Loading…
Loading…
Tender Value
₹1.0 Cr
EMD Value
₹2.1 L
Closing Date
18 Jun 2026, 3:30 pm
Supply, installation, testing and commissioning of New 11KV/415V Sub Station Near Worker Club' in Rail Coach Factory, Hussainpur (Kapurthala).
RCF-EL-TS-ET-151-2025-26
RCF-EL-TS-ET-151-2025-26
Open
12 Months
Kapurthala, Punjab
₹0
₹2.1 L
22 May 2026
22 May 2026
4 Jun 2026
Worker Club' in Rail Coach Factory, Hussainpur (Kapurthala).
Supply, installation, testing and commissioning of New 11KV/415V Sub Station Near Worker Club' in
S No. Item Description of Item Unit Qty Rate Amount
RCF HQ-ELECTRICAL/RCF
1 01 MRS Panels: Supplying, Installing VCB panels Set 1.00 1033723.00 1033723.00
connecting, testing and commissioning of 11
KV , 630 Amp HT VCB Board, VCB compatible
to SCADA, consisting of 02 Nos manual
operated VCB 630 Amp along with one No. NO
Load Isolator with double bus bar
arrangement , CT 400/5+5A CLASS: 1, 5P10,
30 VA for protection & 15 VA for metering
(PSPCL and DG Supply ) with four Nos.
Aluminium bus bar for each phase and other
associated equipments like master relays etc
complete as per specifications and
explanatory notes. * Set: One set consist of
02 Nos. (Main+ DG Supply) VCB's, One No.
NO Load Isolator. Note: Final Commissioning
shall be carried out in the presence of
authorized Technical Representative of 11kv
OEM of VCB and same shall be arranged by
2 02 Sub Station Item: Supplying, Installing VCB Set 1.00 2240385.00 2240385.00
panels, connecting, testing and
commissioning of 11 kV , 630 Amp, 26.3kA
VCB compatible to SCADA without Earthing
switch with PT and CT 400/5+5A CLASS: 1,
5P10, 30 VA for protection & 15 VA for
metering consisting of 02 Nos. Incomer VCB'S
(main & ring main ), 02 Nos outgoing manual
operated 11kV, 630 Amp , 26.3 kA without
earthing switch without PT , One No. Bus
Coupler (VCB 630 Amp and one No. bus
raising panel with earthing trucks (02 Nos) ,
all steal totally enclosed fully interlocked
indoor industrial pattern, metal clad with
associated panel equipments, master relay
etc to be coupled with 11KV, 3 Phase, 3 wire,
50 Hz to be installed at Sub Station complete
as per specs.IEC 62271 and explanatory
notes. *Set: one set consist of 02 Nos of
VCB's(Incomer & Ring Main)+02 Nos outgoing
VCB panels+01 No. Bus coupler+01 No. Bus
raising panel+02 Nos. Earthing trucks.
connecting(After shifting old existing panels),
testing and commissioning of 11 kV , 630
Amp, 26.3kA VCB compatible to SCADA
without Earthing switch with PT and CT
protection & 15 VA for metering manual
operated 11kV, 630 Amp , 26.3 kA without
earthing switch without P T for RING Main at
sub station No.10, all steal totally enclosed
fully interlocked indoor industrial pattern,
metal clad with associated panel equipment's,
master relay etc. to be coupled with 11KV, 3
Phase, 3 wire, 50 Hz to be installed at Sub
Station No.10 complete as per specs. IEC
62271 and explanatory Notes.
4 04 Copper control cable: Supplying and laying RM 100.00 896.00 89600.00
1.1KV grade PVC insulated and PVC sheathed
16 core x 2.5 sq mm copper conductor
armoured cable including both end Cable
Termination with single compression brass
glands as per explanatory Notes.
RCF HQ-ELECTRICAL/RCF
5 05 LT panel: Designing, supply, installation, Set 2.00 1280746.00 2561492.00
testing and commissioning of LT Cubicle
panel fabricated from 14 SWG CRCA sheet
powder coated with Grey paint of size
2400mm(Height) X 2600mm (Length) X
1250mm (depth) having One No. ACB four
pole of 1600 Amp rating draw in /Draw out
type (MDO) breaking capacity 50kA & One No.
four pole Bus Coupler LT breaker 2500 Amp
rating (Draw in /Draw out type (MDO)) with
breaking capacity 60kA. It also includes the
supply and fixing of tinned TPN copper bus
bar size (75mmx 10mm)x 2 Nos and earth
bus bar of size 50X5 mm. The panel shall
have Knock out holes for 400 sq mm cables.
Panel shall also consist of digital voltmeter,
Digital Ammeter, KWH meter, LED indicators
and required Nos. of CT's and in addition to
this panel shall also have 06 Nos of MCCB's
630 Amp rating with 40 mmx10mm tinned
copper bus bar TPN for MCCB connections in
two partitions of panel shall have 03 Nos of
MCCB's 630 Amp rating in each partition. The
panel will be manufactured in three
housings/parts i.e. MCCB chamber, bus bar
chamber and cable chamber as per existing
pattern. Note: One BUS coupler will be
fabricated separately for etc. use.
6 06 Supply, installation, testing, commissioning of Numbers 2.00 432000.00 864000.00
"Indoor Type Automatic Power Factor
Correction Relay Panel for improvement of
power factor) along with "300 KVAR rating
capacitors comprising of 6 (six) Nos. of 50
KVAR (2 x 25 KVAR) Units", as per
explanatory Notes.
7 07 Excavation of trench under soft soil 1500 mm RM 2600.00 323.00 839800.00
deep and 500 mm wide for laying of 02 Nos
HT Cables as per RCF Drawing
No.RCF/EL/HT/Cable laying/01. (Both the
cables will be protected separately with the
sand and bricks) as per explanatory notes.
150mm dia. under earth including Excavation
of trench under Pucca soil /road crossing
1500 mm deep and 600 mm wide for laying
of 02 Nos. HT Cables only one cable to be laid
in each Hume pipe * Running meter for
measurement shall be taken as running
length of executed length for laying of two
parallel lengths of RCC Hume pipe as per
explanatory notes.
means of Bokiee for laying 3X150/240 sq mm
HT cable, under the road/pucca without GI
pipe. Only one cable will be laid in one bokiee
hole for safe working of cables as per
explanatory notes.
grade (E), ISI Marked, XLPE Insulated,
Armoured, Stranded Compacted Circular
Conductors of 3X150/240 sq mm size as per
explanatory notes.
11 11 Providing & Making HT cable end termination Numbers 14.00 10186.00 142604.00
with heat shrinkable indoor joining kit for
underground XLPE cable of 3x150 Sq mm
,aluminum conductor HT cable 11 KV as per
explanatory notes.
RCF HQ-ELECTRICAL/RCF
12 12 Providing & Making HT cable end Straight Numbers 13.00 6791.00 88283.00
through joint with heat shrinkable outdoor
jointing kit for underground XLPE cable of size
3x150Sqmm ,aluminum conductor HT cable
11 KV as per explanatory notes.
13 13 Laying, Testing, Commissioning of LT 4X400 RM 1800.00 57.00 102600.00
sq mm XLPE cable Insulated, Armoured, cable
in the excavated, GI pipe, Hume pipe as per
explanatory notes.
14 14 Excavation of cable trench under soft soil 1.0 RM 1100.00 147.00 161700.00
meter deep 400mm wide for LT cable of size 4
x400 sq mm, providing sand 75 mm thick
layer around the cable & top protection with
class B bricks as per RCF drawing as per
explanatory notes.
15 15 Excavation of cable trench 1.0 meter deep RM 400.00 340.00 136000.00
400mm wide for LT cable of size 4x400 sq
mm under PUCCA soil as per explanatory
16 16 Excavation of cable trench 1.0 meter deep RM 100.00 391.00 39100.00
through bockie for laying of 01 Nos of 4x400
sq mmm LT cable under the road/ crossing
the road/pathway/pucca surface area etc. the
hole of bokiee shall be 1000mm below the top
surface of the road & providing & laying the
DWC hume pipe of required size to run
through power supply cable, supply of pipe is
under the scope of tenderer as per
explanatory notes.
17 17 Supply and making testing and Numbers 36.00 566.00 20376.00
commissioning of end terminations for LT
cable 4x400 sq mm with aluminum thimbles
and compression glands and crimping sockets
etc. as per explanatory notes.
18 18 Supply and making LT cable straight through Numbers 7.00 2953.00 20671.00
joints with heat shrinkable outdoor jointing kit
in the underground cable of size 4x400sq.mm
XLPE aluminum conductor cable of 1.1kv as
per explanatory notes.
19 19 Supply and erection of LT/HT cable route Numbers 60.00 922.00 55320.00
marker as per specification and CAST iron
plate of required dimensions and literature to
be engraved on the plate with UG HT/LT
cables and to be erected with 1000mm long
black painted MS angle of size 45mmx45mm
x 5mm with concrete foundation
300mmx300mm concrete as per explanatory
20 20 Supply and erection of fire buckets 04 Nos. 10 Set 4.00 1137.00 4548.00
leter capacity in each with MS stand duly
painted in red colour of each set as per
explanatory notes.
21 21 Providing and fixing of Co2 fire extinguisher Numbers 6.00 7350.00 44100.00
of 4.5kg each mounted on wall hook as per
IS:2878-1976 as per explanatory notes.
22 22 Providing and fixing of MV Danger Notice Numbers 2.00 245.00 490.00
plate as per explanatory notes.
23 23 Supply installation and erection PVC insulated RM 40.00 3063.00 122520.00
11KV mats as per explanatory notes.
commissioning of 24 Volt SCR Controlled
Automatic Float cum Boost charger suitable
for 230V +/- 10% input and output is suitable
to float /boost charge 24V-200 Amp hour SMF
VRLA batteries and supply installation of set
of batteries( batteries 12Nos./04 No. of 2 V/
6V, 200AH/120Ah respectively as per
explanatory notes .
RCF HQ-ELECTRICAL/RCF
25 25 Supply, erection, testing and commissioning Numbers 10.00 6874.00 68740.00
GI 600x600x6 mm thick GI plate earth
electrode including accessories and providing
masonry enclosure with cover plate having
locking arrangement watering pipe of 2.7
mtr. Long etc. with charcoal/ coke and salt ,
PVC Earth Pit Chamber of minimum 300 mm
dia x 450 mm depth, with heavy-duty cover
marked 'E', suitable for housing earth
electrode for 11 kV substation earthing
system. The pit shall be weatherproof, non-
corrosive, and made from UV-stabilized
material with load bearing 5 kN."as required
as per explanatory Notes.
26 26 Supply & laying of 50x6 mm GI strip under RM 10.00 923.00 9230.00
300mm deep by breaking the pucca area and
after laying the strip in trench, making the
area same as original in shape as per
explanatory Notes.
27 27 Supply & laying of 50x6 mm GI strip under RM 50.00 597.00 29850.00
soft soil in 300mm deep by excavation the
trench in soft soil and after laying the strip in
trench, making the area same as original as
per explanatory notes.
28 28 Supply and laying of 50x6 mm GI strip in RM 45.00 543.00 24435.00
trench with clamp of MS 14 SWG 20 mm
width after 1 meter apart in existing trench at
11 kV substation & connect with the assets as
per explanatory notes.
29 29 Supply, erection, testing and commissioning Numbers 5.00 2235.00 11175.00
of exhaust fan 450mm sweep as per
explanatory notes.
30 30 Supply, erection, testing and commissioning Numbers 24.00 331.00 7944.00
of LED tube light fittings of 18-20 watt as per
explanatory notes.
31 31 Supply, erection, testing and commissioning Numbers 6.00 544.00 3264.00
of LED street light fittings of 45watt on sub
station building with GI pipe as per
explanatory notes.
32 32 Fixing, testing and commissioning of ceiling Numbers 8.00 55.00 440.00
fan BLDC 1200 mm , 5 Star with BLDC Motor
as per explanatory notes.
33 33 Supply wiring, testing and commissioning of Numbers 50.00 587.00 29350.00
light/ceiling fan/exhaust fan/bracket light
point with 1.5 sq mm copper multistrand wire
as off wire 1.5 sq mm as earth wire along
with modular switch and modular plate etc.
as per explanatory notes.
34 34 Supply ,Wiring, testing and commissioning of Numbers 6.00 755.00 4530.00
6/16 amp socket plug point with 02 x4.0 Cu
wire & 2.5 Sq mm as Earth wire along with
modular switch, socket & Modular plate as
per explanatory notes.
35 35 Supply, erection, testing and commissioning Numbers 6.00 679.00 4074.00
of 6 amp. Modular socket with plug point 1.5
sq mm cu. Wire as phase, neutral and 1.5 sq.
mm as earth wire along with modular switch,
socket & Modular plate as per explanatory
36 36 Supply, erection, testing and commissioning Numbers 1.00 4326.00 4326.00
of 4 Way TPN/DB along with TPN/RCCB and
MCB'S as per explanatory notes.
37 37 Supply, erection, testing and commissioning Numbers 1.00 3071.00 3071.00
of TPN loop in loop out box made of SS304
steel size 350x250x100 mm of 1.6mm thick
sheet as per explanatory notes.
RCF HQ-ELECTRICAL/RCF
cable in excavated trench as per explanatory
39 39 supply making testing and commissioning of Numbers 2.00 99.00 198.00
end termination of 4x70/50 sq mm cable with
aluminum thimbles compression glands and
crimping sockets etc. as per explanatory
with BLDC Motor as per explanatory notes.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
Tender Documents
ATTACHMENT
drawing.pdf
ATTACHMENT
RCF-EL-TS-ET-151-2025-26.pdf.pdf
ATTACHMENT
Download all tender documents and submit your bid