| 1.00 | Repairs/replacement by Providing fitting of 600/630 ampere HRC fuse based main switch of reputed make in place of worn out existing one by way of dismantling the old worn out Main switch by disconnecting it from the input and output and the then installing the new Main switch and making the connections. The job further includes Repair of LT control Panel for 2×150Hp Motors installed at LIS KOT-II by disconnecting the incoming and outgoing cables of LT panel. P/F of new 400 Amp rated main incomer MCCB (1 No.) and 320/300 Amp MCCB (2 No.) for 2 No. 150 HP pump motor unit in place of damaged/burnt ones. These MCCBs should be provided with spreader terminals of requisite specifications along with P/f of new bus bars for making the circuit connections with these spreader terminals. The MCCBs should have a minimum of 36KA breaking capacity at 415volts-50 hertz. The job further involves provide and fitting of protection relays (for each 150 HP motor) having under & over voltage protection, phase failure/single phase protection and current/thermal overload protection as per motor characteristics by way of P/F of Shunt modules along with the aforementioned MCCBs of requisite specifications, CT coils, circuit wirings & other electronic components within the panel to give the desired aforementioned protections to each 150 HP (2 No.) motor pump units. The job also involves replacing the old damaged/ worn out circuit wiring with new circuit wirings. Servicing of panel by cleaning the contact with suitable chemicals to make it spark free. The job also includes replacement of damaged voltmeter, ammeter and 3 phase light indicators for the LT control panel and voltage stabilizer. Complete job includes rebate on account of old damaged/worm out parts/components, cost of material and labor charges for skilled and semi-skilled labor, hire charges of tools and tackles required at site for execution of job (Complete job).). | 1 | 01 job | 2,20,000 ₹2,20,000 | 2,10,000 ₹2,10,000 | 1,85,500 ₹1,85,500 Lowest |
| 2.00 | Extraction of damaged burnt and worn out 240 mm2 3.5 core cable and upgradation by way of Provide and fitting of 300 mm² single core XLPE insulated ST2 Type outer sheathed Aluminium cable (30 m approx.) of reputed make as per IS 7098 (Part 1) 1988 with upto date amendments, in place of damaged burnt/worn out existing cables laid between the main switch to voltage stabilizer and between voltage stabilizer to control panel by way of disconnecting LT supply from transformer side after removing removal of rusted thimbles along with cable from main switch output and then removing the other end from voltage stabilizer by cutting the rusted thimbles with cutter. Similarly removing the old wire from the voltage stabilizer to the control panel and replacing them with new above mentioned single core wire. The job further includes P/F of new thimbles on new single core Aluminium cable after preparing all the sixteen ends for connection from Voltage stabilizer to main switch and from Voltage stabilizer to LT control panel using appropriate tools and tackles and securing and tightening properly at suitable ends using cotton tape etc. testing on no load for checking the continuity of phases and the testing on full load. The job includes rebate on account of old damaged/worn out parts/components, cost of material, carriage, skilled and semi-skilled labour, hire charges of tools and tackles required at site for execution of job (Complete job). | 1 | 01 job | 75,000 ₹75,000 | 90,000 ₹90,000 | 67,000 ₹67,000 Lowest |
Tender Value
Refer Docs
EMD Value
₹7,500
Closing Date
19 Nov 2025, 12:00 pmClosed
Executive Engg. MICD Jammu
Executive Engineer MICD Jammu
Repairs to electro mechanical machinery along with other allied works at LIS Kot-II
2025_IFC_294945_1
MICD/J/39 dated 12/11/2025
Open Tender
Electrical and Maintenance Works
Item Rate
Akhnoor
Please refer Tender documents.
9 documents required · 9 mandatory
₹300
Convener, purchase committee, Directorate of ISM
₹7,500
26 Nov 2025
12 Nov 2025
19 Nov 2025
12 Nov 2025
19 Nov 2025
12 Nov 2025
Amount
Repairs/replacement by Providing fitting of 600/630 ampere HRC fuse based main switch of reputed make in place of worn out existing one by way of dismantling the old worn out Main switch by disconnecting it from the input and output and the then installing the new Main switch and making the connections. The job further includes Repair of LT control Panel for 2×150Hp Motors installed at LIS KOT-II by disconnecting the incoming and outgoing cables of LT panel. P/F of new 400 Amp rated main incomer MCCB (1 No.) and 320/300 Amp MCCB (2 No.) for 2 No. 150 HP pump motor unit in place of damaged/burnt ones. These MCCBs should be provided with spreader terminals of requisite specifications along with P/f of new bus bars for making the circuit connections with these spreader terminals. The MCCBs should have a minimum of 36KA breaking capacity at 415volts-50 hertz. The job further involves provide and fitting of protection relays (for each 150 HP motor) having under & over voltage protection, phase failure/single phase protection and current/thermal overload protection as per motor characteristics by way of P/F of Shunt modules along with the aforementioned MCCBs of requisite specifications, CT coils, circuit wirings & other electronic components within the panel to give the desired aforementioned protections to each 150 HP (2 No.) motor pump units. The job also involves replacing the old damaged/ worn out circuit wiring with new circuit wirings. Servicing of panel by cleaning the contact with suitable chemicals to make it spark free. The job also includes replacement of damaged voltmeter, ammeter and 3 phase light indicators for the LT control panel and voltage stabilizer. Complete job includes rebate on account of old damaged/worm out parts/components, cost of material and labor charges for skilled and semi-skilled labor, hire charges of tools and tackles required at site for execution of job (Complete job).).
Extraction of damaged burnt and worn out 240 mm2 3.5 core cable and upgradation by way of Provide and fitting of 300 mm² single core XLPE insulated ST2 Type outer sheathed Aluminium cable (30 m approx.) of reputed make as per IS 7098 (Part 1) 1988 with upto date amendments, in place of damaged burnt/worn out existing cables laid between the main switch to voltage stabilizer and between voltage stabilizer to control panel by way of disconnecting LT supply from transformer side after removing removal of rusted thimbles along with cable from main switch output and then removing the other end from voltage stabilizer by cutting the rusted thimbles with cutter. Similarly removing the old wire from the voltage stabilizer to the control panel and replacing them with new above mentioned single core wire. The job further includes P/F of new thimbles on new single core Aluminium cable after preparing all the sixteen ends for connection from Voltage stabilizer to main switch and from Voltage stabilizer to LT control panel using appropriate tools and tackles and securing and tightening properly at suitable ends using cotton tape etc. testing on no load for checking the continuity of phases and the testing on full load. The job includes rebate on account of old damaged/worn out parts/components, cost of material, carriage, skilled and semi-skilled labour, hire charges of tools and tackles required at site for execution of job (Complete job).
N B Engineering and Electric Works (BID ID -2644830)
GS ENGG WORKS (BID ID -2644675)
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.85 MB
BOQ_954395.xls
BOQ • 0.25 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .