Tender Value
Refer Docs
EMD Value
₹80,000
Closing Date
2 Mar 2024, 6:00 pmClosed
GE AF UDHAMPUR
GE AF UDHAMPUR
COMPREHENSIVE MAINTAINCE OF FLAME PROOF LIGHT FITTING/FIXTURE/FLAME PROOF EXHAUST FAN ,FLAME PROOF DBS ,SWITCHES/WIRING AT VARIOUS BLAST PAN OR OTHER LOCATION ALONGWITH CERTAIN REPAIR/ MAINTAINCE WORK OF FIRE ALARM WITH SMOKE DETECTOR
2024_MES_640587_1
GE/AFU-60/2023-24
Open Tender
Civil Works
Item Rate
270 days
GE AF UDHAMPUR
AS PER NIT AND TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE AF UDHAMPUR
₹80,000
Yes
3 Apr 2024
3 Feb 2024
4 Mar 2024
3 Feb 2024
2 Mar 2024
17 Feb 2024
3 Feb 2024 - 10 Feb 2024
Amount
M&L in repair Explosion proof point wiring for one light/bell /buzzer contrlled by one way switch with 1.5 Sqmm 1100 Volts grade PVC FRLS insulated fire retrardent multi stranded flexible copper conductor cable in and including ERW rigid steel in concealed conduit ISI marked with all flame proof conduit fittings and accessories fixed is walls/ceiling with proper fixing arrangment including one number continuous run of 1.5 Sqmm PVC insulated fire retardent multistandard copper conductor cable as earth continuity conductor fixed to earth terminal and metallic body of light fittings/fan and socket etc complete all as suitable with colour coding according to norms for Class Zone IE Ex II C ,complete all as specified.
M&L in repair Explosion proof point wiring for one light/bell/buzzer contrlloed by one way switch with 1.5 Sqmm 1100 Volts grade PVC FRLS insulated fire retrardent multi stranded flexible copper conductor cable in and including ERW rigid steel in surface conduit ISI marked with all flame proof conduit fittings and accessories fixed is walls/ceiling with proper fixing arrangment including one number continuous run of 1.5 Sqmm PVC insulated fire retardent multistandard copper conductor cable as earth continuity conductor fixed to earth terminal and metallic body of light fittings/fan and socket etc complete all as suitable with colour coding according to norms for Class Zone IE Ex II C , complete all as specified.
M&L in repair Explosion proof point wiring for one light/bell/buzzer controlled by one way switch with 1.5 Sqmm 1100 Volts grade PVC FRLS insulated fire retrardent multi stranded flexible copper conductor cable in and including ERW rigid steel in existing conduit ISI marked with all flame proof conduit fittings and accessories fixed is walls/ceiling with proper fixing arrangment including one number continuous run of 1.5 Sqmm PVC insulated fire retardent multistandard copper conductor cable as earth continuity conductor fixed to earth terminal and metallic body of power point etc complete all as suitable with colour coding according to norms for Class Zone Ex II C complete all as specified.
M&L in repair Explosion proof point wiring 2.5 Sqmm 1100 Volts grade PVC FRLS insulated fire retrardent multi stranded flexible copper conductor cable in and including ERW rigid steel in concealed conduit ISI marked with all flame proof conduit fittings and accessories fixed is walls/ceiling with proper fixing arrangment including one number continuous run of 2.5 Sqmm PVC insulated fire retardent multistandard copper conductor cable as earth continuity conductor fixed to earth terminal and metallic body of power point complete all as suitable with colour coding according to norms for Class Zone Ex II C complete all as specified.
M&L in repair Explosion proof point wiring for 2.5 Sqmm 1100 Volts grade PVC FRLS insulated fire retrardent multi stranded flexible copper conductor cable in and including ERW rigid steel in surface conduit ISI marked with all flame proof conduit fittings and accessories fixed is walls/ceiling with proper fixing arrangment including one number continuous run of 2.5 Sqmm PVC insulated fire retardent multistandard copper conductor cable as earth continuity conductor fixed to earth terminal and metallic body of power point complete all as suitable with colour coding according to norms for Class Zone Ex II C for all as specified.
M&L in repair Explosion proof point wiring for 4.0 Sqmm 1100 Volts grade PVC FRLS insulated fire retrardent multi stranded flexible copper conductor cable in and including ERW rigid steel inexisting conduit ISI marked with all flame proof conduit fittings and accessories fixed is walls/ceiling with proper fixing arrangment including one number continuous run of 4.0 Sqmm PVC insulated fire retardent multistandard copper conductor cable as earth continuity conductor fixed to earth terminal and metallic body of power point complete all as suitable with colour coding according to norms for Class Zone Ex II C for all as specified.
M&L in repair Explosion proof point wiring for 4.0 Sqmm 1100 Volts grade PVC FRLS insulated fire retrardent multi stranded flexible copper conductor cable in and including ERW rigid steel in concealed conduit ISI marked with all flame proof conduit fittings and accessories fixed is walls/ceiling with proper fixing arrangment including one number continuous run of 4.0 Sqmm PVC insulated fire retardent multistandard copper conductor cable as earth continuity conductor fixed to earth terminal and metallic body of power point etc complete all as suitable with colour coding according to norms for Class Zone Ex II C for, all as specified.
M&L in repair Explosion proof point wiring for 4.0 Sqmm 1100 Volts grade PVC FRLS insulated fire retrardent multi stranded flexible copper conductor cable in and including ERW rigid steel in surface conduit ISI marked with all flame proof conduit fittings and accessories fixed is walls/ceiling with proper fixing arrangment including one number continuous run of 4.0 Sqmm PVC insulated fire retardent multistandard copper conductor cable as earth continuity conductor fixed to earth terminal and metallic body of power point etc complete all as suitable with colour coding according to norms for Class Zone IE Ex II C for , all as specified.
Explosion proof rotary switch single pole on and off with cable termination box of 10 Amps rating 230 Volts Class E EX II C suitable for class I Zone I, all as specified. Make :- Sudhir/Shyam
Supply and repair of Explosion proof rotary switch single pole on and off with cable termination box of 16 Amps rating 250 Volts Class E EX II C suitable for class I Zone I, all as specified. Make :- Sudhir/Shyam
Flame proof switch socket & plug combined in LM6 cable termination box in LM6, 16 Amps, 250 Volts, 2P+earth all as specified. Make :- CAT No SSPL/2C/1010 of shyam or equivalent in Sudhir
Flame proof switch socket & plug combined in LM6 cable termination box in LM6, 25 Amps, 250 Volts, 2P+earth all as specified. Make :- CAT No SSPL/2C/1010 of shyam or equivalent in Sudhir
M&L in repair of Flameproof intergral wellglass luminaire epoxy finish LM6 aluminium alloy housing with heat resistant and toughened glass cover painted MS wire guard and eye bolt LED 60 Watt incuding all accessories pre wired with polycarbonate cover polyester resin encloser and central locking system, complete all as specified.
M&L in repair of Flameproof non-intergral wellglass luminaire epoxy finish LM6 aluminium alloy housing with heat resistant and toughened glass cover painted MS wire guard and eye bolt 70 Watt incuding all accessories pre wired with polycarbonate cover polyester resin encloser and central locking system, complete all as specified
S&Fin repairsof LED light fitting 2 x 20 /16 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum hosing with heat resistant toughened glass with LED tube light fixtures driver, holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size.
M&L in repair Bulk Head LED light fitting 30 Watt flame proof, CMRI certified commended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum housing with heat resistant toughened glass, with LED tube light fixtures driver, holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size.
M&L in repair of LED light fitting 1x16/20 Watt 4 Feet flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum hosing with heat resistant toughened glass with LED tube light fixtures driver, holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size.
M&L in repair Flame proof Flood light fitting 50 watt LED With IP65 of protection with reflector wire guard 50 watt LED ,complete all as specified and direcetd.
Supply and replacement of Flame proof LED 90W with IP 65 of protection with reflector &wire guard 90watt led flood light fitting ,complete all as specified and direcetd.
Supply and replacement of Flame proof Flood light fitting 150 watt LED With IP65 protection with reflector wire guard 150 watt LED ,complete all as specified and direcetd.
Supply and replacement of Flame proof Flood light fitting 200 watt LED With IP65 protation with reflector wire guard 200 watt LED ,complete all as specified and direcetd.
M&L in rpelacement of Flame Proof Weather Proof tube LED type ,1x20 Watt fitting ,230 Volt 50HZ Including minor repair as such Replacement of connector,Holder (Bipin) ,starter etc all as specified and as directed
M&L in rpelacement of Flame Proof Weather Proof tube LED type ,2x20 Watt fitting ,230Volt 50HZ Including minor repair as such Replacement of connector,Holder (Bipin),starter etc all as specified and as directed.
M&L in replacement of Flameproof control gear box epoxy finish LM6 aluminium alloy housing including all accessories prewired with polycarbonate cover polyster resin encloser and central locking system, all as specified complete all as specifeid and as directed
M&L in repair for rewinding of ceiling fans motor of any make with super enameled copper winding wire of appropriate size/same gauge as original including packing insulating material, soldering, varnishing capacitor, ball bearing, bush,locking pin and certain minor repair etc assembling and testing and refixing of same places complete all as specified.
M&Lin repair for rewinding of Exhaust fans motor of any make with super enameled copper winding wire of appropriate size/same gauge as original including packing insulating material, soldering, varnishing capacitor, ball bearing, bush,locking pin and certain minor repair etc assembling and testing and refixing of same places complete all as specified.
M&L in repair of FLP/WP Lighting distribution panel board encloser single pole & neutral 240 volts 12way complete with appropriate size bus bar and neutral link suitable for class 1 Zone 1 & Ex IIC suitable for & including following accessories : (i) incomming : MCB 2P,16 Amps/25Amps/25A-1No Out going: MCB 1P ,6Amps/10A-2Nos with internal busbar & wiring up to terminal Make :- Sudhir or equivalent in shyam
M&L in repair of FLP/WP Lighting distribution panel board size (300x300x190 mm)encloser single pole & neutral 240 volts 6way complete with appropriate size bus bar and neutral link suitable for class 1 Zone 1 & Ex IIC suitable for & including following accessories : (i) incomming : MCB 2P,32 Amps-1No Out going: MCB 1P ,6 Amps/10A-4Nos with internal busbar & wiring up to terminal Make :- Sudhir or equivalent in shyam
M&L in repair of FLP/WP Lighting distribution panel board size (330x350x190 mm)encloser single pole & neutral 240 volts 8 way complete with appropriate size bus bar and neutral link suitable for class 1 Zone 1 & Ex IIC suitable for & including following accessories : (i) incomming : MCB 2P,32 Amps-1No Out going: MCB 1P ,6 Amps/10A-6Nos with internal busbar & wiring up to terminal Make :- Sudhir or equivalent in shyam
M&L in repair of FLP/WP Lighting distribution panel board size (330x350x190 mm)encloser single pole & neutral 240 volts 10way complete with appropriate size bus bar and neutral link suitable for class 1 Zone 1 & Ex IIC suitable for & including following accessories : (i) incomming : MCB 2P,63 Amps-1No Out going: MCB 1P ,6 Amps/10A-8Nos with internal busbar & wiring up to terminal Make :- Sudhir or equivalent in shyam
M&L in repair of FLP/WP Lighting distribution panel board size (300x300x900 mm)encloser single pole & neutral 240 volts 12way complete with appropriate size bus bar and neutral link suitable for class 1 Zone 1 & Ex IIC suitable for & including following accessories : (i) incomming : MCB 2P,63 Amps-1No Out going: MCB 1P ,6 Amps/10A-8Nos with internal busbar & wiring up to terminal Make :- Sudhir or equivalent in shyam
M&L in repair of FLP/WP Lighting distribution panel board size (420x420x250 mm)encloser single pole & neutral 240 volts TPN 4way complete with appropriate size bus bar and neutral link suitable for class 1 Zone 1 & Ex IIC suitable for & including following accessories : (i) incomming : MCB 4P,63 Amps-1No Out going: MCB 1P ,6 Amps/10A-12Nos with internal busbar & wiring up to terminal Make :- Sudhir or equivalent in shyam
M&L in repair of FLP/WP Lighting distribution panel board size (480x480x250 mm)encloser single pole & neutral 240 volts TPN 8way complete with appropriate size bus bar and neutral link suitable for class 1 Zone 1 & Ex IIC suitable for & including following accessories : (i) incomming : MCCB 4P,63 Amps-1No Out going: MCB 1P ,6 Amps/10/16 A-24Nos with internal busbar & wiring up to terminal Make :- Sudhir or equivalent in shyam
Supply and replacement of Flame proof MCB Socket & plug combined 250V 32 AMPS 4P+Earth complete all as specifeid and as directed
Supply and replacement of Flame proof MCB Socket & plug combined 250V 63 AMPS 4P+Earth complete all as specifeid and as directed
Supply and fixing in repairs Flame proof FH/199 FLP/WP flexible Metalic Conduit in SS304 with3/4" ET(M)X3/4" ET complete all as specifeied and asd directed.
Supply and fixing in repairs of Flame proof JB/104 FLP Junction box 3/4 way(to be used as incpection Elbow) complete as per existing size complete all as specified and as directed.
Supply and fixing of Flame proof CG/209- FLP/WP3/4" ET 17.50mm OD DC bras Nickel plated Cable Gland complete as per existing size complete all as specified and as directed.
Supply and fixing of Flame proof ACC/2019 FLP/WP Bends for conduit with3/4" ET entries complete all as specified and as directed.
M&L in repair to Sub main wiring using approved colour coding as per IS with two single core, PVC insulated, unsheathed FRLS multistranded copper conductor of size 4.00 sqmm (nominal area) 1100 volts grade and one single core, PVC insulated, unsheathed FRLS multistranded copper conductor of size 4.00 sqmm (nominal area) 1100 volts grade cable as earth wire including suitable size of heavey duty steel conduit drawn through steel conduit and connected to main board and making good disturbed surface after taking out old unserviceable sub main wiring and disposing from site complete all as specified and as directed. Note: Two runs each of 4.00 sqmm main cable and one RM of 4.00 sqmm cable as earth wire together alongwith conduit shall be considered as 1 running metre for payment purpose.
M&L in repair to Sub main wiring using approved colour coding as per IS with two single core, PVC insulated, unsheathed FRLS multistranded copper conductor of size 4.00 sqmm (nominal area) 1100 volts grade and one single core, PVC insulated, unsheathed FRLS multistranded copper conductor of size 4.00 sqmm (nominal area) 1100 volts grade cable as earth wire including suitable size of rigied existing steel conduit drawn through steel conduit and connected to main board and making good disturbed surface after taking out old unserviceable sub main wiring and disposing from site complete all as specified and as directed. Note: Two runs each of 4.00 sqmm main cable and one RM of 4.00 sqmm cable as earth wire together alongwith steel conduit shall be considered as 1 running metre for payment purpose.
All as per Sl item No 40 but of size 6.00 sqmm but heavey duty 20/25mm rigied existing conduit steel pipe (nominal area) and of size 6.00 sqmm (nominal area) 1100 volts grade cable as earth wire. Note: Two runs each of 6.00 sqmm main cable and one RM of 6.00 sqmm cable as earth wire together shall be considered as 1 running metre for payment purpose.
All as per Sl item No 41 but of size 10.00 sqmm but heavey duty 20/25mm conduit steel pipe (nominal area) and of size 10.00 sqmm (nominal area) 1100 volts grade cable as earth wire. Note: Two runs each of 10.00 sqmm main cable and one RM of 10.00 sqmm cable as earth wire together shall be considered as 1 running metre for payment purpose.
Supply and fix in repair Sheet metal enclosures for DBs SPN 12 way (when MCBs to be used) flush mounted including accessories therein and disposing off complete all as specified and directed. Make:Legrand/HAVELLS / Schneider
Supply and fix in repair Sheet metal enclosures for DBs SPN 2 way (when MCBs to be used) flush mounted including accessories therein and disposing off complete all as specified and directed. Make:Legrand/HAVELLS / Schneider
Supply and fix in repair Sheet metal enclosures for DBs SPN 8way (when MCBs to be used) flush mounted including accessories therein and disposing off complete all as specified and directed. Make:Legrand/HAVELLS / Schneider
Supply and fix in repair MCB SPN 40 to 63 Amps, 240 Volts, having breaking capacity 10 kA, 'C' characterstic including accessories therein & disposing from site complete all as specified and as directed.
Supply and fix in repair MCB SP 6-32 Amps, 240 Volts, having breaking capacity 10 kA, 'C' characterstic including accessories therein & disposing from site complete all as specified and as directed.
Supply and fix in repairs of MCCB 4P 100 Amps /415Volts ,having breaking capacity 25 ka with Complete accessories as per existing suitable size complete all as specified and as directed
Supply, laying, jointing and testing XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) with stranded aluminium condutor 1100 volts grade of size 10 Sqmm 4 core laid on walls/floors or in air with saddles and gutties complete all as specified and directed.Make :- Gloster / Havells / CCI.
Supply laying, jointing and testing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, of size 25 sqmm 4.0 core laid in trenches or passing through pips/ ducts complete all as specified and directed by Engineer in charge
Supply, laying, jointing and testing XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) with stranded aluminium condutor 1100 volts grade of size 16 Sqmm 4 core laid on walls/floors or in air with saddles and gutties including PVC conduitcomplete all as specified and directed.Make :- Gloster / Havells / CCI.
S&F inrepair of recess on wall ERW Conduit of size 20/25mm, ISI marked, heavy duty with all Conduit Accessories and Making Good Surfaces to match the Exiting Treat-ment (as per Site requirement) complete all as specified and as directed.
S&F in repair MS Nipple BSP 175 MM/3/4" as per existing firring /DBs complete all as specified and as directed.
Supply and fix in repair alluminium alloy/ cast iron Neoprene Gasket degree of protetion IP65 complete all as specified and as directed .
Supply and repair of MS Nipple conduit 175 MM/3/4" as per existing firring /DBs complete all as specified and as directed.
Supply and fixing of Electronic Hotter three phase Dynamically Balanced Siren including electric connection range of Hooter 1.5 KM Both side including fixing arrangement up to the height of 20 mtr complete all as specified and specified and as directed.
Excavation in trenches in any type of soil not exceeding 1.50 metre wide and not exceeding 1.50 metre in depth, for foundation, laying of pipes and LT cable and getting out, , complete all as specified and directed by Engineer-in-Charge
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick each in any type of soil , complete all as specified and directed by Engineer-in-Charge
Removing excavated spoil (soil) to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point , complete all as specified and directed by Engineer-in-Charge
Dry sand cushioning to under ground cable all as per clause 19.75 of SSR Part - I laid before and after laying of cable, complete all as specified and directed by engr-in-charge.
Sub class 'B' old size bricks well burnt as covering to under ground cables , laid dry, flat over the cables on sand cushioning with width equal to length of the brick as mechanical protection to cable complete all as specified and directed
Cutting of road (in hard/ dense soil ) for laying pipe line or repair to pipes of any size upto 0.5mtr. Depth and getting out incluiding forming bottom surface to required level and making good the road as per existing bitumens , concrete complete all as specified and directed.
S&F 80 mm dia GI tubing,light grade,for protection of cable passing across the road,under floor etc,complete all as specified and directed.
Servicing of Fire Alarm control panel complying with adderssable type single loop panel /double loop of capacity from 99 detectors & modules upto 200 detector with UV/IR Detection capacity including programing as per site requirement and complete all specified and directed by AGE E/M Note :- (i) Testing /commissioning and programming etc shall be deemed in to the quoted rates and nothing shall be extra payment to the contractor. ( ii) Penality shall be made after 48 Hrs to receipt the UNSV complaint of fire alarm panel @500Per day Penality shall be recovered from the contractor. (iii) Serviceability certificate shall be produced by the contractor along with signature of user and MES Rep.
Servicing of Fire Alarm control panel complying with Conventional type panel /double loop of capacity from 99 detectors & modules upto 100 detector with UV/IR Detection capacity including the programing as per site requirement complete all specified and directed by AGE E/M Note :- Note :- (i) Testing /commissioning and programming etc shall be deemed in to the quoted rates and nothing shall be extra payment to the contractor. ( ii) Penality shall be made after 48 Hrs to receipt the UNSV complaint of fire alarm panel @500Per day Penality shall be recovered from the contractor. (iii) Serviceability certificate shall be produced by the contractor along with signature of user and MES Rep.
S&F in repair of Addressable fire alarm panel as per existing size the following technical specifications Honewell / Morly ZX DX Series including programing and connected accessories complete all as specifeied and directed by Enginer in charge . (a) Oprating voltage : Between 15-30 volts DC peak (b) Max Stand by current : less than 1mA (c) Alarm LED current : max 1 mA (d) Operating Temp :- 100 C to +550 C (e) humidity : 0 to 95% RH (f) Wiring : 2 core (g) Protective transparent flip cover to prevent accidental activation (h) Electonic Addressing (j) Blinking LED for visual supervision (k) No frangible glass (l) Stable Communication with noise immunity (m) Automatic device Mapping. (n) Alarm flag for fast alarm reporting.
S&F in repair of conventional fire alarm panel the following technical specifications and all specified and directed Engr-in-Charge. (a) Oprating voltage : Between 15-30 volts DC peak (b) Max Stand by current : less than 1mA (c) Alarm LED current : max 1 mA (d) Operating Temp :- 100 C to +550 C (e) humidity : 0 to 95% RH (f) Wiring : 2 core (g) Protective transparent flip cover to prevent accidental activation (h) Electonic Addressing (j) Blinking LED for visual supervision (k) No frangible glass (l) Stable Communication with noise immunity (m) Automatic device Mapping. (n) Alarm flag for fast alarm reporting.
Supply and replacement of Smoke Detectors Complying with and type certified to EN - 45 smoke detector Photoelectric /Optical with base with self built intelligence as per IS: 11360 complete all as specifeid and as directed.
Supply and replacement of Mother board (Addrassable type) Complying with and type certified to NFS-2640 Notifier/Honyweloptical with base with self built intelligence as per IS: 11360 for panel 1 loop complete all as specifeid and as directed.
Supply and replacement of Mother board (Addrassable type) Complying with and type certified to NFS-2640 Notifier/Honyweloptical with base with self built intelligence as per IS: 11360 for panel 2 loop complete all as specifeid and as directed.
Supply and replacement of Mother board (Conventional type) Complying with and type certified to EN - 45 smoke detector Photoelectric /Optical with base with self built intelligence as per IS: 11360 complete all as specifeid and as directed.
Supply and replacement of power supply SMPS ( (Addrassable type) panel Complying with and type certified to complete all as specifeid and as directed.
Supply and replacement of Hooter Conventional/addressable type Complying with and type certified to EN - 45 smoke detector Photoelectric /Optical with base with self built intelligence as per IS: 11360 complete all as specifeid and as directed.
Supply and replacement of manual call point Complying with and type certified to EN - 45 Addressable type smoke detector Photoelectric /Optical with base with self built intelligence as per IS: 11360 complete all as specifeid and as directed.
Servicing and cleaning of Smoke Detectors Complying with and type certified to EN - 45 Addressable type smoke detector Photoelectric /Optical with base with self built intelligence as per IS: 11360 as per existing and arrangement of ladder of suitable building height complete all as specifeid and as directed.
Supply, laying & testing PVC insulated, PVC sheathed FRLS electric control cables (Heavy duty) with stranded copper fire serval cable conductor of size 1.5 sq mm ,2 core, 1100 Volts grade including taking down complete all specified and directed Engr-in-Charge. (Make: KEI/ Finolex/ RR cables/ Polycab/Havells)
Supply and repair of Battery sealed accied as per existing size suitable for control panel 24 V DC (2 Nos of 12V, 7 SMF batteries )complete all as specified and as directed.
Supply and fix in repair of Integral LED aviation light luminaire in yellow die-cast aluminium alloy housing with red coloured polycarbonate dome of including necessary electric connection with suitable size of PVC copper 2.5 sqmm with earth wire cable and suitable size GI bricket as per manufacture's requirement and blast pen building complete all as specified and as directed by Engineer-in-Charge.Cat part No BGAV 302 LED of Make Bajaj or equivalent C&S/CG/Philips
MCB TPN 40 to 100 Amps, 240 Volts, having breaking capacity 10 kA, 'C' characterstic including accessories therein & disposing from site complete all as specified and as directed.
Supply and repair of Remote response indicators Addressable /conventional type including unservisble spare parts and all specified and directed Engr-in-Charge.
KARAN TRADERS
shivom builders
LUXMI ELECTRONIC WORKS
JANDIAL ENTERPRISES
DAVINDER SINGH
ASIA BUILDER
ANIKET TRADERS
JCC ENGINEERS PRIVATE LIMITED
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .