Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 116 SHANTINAGAR ROAD BHADRAKALI UTTARPARA HOOGHLY WEST BENGAL 712232 | HOOGHLY | WEST BENGAL | 712232 | Admitted-Finance |
| 2 | Admitted-Finance 57 B FEEDER ROAD GROUND FLOOR 57 B FEEDER ROAD BARRACKPORE NORTH 24 PARGANAS WEST BENGAL 700120 | 24 PARAGANAS NORTH | WEST BENGAL | 700120 | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
| 5 | Admitted-Finance | Admitted-Finance |
Tender Value
₹75.4 L
EMD Value
₹1.5 L
Closing Date
8 Jun 2023, 12:00 pmClosed
Superintending Engineer (EM)
Office o the Superintending Engineer (EM), Estate (EM) Works Section, Old Building IIT KGP
Supply, Installation, Testing and Commissioning of Air conditioning work for Architecture and Regional Planning (ARP) Lab complex at old Biotech building of IIT Kharagpur.
2023_IITKG_753233_1
IITKGP/IW/RAC/ARP/2023
Open Tender
Plant Protection Input/Equipment Works
Item Rate
100 days
IIT Kharagpur
Please refer Tender documents.
8 documents required · 8 mandatory
₹0
₹1.5 L
Yes
Estate (EM) Works Section, Old Building IIT KGP
13 Jul 2023
15 May 2023
9 Jun 2023
15 May 2023
8 Jun 2023
15 May 2023
24 May 2023
Amount
Supply, Installation, Testing & Commissioning of Air Cooled type outdoor units of VRF system having hermetically sealed inverter scroll/twin rotary compressor, condenser coil fabricated from Seamless Copper tube & Plate type Al. Fins of Multi Row, Axial Flow, top discharge throw condenser fan, Condenser fan - motor unit, insulated refrigeration piping, power / control wiring with TPN MCB & encloser, and earthing, external wiring between Indoor & Outdoor units, all system controls-safety. The system should have flexibility to handle total 280 Rmt of ref. piping. ODU shall be placed on structure with heavy duty anti vibrational pad to protect the system from any kind of unwanted vibration. The system shall have minmum COP of 3.7 at ARI condition as per CPWD guidelines. Each Outdoor units with High Pressure switch, Fan driver overload protector, Over current relay, Inverter Overload Protector & Fusible Plug. The unit shall be suitable for 415 ± 10 % volts, 50 Hz, 3 phase AC supply, and IP protection will be suitable for outdoor installation. The VRF System shall have green ref. gas only- R410A/ R407
Indoor Units Supply, Installation, Testing & Commissioning of Indoor units address setting and capacity as mentioned below. Multi speed motor, coil section with DX coil, outer cabinet, drain pan mechanism insulation, pipe connections, clamp metal, washer fixing plate, sealing pads, screws, clamps, washer for hanging bracket & insulation for fitting, fresh air intake connector for cassettes etc. of various capacities as per specifications. Power cabling (3mtr from unit) with conduit from power socket & plug top to indoor is inclusive of price.
Hi-Wall Type Indoor Unit With Cordless Remote Control - Capacity - 2.0TR
Hi-Wall Type Indoor Unit With Cordless Remote Control - Capacity - 1.0TR
VRF Y JOINTS FOR BRANCH DISTRIBUTION REFRIGERENT PIPE JOINTS WITH PRECAST INSULATION
REMOTE CONTROLLER
Supply, installation, testing & commissioning of Cordlesss remotes for VRF indoor units
SITC of VRF Refrigerant Piping: Supply, installation, testing & commissioning of Seamless heavy gauge Copper piping of following size duly insulated with 13 mm/ 19mm thk. Nitrile Rubber Insulation covered with aluminium foil ( As per Specified with K Value of 0.027-0.029 K Cal/Hr.M Deg C at 0-16 Deg C) . Refrigeration piping will have to be taken in the piping rack / Support individually connecting to all indoor units for the respective floors. Even necessary supports, fittings, valves & ref. joints where ever required will be included. The exposed refrigerent insulated piping shall be covered with UV Resistance canvass coating.
41.3 mm O.D.(with 19 mm insulation )
38.1 mm O.D.(with 19 mm insulation )
31.8 mm O.D.(with 19 mm insulation )
28.6 mm O.D.(with 19 mm insulation )
25.4 mm O.D..(with 19 mm insulation )
22.2 mm O.D..(with 19 mm insulation )
19.05 mm O.D..(with 19 mm insulation )
15.88 mm O.D..(with 19 mm insulation )
12.7 mm O.D..(with 19 mm insulation )
22.2 mm O.D..(with 13 mm insulation )
19.1 mm O.D..(with 13 mm insulation )
15.9 mm O.D..(with 13 mm insulation )
12.7 mm O.D.(with 13mm insulation )
9.52 mm O.D.(with 13mm insulation )
6.35 mm O.D.(with 13mm insulation )
Supply, Installation and Testing of rigid PVC Drain Piping complete with fittings, supports as per specifications and duly insulated with 6 mm thick closed cell nitrile rubber insulation.
50 mm dia
32 mm dia
25 mm dia
SITC of GI perforated Cable Tray for the refrigerant pipe hanging & Covering
Supply & fixing of control cum transmission wiring of Copper conductor Shielded cable along with PVC conduit / casing for looping between indoor & outdoor VRF system.
2 C X 1.5 Sq. mm (Communication cable)
3 C X 1.5 Sq. mm - PVC insulated & PVC sheathed cable for IDU power connection
Supply, installation, testing & commissioning of Power Cabling with termination to individual Outdoor units.( From Power Panel to VRF ODU)
Supply, Installation Testing & Commissioning along with all necessary cabling of Central Station with basic control system such as ON/OFF, Operation Mode & Temp , Air Quantity & ALARM CODE display incase of any error occur etc upto 63 nos IDU
Civil foundation of VRF ODU
Making wall opening for passage in the wall/glass for ref & drain pipes and cables and making good of the same for all the indoor/ outdoor units.
Decorative Pelmets of required size for IDUs with 16 mm thich anti termite laminated board.
Comprehensive AMC of the VRF system for four years after DLP.
Comprehensive AMC 1st Year after DLP
Comprehensive AMC 2nd Year after DLP
Comprehensive AMC 3rd Year after DLP
Comprehensive AMC 4th Year after DLP
GATES
AIR Q SOLUTIONS
Shinryo Suvidha Engineers India Pvt. Ltd.
EVAC ENGINEERING PROJECTS PVT. LTD.
M/s Auto-Tech Projects Pvt. Ltd
UNIVERSAL ENERGY SOLUTIONS PVT. LTD.
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .