Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.9 LAccepted-AOC 011 NAGAREWADI 612 NAGAREWADI POST PADALI TALUKA SHIRUR KASAR DISTRICT BEED 413249 BEED MAHARASHTRA 413249 UDYAM MH 05 0079863 | BEED | MAHARASHTRA | 413249 | L1 | Accepted-AOC Lowest | |
| 2 | L2₹5.0 L+₹1.1 L (29.5%)Rejected-Finance PULGAON | L2 | Rejected-Finance Not Lowest | |
| 3 | L3₹5.5 L+₹1.7 L (43.0%)Rejected-Finance | L3 | Rejected-Finance Not Lowest | |
| 4 | L4₹5.7 L+₹1.9 L (48.3%)Rejected-Finance 84 A VIJAY NAGAR COLONY LALGHATI PO NAYAPURA BHOPAL 462032 | 462032 | L4 | Rejected-Finance Not Lowest | |
| 5 | L5₹8.2 L+₹4.3 L (111.4%)Rejected-Finance | L5 | Rejected-Finance Not Lowest |
Tender Value
₹9.3 L
EMD Value
₹18,700
Closing Date
21 Jan 2020, 6:00 pmClosed
GE PULGAON
GE PULGAON
PROVN OF SECURITY LIGHT HIGH MAST NEAR CHILDREN PARK IN CRLC LINE AT CAD PULGAON
2019_MES_282135_3
8780/PUL/E8
Open Tender
Electrical and Maintenance Works
Works
120 days
GE PULGAON
As per tender documents
7 documents required · 7 mandatory
₹500
Yes
GE PULGAON
₹18,700
Yes
29 Jan 2020
31 Dec 2019
23 Jan 2020
31 Dec 2019
21 Jan 2020
14 Jan 2020
31 Dec 2019 - 21 Jan 2020
Amount
Supply and Installations, testing and commissioning of high mast light fabricated structure 16 metre hight comprising the following fixtures and specification all as specified and as directed. (i) Hotdip Galvanised MS sheet of 3 mm thick as per BSEN 10025. (ii) Mast shaft shall be in two section, tapered with top dia 150 mm and bottom dia 350(+/ -) 10 mm and suitable for wind velocity as per IS 875 part-III. (iii) Lantern carriage:- made of Galvanised MS angle/Circular pipe sutiable for 600 Kg load in two segments with jointing arrengment including 3 point suspension system and head frame canopy and with mounting breakets and accessories. (iv) Raising and lowering arrengment:- SS wire rope self lubricating type 6 mm dia (7/19 construction) double drum winch, motor/manual opareted capable to take load of 600 Kg. (v) Twin dome aviation obstraction light with two Nos of LED light fitting complete. (vi) Lighting protection provided with aluminium strips 25 x 3 mm with air termination rod suitable for highmast light. (vii) Power tool: Consisting of 1.5 HP motor, single speed, reversible, 3 phase 440 Volts 50 HZ AC supply. (viii) RCC foundation with M-15 (normal mix) and foundation bolts with anchors plates and fixing arrangment complete as per manufacturer. (ix) Note:- Installation should be done as per manufacturer instruction.
Supply and fix Energy saving LED 150W IP65 light body flood light, light bay luminaire
Earthing complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of the plate not less than 1.5 metre below normal ground level connected to galvanized iron 32 x 6 mm strip as earthing lead by means of galvanized steel bolts, nuts check nuts and washers and other end connected with to ,Panel Board etc as directed including funnel, 20mm bore, light grade galvanized iron pipe, wire mesh charcoal of coal dust and common salt in alternative layer all around the earth electrode compacted thickness 15cm with concrete pit in PCC 1:3:6 type C1 50mm thick pre cast RCC 1:2:4 type B1with 8mm dia cover slab set in CM (1:4) re-enforcement with 8mm dia deformed bars @ 15cm C/C and suitable handle of 10mm dia MS round bars, including earth work as required complete all as shown in electrical plate No 3 of MES Schedule Part I and testing complete all as specified and as directed.
Supply, laying, and testing UG cable PVC insulated,XLPE armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross sectional area 10 sqmm 4 core and including necessary cable lugs, bolts, nuts and washers complete all as specified and directed.
Excavation in trenches not exc 1.5m wide and not exc 1.5M depth for laying of cables GI/CI pipe lines getting out including forming bottom surface to required level and gradient in hard/dense soil all as specified and directed.
Returning and filling in excavated soil including spreading leveling, watering, well ramming in layers not exc 25 Cm thick complete all as specified and directed.
Removing of excavated materials not exceeding 50 Mtrs and depositing where directed at a level not exceeding 1.5 Mtrs above the starting point all as specified and directed.
Material and labour for sand cushioning with dry river sand in trenches for cushioning of underground cable line including spreading, leveling, well ramming completed all as specified and directed. Note:- Only punned thickness will be measured and paid.
Supplying and laying un-reinforced precast concrete cable cover,Class LV, Type I, flat, size 250 mm x 150mm x 40mm all as specified and as directed by Engr-in-charge. Note:- The grade of cable cover shall be M-20
Supply and laying 50 mm bore GI tube light grade as in cable protection pipe including all fittings the end of pipe shall be sealed with sealing compound complete all as directed.
M/S Maa Durga Constructions,Pulgaon
M/s MM TRADERS
POONAM ELECTRIC INDUSTRY
Vaidehi E Link
shanti enterprises
Bidder Name
Vaidehi E Link
MAHARASHTRA ENTERPRISES
shanti enterprises
M/S Maa Durga Constructions,Pulgaon
POONAM ELECTRIC INDUSTRY
M/s MM TRADERS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .