.
Providing and fixing cast iron double flanged sluice valve of class II 65mm dia of leader/ Behl Kirlsker/GIED/ Kilburn/Fouress make nsuction side as per the relevent IS code.Sluice valve
Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader/of reputed make of suitable size cast iron /cast steel double flanged sluice valve having size equal to delivery of pump and capable of with standing nominal seat pressure of 52kg/cm^2. The sluice valve shall conform to BIS 780-1984 latest with up to date ammendments. However if the seat pressure exceeds the limits prescribed in BIS 780 then the sluice valves shall be of cast steel conforming to class 150 ASA (Seat pressure 21Kg/cm^2) or class 300 ASA (seat pressure 52Kg/cm^2) as per BS 1414 (40mm dia)Sluice valve
Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader/of suitable size cast iron /cast steel double flanged swing check type reflux valve having bye pass arrangement & size equal to delivery of pump for withstanding nominal seat pressure of 52Kg/cm/^2 The reflux valve shall conform to BIS 5312-1984 (part I) latest with up to date ammendments. However if the seat pressure exceeds the limits prescribed in BIS 5312 then the reflux valves shall be cast steel conforming to class 150 ASA (Seat pressure 231Kg/cm^2) or class 300 ASA (seat pressure 52Kg/cm^2)) as per BSI 1414 (40mm dia) Reflux valve
Providing and fixing double flanged cast steel reflux valve of Leader/BHEL/Kilosker/Kilburn/ GLED/Fouress make and of dia for rising main having byepass arrangement for rising main andcapable withstanding the
Supply of standard make 100mm dia circular dial pressure of suitable range Fiebeg/ Bourden/Precision make with all accessories such as stop cock, copper tubing etc. conforming to BIS 3624-1987 latest with up to date ammendments.Pressure guage
Providing, laying, testing & commissioning at site in trenches bevelled ended conforming to IS/ISO:3183-2007 latest having wall thickness & per Rmt. weight as mentioned below & capable of withstanding required test pressure as prescribed in BIS code, in random lengths of 5.5 to 6.5 mtr. The pipe ends shall be bevelled suitable for butt welding, including the cost of jointing with butt welding confirming to IS 816-1969 or latest as applicable and with uptodate ammendements (leak proof) in three layers at site of work welding rods of Advani/oerliken make/ISI marked (welding rods 3mm to 4mm) and all allied accessories whatever required for welding at site, tail please, tees, bends & other special manufactured from parent pipes as applicable to the particular reach and of approved specification as per site conditions and cutting of pipe wherever required as per site requirement including carriage in all leads & lifts and as directed by the Engineer-in-charge. The pipe shall have zinc coating inside & out side confirming to IS-4736-1986 or latest with upto date ammendments & shall be engraved with API- X 46 etc. The sizes of various components to be as under: Suction Pipe l) Suction Pipe ---------- mm dia ii) Delivery Pipe ---------- mm dia iii) Common Header ---------- mm dia. and will be extended up to 5 mtr from the outer wall of the pump house in th direction to be jointed.
Providing and laying copper PVC insulated armoured power cable (One vable carrying all the three phasees) of suitable size and capacity to motors and all other electrical equipments as per IS:1554 (P-1) 1988 or latest with up to date ammendments of seimence/Gloster/IEC/EICO/National/Grandly make including all other accessories such as thimbles, flexible pipe, solder, nut & bolts, vable gland etc. laid in pipe or trenches under floor.
P/L double loop earthing with crpper plate 600x600x3mm thick electrode complete with material such as charcoal, common salt, GI pipes, thimbles, nuts & bolts, digging of pits, GI wiring & 25x5mm copper strips of required capacity conforming to BIS 3043-1987 latest with up to date ammendmentsfor above motors & other electrical equipment.
NIKHIL TEGTA (BID ID -527825)
ZAFIR HUSSAIND (BID ID -527846)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid