| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹42.1 LAccepted-AOC GROUND FLOOR 281 1 D SHIVRAI NAGAR SAI MIRACLE ROAD RAHATNI PUNE 411 017 | PUNE | PUNE | MAHARASHTRA | 411017 | L1 | Accepted-AOC AWARDED | |
| 2 | L2₹43.5 L+₹33,056.10 (0.77%)Rejected-AOC FLAT NO 203 SEC 14 PLOT NO 142 SHIVSRUTI PARK APARTMENT E WING 1ST FLOOR MOSHI PRADHIKARAN TAL HAVELI DIST PUNE 412 105 | PUNE | MAHARASHTRA | 412105 | L2 | Rejected-AOC SECOND LOWEST BIDDER (L2) | |
| 3 | L3₹49.8 L+₹6.6 L (15.3%)Rejected-AOC NEAR SWAMI SAMARTH MANDIR GROUND FLOOR 28 1 1 D SHIVRAJ NAGAR SAI MIRACLE ROAD RAHATNI PUNE 411 017 | PUNE | MAHARASHTRA | 411017 | L3 | Rejected-AOC THIRD LOWEST BIDDER (L3) | |
| 4 | L4₹58.8 L+₹15.6 L (36.3%)Rejected-AOC | L4 | Rejected-AOC FOURTH LOWEST BIDDER (L4) | |
| 5 | Rejected-Technical | - | Rejected-Technical Requisite Documents not uploaded |
Tender Value
Refer Docs
EMD Value
₹90,000
Closing Date
7 Oct 2023, 6:00 pmClosed
GERD PASHAN PUNE
GERD PASHAN PUNE
REPAIR AND REPLACEMENT WORK TO EXTERNAL ELECTRIFICATION STREEL TUBULAR POLES LT HT CABLES PANELS SWITCH GEAR AND OTHER MISC E M WORK AT CHATURSHRUNGI VAIDUWADI PANCHWATI AND INSIDE ARDE UNDER GERD PASHAN
2023_MES_607114_3
GERD/TOKEN/24 OF 2023-2024
Open Tender
Civil Works
Item Rate
180 days
GERD PASHAN PUNE
AS PER TENDER
9 documents required · 9 mandatory
₹500
GERD PASHAN PUNE
₹90,000
7 Dec 2023
9 Sept 2023
10 Oct 2023
9 Sept 2023
7 Oct 2023
23 Sept 2023
9 Sept 2023 - 16 Sept 2023
Amount
On load filteration of transformer oil by continuous circulation of transformer oil through mechanical filters to achive the desired dielectric strength of 35 KV for one minute at 4 mm gap of sphere of oil testing machine complete all as specified and directed. Note: 1.Oil samples are to be collected from top and bottom of oil tank and test results to be recorded for each sample before and after filteration.
Supply and topping up transformer oil of dielectric strength 50 KV at 4 mm gap of sphere of oil testing machine in transformers of various capacity installed at various locations complete all as specified and directed. Make of Transformer oil: Savitha/ Power oil/ HP Notes : (a) New Transformer oil shall be filled in the transformer only after filteration and dehydration of existing transformer oil of the transformer. (b) Transformer oil shall be supplied in sealed barrel with test result and test certificate.
Supply and fix in repair breather assembly transparent plastic body with top and bottom portion pressed with metallic cover, filled with silica gel blue in colour and suitable for fixing on existing pipe of size 15/20/25 mm dia with suitable reducers/connectors etc as per site requirement /capacity of transformer complete all as specified and directed. Note : Rate quoted shall be deemed to include the cost of modification if any required to fix on existing MS Pipe.
Material and labour for straight through joint,heat shrinkable type for under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable XLPE 3 core 22 KV for the cable size 95 sqmm, 3 core including taking down existing unserviceable joint complete all as specified and directed by Engineer-in-charge.
All as per item No 4.00 here-in-before but for 120 to 185 sq mm cable 3 core
Material and labour for outdoor type end termination joint, heat shrinkable type for under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable XLPE, 3 core 22 KV, for the cable size 95 sqmm, 3 core including taking down existing unserviceable joint complete all as specified and directed by Engr-in-charge. Make : M seal/3M/ Yamuna
(b) All as per item No 6.00 here-in-before but 120 to 185 sq mm cable 3 core
Material and labour for indoor type end termination joint, heat shrinkable type for under ground cable including joint kits and labour complete for making joints suitable for aluminium conductor cable XLPE, 3 core 22 KV for the cable size 95 Sqmm, 3 core including taking down existing unserviceable joint complete all as specified and directed by Engr-in-charge. Make : M seal/3M/ Yamuna
(b) All as per item No 8.00 here-in-before but for 120 to 185 sq mm cable 3 core
Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre deep for taking out/laying of HT/ LT under ground cable and getting out in the following type of earth strata complete all as specified and as directed:- (a) Soft / loose soil
(b) Hard / dense soil
(c) Soft/ Disintegrated rock
(d) Hard Rock
Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25cm in soils complete all as specified and directed.
Removing surplus excavated soil to a distance not exceeding 50metre depositing where directed at a level not exceeding 1.5metre above the starting point complete all as specified and directed.
Material and labour for riddled earth filling in trenches to required width at bottom and top of cable cushioning including spreading leveling and consolidation complete all as specified and directed. Note : Punned thickness shall only be measured and paid.
Supply and lay in trenches un-reinforced precast concrete cable cover class LV, Type I, flat, size 250mm x150mm x 40mm for cable protection complete all as specified and directed by the Engr-in-Charge.
Supply and lay in trenches reinforced precast concrete cable cover class HVV type 2 ,flat size 300 x 180 x 40mm for cable protection complete all as specified and directed by the Engr-in-Charge.
Material and labour for straight through joint,heat shrinkable,type,for HT OH AB cable including joint kits and labour complete for making joints suitable for aluminium conductor cable XLPE, 3 core 95 to 185 sqmm,22 KV complete all as specified and directed by Engineer-in-charge. Make : M seal/3M/ Yamuna. Note: No of 03 run of HT AB Joint will be measered as one joint only. Rate for the same should quoted accordingly.
Repair to gang operated air brake switch device upto 400 Amps,22 KV capacity including greasing/oiling of all moving contacts,replacement of nut bolts,washers of suitable sizes,unserviceable spares and jumper connections in all phases for smooth functioning of the devices complete all as specified and directed by Engr-in-charge. Note : Unserviceable spares and jumper connections replaced will be measured and paid separately as "Supply only"
Supply only the following items against repairing of GOD any type :- a) Female contact /fix contact jaw for gang operated AB switch devices.
b) Male contact/moving contact blade of gang operated AB switch devices suitable for 22 KV
c) Tinned copper flexible jumper 200/200 Amps
d) Post top Polymer insulators of gang operated AB switch devices.
e) Middle post Polymer insulators of gang operated AB switch devices.
f) Bottom post Polymer insulators of gang operated AB switch devices.
g) MS jumper carrier.
h) Back connector plate.
i) GI pipe, light grade 25 mm dia made to shape for gang operating from ground.
Repairs to drop out fuse complete upto 400 Amps,22 KV capacity including replacement of worn out nut bolts,washers,of suitable size /unserviceable spares and jumper connections for smooth functioning of the devices complete all as specified and directed by Engr-in-charge. Note : Unserviceable spares and jumper connections replaced will be measured and paid seprately as "Supply only"
Supply only the following items (to be incorporated under Item No 30 above) a) Fix top contact/L contact for drop out fuse.
b) Fix lower contact for drop out fuse.
c) Post insulators of drop out fuse.
Material and labour for repair to ACSR conductor (Ferret) jumper connections of following lengths both ends secured with suitable aluminium lugs or one end with aluminium lugs and other end plain for binding with conductor encased with polythylene sleeve, RYB colours of suitable dia complete all as specified and directed for :- a) Not exceeding 0.75 metre length.
b) Exceeding 0.75 metre length but not exceeding 1.5 metre length.
c) Exceeding 1.5 metre length but not exceeding 2.5 metre length.
d) Exceeding 2.5 metre length but not exceeding 3.0 metre length.
Supply install testing and commissioning 22 KV outdoor type Polymer based gang operated air brake switch triple pole, suitable for verticle mounting complete with GI operating rod of suitable length for operating mechanism operated from ground level complete in both OFF and ON positions, for current rating upto 200 Amps,each pole consist of galvanised steel base HT insulators as per BSS/ISS non ferrous and spring loaded contacts, arcing horns of adequate section to brake magnetizing current of the transformers. All ferrous parts hot dipped galvanised and non ferrous parts suitably tinned to with stand weather complete all as specified and directed.
Supply and Fixed in repair Polymer based dropout fuse unit complete set suitable and including for 22 KV, HT outdoor and dropout type of capacity 200 Amps including jumper connections with copper flexible designed jumper and testing and commissioning complete all as specified and directed.
Supply and Fix Polymer Pin type insulator of 22 KV including necessary hardware and taking down existing unserviceable insulator complete all as specified and directed.
Supply and Fix Polymer disc type insulator, ball and socket type, white brown or green 2 in series for 22KV including necessary hardware and taking down existing unserviceable insulator complete all as specified and directed.
Supply and Fix lightining distribution surge arrestor, non linear type MCOV, 18 KV, 5 KA with all fittings bolts nuts and washers etc including taking down unserviceable surge arrestor complete all as specified and directed.
Material and labour for preperation of old painted steel surface of 6/4/2 pole structure HT street light HT steel tubular poles 11 metre long above GL/coping including cross arms,channels,Flat iron,Clamps in HT OH line by scraping with wire brush and applying one coat of aluminium paint including writing pole number with synthetic enamel paint complete all as specified and directed by Engr-in-charge for the following types:- a) HT 6 Pole structure 11 metre long including channels, nut, bolts and clamps complete all as specified and directed.
b) HT 3/4 Pole structure 11 metre long including channels, nut, bolts and clamps complete all as specified and directed.
c) HT 2 Pole structure 11 metre long including channels, nut, bolts and clamps complete all as specified and directed.
d) HT pole 11 metre long including channels, nut, bolts and clamps complete all as specified and directed.
Disconnecting the Pole mounted/platform mounted outdoor type transformer situated at various locations inside ARDE sub station 22/ 0.433 KV of any make and transporting to workshop for repairs/ rewinding, dismantling the transformer and accessories, removing insulating oil, taking out the core assembly, taking out the defective winding, cleaning the transformer internally and externally, rewinding burnt HT/LT coil with existing guage of copper super enamelled wire/ copper strip of existing size, providing new insulation, sleeves for outlet connections, opening the complete core assembly, reassembling, including dehydration and filtration of Transformer oil to achieve desired dielectric strength, carrying out routine test, re-installation and commissioning for the following capacity of Transformer complete all as specified and directed:- Note : The repair work also includes the routine tests i.e. IR value, High voltage test, Ratio test, Short circuit test & BD value of oil of the transformer to be carried out at worshop for following capacities of transformer :- a) 50 to 100 KVA.
b) 150 to 200 KVA.
c) 250 to 315 KVA.
d) 630 to 1000 KVA. Notes (i) Copper winding wire/strip will be measured and paid separately as supply only (ii) Insulating oil for topping up will be measured and paid separately. (iii) Transportation of transformer for repair and re-installation and other labour charges is deemed to include in quoted rates.
Supply only super enamelled copper winding wire of various gauges or existing specifications for repair and rewinding of transformers under item No. 47 to 50 primary and secondry coils including necessary class of insulation complete all as specified and directed. Make : ISI marked as approved by GE/Engr-in-charge.
Supply only DPC copper strip of various gauges or existing specifications for repair and rewinding of transformers under item No. 47 to 50 primary and secondry coils including necessary class of insulation complete all as specified and directed. Make : ISI marked as approved by GE/Engr-in-charge.
Material and labour for carrying out Lab test for acidity of Transformer oil for various Transformers and submitting test report on the format complete all as specified and directed.
Disconnecting the transformer outdoor type from HT/ LT system and opening carefully by draining out transformer oil upto HT/LT boxes for rectifying the leakage by replacing the unserviceable spare parts of capacity 50 to 750 KVA transformer, refilling the transformer oil and complete assembling after repairs including testing for any oil leakages and connecting the HT/LT system after the leakages have been rectified and tested on available electric load complete all as specified and directed. Note : Defective parts replaced will be measured and paid separately as "Supply only" under respective items here in after.
(a) Supply only LT bushings with brass studs of existing specification.
(b) Supply only top cover gasket set.
(c) Supply only radiator flanged gasket 6 mm thick.
(d) Supply only oil level indicator gasket set.
(e) Supply only HT bushing with stud 22 KV of existing specification.
Supply and Fixed in repair explosion vent diaphragm of suitable size to match with the existing complete all as specified and directed.
Material and labour for preparation of old painted surfaces of transformer, removing rusted scale/oil & painting of transformer with one coat of synthetic enamel paint of approved make duly Marking/ Writing MES/SM No. complete all as specified and directed by Engr-in-charge for following capacity :- (a) 50 to 100 KVA capacity of transformer.
(b) 160 to 250 KVA capacity of transformer.
(c) 630 to 1000 KVA capacity of transformer.
Material and labour for lifting of serviceable transformer of capacity 100 KVA to 500 KVA, 22/ 0.433 KV rated voltage, from one place to other by crane and transporting to other place within 02 Km radius including placing on plinth/pole mounting and connecting up all HT/LT connections, testing and energising the transformer complete all as specified and directed by Engr-in-charge.
Material and labour for lifting of serviceable DG Set of capacity 75 KVA to 250 KVA , 0.433 KV rated voltage, from one place to other by crane and transporting to other place within 02 Km radius including placing on plinth and connecting up all LT connections, testing complete all as specified and directed by Engr-in-charge.
Material and labour for disconnecting, opening, draw out RMU/ VCB trolley complete from its position after isolating safely from contacts of breakers for inspection, checking and re installing testing commissioning of same after carryout following repair work and replacement of unserviceable spares complete all as directed and specified by OEM. (i) Checking of Draw out mechanism/arrangement of VCB (ii)Inspection of isolating Contacts, and decarbonising the male /female contacts, jaws complete and replacement of worn out contacts . (iii) Checking of alignment with spout and setting of contact gaps. (iv) Replacement of worn out/defective minor spares parts, lubrication of moving parts of the truck by moly grease. (v) Checking/setting of master control relay, earth fault realy and overload realy. (vi) Replacement of burnt out spring charge motor, (vii) Replacement of Closing Coil 30V DC, (viii) Replacement of tripping Coil 30V DC. (ix) Replacement of top spout with Busbar. (x) Replacement of Bottom spout with Busbar. (xi) Replacement of power pack. (xii) Also checking ON/OFF/TRIP indication and make it serviceable by necessary checking/repair/replacement of control wiring. Replacement of Push button for open and Close, micro switches, indication lamps. (xiii) Decarburizing and reinsulation of complete busbar track system condition in all respect. (xiv) Misc works deemed essential to make VCB in perfectly working order. Note : Major spare parts shall be measured and paid separately under respective items here in after, as supply only however cost of minor spares fixing charge as of spares shall be deemed to be included in rate quoted.
Supply only following spare parts suitable for 30 VDC/ 110VAC to be incorporated under item No 66 above : a) Spring charge motor single phase 110/220 volts
b) Closing Coil 30V DC
c) Tripping Coil 30V DC
d) Top spout with Busbar 22 KV.
e) Bottom spout with Busbar 22KV.
f) Finger contact
g) Push button for open and Close.
h) Micro switches
j) Indication lamps.
Supply and fix in repairs Current Transformer - 01 No dual ratio of rating 1000/500/100/50A, 22 KV pressure epoxy cast resin complete duly intalled, commissioned, connected and tested at site complete all as specified and directed.
Supply and fix in repairs Potential Transformer ( PT) - 01 No ratio 22000/√3 volts/110/√3 volts, VA class for PT 50/0.2, Insulation level 24/50/125 KVP specially designed all as per MSEDCL recommendations and approval complete. Notes for item Nos 78 above :- The contractor's quoted rates Sl No 78 shall be deemed to include for the followinig provisions also. Nothing extra shall be paid on this account. (i) The work shall be carried out under combined supervision of MES and MSEDCL and Accepting Officer. (ii) It is the responsibility of the contractor to get approval of repair work from MSEDCL. (iii) The contractor should co ordinate the work with MSEDCL authorities for testing of metering unit (KIOSK) for repair work (iv) CT ratio of metering unit should be as per the requirement of MSEDCL at the time of commissioning of the installation. (vi) Testing metering unit and TOD meter shall be as directed by MSEDCL Officer. (v) Rate quoted is inclusive of Transportation from manufacturers workshop to work site, Testing charges of MSEDCL etc.
Material and labour for checking of resistance of earthing by disconnecting all electrical connection safely complete all as specifed and directed. Note: (i) Contractor will deploy necessary equipment and skilled person at site & no extra payment will be paid on this account. (ii) Contrctor shall submit earth test report to the Engineer-in-charge.
Material and labour for Fault Finding of defective, short circuit unserviceable under Ground 1.1KV LT cable with mobile fault finding instrument and accessories, locating fault or place of short circuit for jointing and defect rectification complete all as specified and directed. Note : The quoted rate deemed to include for executing the items at any time round the clock.
Material and labour for Fault Finding of defective, short circuit unserviceable under Ground 22 KV HT cable with mobile fault finding instrument and accessories, locating fault or place of short circuit for jointing and defect rectification complete all as specified and directed. Note : The quoted rate deemed to include for executing the items at any time round the clock.
Material and labour for primary and secondry injection testing of existing CT's set of three any type any capacity installed in VCB's 22 KV located at different sites and providing authentic test results complete all as specified and directed.
Dismantling cross arms / MS channel from HT pole including clamps, nuts, bolts & washers complete all as specified and directed.
Supply, installation, commissioning and testing numerical digital over current and earth fault relay with High set & RS -485 port including suitable rating of CT, IDMT & definite time characteristics, last 30 trip data recording with date and time and password protection operated on 30 Volts DC/240 volts AC of any make installed in VCB panel for protection against short circuit and earth fault, testing, commissioning and submitting test report on proper format including taking out old unserveciable one complete all as specified and as directed. Make : L&T Cat No MC61 CNX4000 or techno commercial equivalent features in Crompton Grieves, Siemens, schnieder.
Supply and fixing in repair HT Right angle boot 22 KV rating on HT side (set of 3) of existing transformers for jointing HT cable complete all as specified and as directed.
Supply and fix power connector accessories made out of aluminium alloy according to IS:617 : 1975 and conforms to IS: 5561 : 1970 galvanic corrosion free heavy duty working pressure 22 KV , enough to carry electrical load and to withstand the mechanical forces imposed during installation as well as service condition and the arrangement of nuts, bolt & washers so that the pressure is uniformly distributed over the whole contact surface area complete all as specified and as directed for following type of clamps:- a) PG clamps suitable to connect conductor to conductor Make : Jaipuria Brothers or techno commerical equivalent.
b) Pad connector suitable to pin insulators and aluminium bus bar
c) T connector suitable to connect aluminium bus bar to conductor
d) Expansion type connector for multiple connection
Material and labour for Earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 metre deep below normal ground level) with the top edges of plate not less than 1.5 metre below normal ground level connected to GI earth strip 32 mm x 6mm by means of GI nuts, bolts check nuts and washers earth lead protected by 40mm dia GI pipe light grade and connected to main distribution board/earthing test point all as shown in electrical plate No 3 of SSR part 1 and all as specified including testing on completion. Notes : The unit rate also including for excavation, earth work in any type of strata, plain cement concrete 1:3:6 , Type C1 using 20mm graded stone aggregate pit, 40mm thick RCC 1:2:4, type B1 using 20mm graded stone aggregate as in cover slab reinforced with 8mm dia TMT bars @150mm C/C both ways, GI funnel with GI watering pipe 20mm dia medium grade, wire mesh, protection pipe 40mm dia GI pipe light gde for earth lead upto 7.50metre long salt, charcoal complete all as specified and directed.
Material and labour for Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 metre deep below normal ground level) with the top edges of plate not less than 1.5 metre below normal ground level connected to GI wire 4.0 mm dia by means of GI nuts, bolts check nuts and washers earth lead protected by 15 mm dia GI pipe light grade and connected to main distribution board/earthing test point all as shown in electrical plate No 3 of SSR part 1 and all as specified including testing on completion. Notes : The unit rate also including for excavation, earth work in any type of strata, plain cement concrete 1:3:6, Type C1 using 20mm graded stone aggregate pit, 40 mm thick RCC 1:2:4, type B1 using 20 mm graded stone aggregate as in cover slab reinforced with 8 mm dia TMT bars @150 mm C/C both ways ,GI funnel with GI watering pipe 20 mm dia med grade ,wire mesh, protection pipe 40 mm dia GI pipe light grade for earth lead upto 7.50 m long salt, charcoal complete all as specified and directed.
Material and labour for Earthing complete with hot dip galvanized steel pipe in pipe electrode, outer pipe 76 mm dia medium grade and inner pipe 32 mm dia including testing 3 metre long and having 50x6 mm terminal on inner pipe to connect earthing strip with 14 mm dia holes for nut bolts. buried directly and vertically in ground with top edge at 30 cm below ground level after making bore hole of 100 mm dia and 3.3 metre deep using suitable mechanical drilling machine (for drilling near the specified bldg) connected with galvanized steel earthing lead of 32 x 6 mm strip with minimum two Nos of GI nut, bolts and connected to test point from earthing pit. The electrode pipes should be filled with 2x 25 Kg bags of carbon based earthing compound. The compound shall be highly conductive, hygroscopic, non magnetic, non corrosive in nature and have best moisture retaining qualities! with ph value between 7 to 9, connected to the earthing test point, fiber reinforced plastic pit not less than 300x300 mm with pit cover, including necessary returning, filling and removal of extra soil.MAKE:- U-Protect or techno commercial equivalent
Material and labour for 4mm dia GI Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated location for loop earthing etc complete all as specified and directed.
Material and labour for Earth contunity conductor or main earthing lead fixed to wall on recessed or burried in ground or drawn in conduit/pipe fixed to poles or any other indicated situation for loop earthing as required 25 x 4 mm size galvanised strip complete all as specified and directed.
Material and labour for GI strip of 32mmX6mm as in earth contunity conductor or main earthing lead fixed to wall on recessed or burried in ground or drawn in conduit/pipe fixed to poles or any other indicated location for loop earthing complete all as specified and directed.
Material and labour for 22 KV HT Hi-Pot Testing ( High potential, high voltage test) with high voltage AC/DC Instrument and find out fault/weak points in the over head lines system for rectifying defects and test report to be submitted complete all as specified and directed. Note : The quoted rate deemed to include for executing the items at any time round the clock.
Material and labour for 22 KV HT Hi-Pot Testing ( High potential, high voltage test) with high voltage AC/DC Instrument and find out fault/weak points in the HT structure 2/4/6 poles and its controlling system for rectifying defects and test report to be submitted. Note : The quoted rate deemed to include for executing the items at any time round the clock.
Material and labour for PCC 1:3:6 type C-2 using 40mm graded aggregate as in foundations of stays and poles etc complete including weathering, slightly rounded or chamfered angles and throating complete all as specified and directed.
Material and labour for PCC 1:3:6 type CI using 20mm graded stone aggregate as in coping weathering, slightly rounded or chamfered angles and throating including necessary formwork complete all as specified and directed.
Material and labour for PCC 1:2:4 type B-1 by using 20mm graded crushed stone aggregate as in making good road/ foot path/ hard standing/ drain/ bldg plinth protection complete all as specified and directed.
Material and labour for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size fixing to existing pole and inclusive of one primer coat, one under coat and one finishing coat of paint as indicated or directed by Engineer-in-Charge
Dismantling and taking down guarding wire and removing to store for safe custody or issue under Sch of credit complete all as specified & as directed.
Taking out steel tubular swaged poles HT/LT 11/9 metre long and removing to store for safe custody or issue under schedule of credit complete all as specified and directed.
Supply and fix Pin type, porcelain, vitreous white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100 mm height, 65mm dia suitable for 1100 volts grade including taking out existing unserviceable insulator complete all as specified and as directed.
Material and labour for Cradles, hexagonal / rectangular, fabricated with galvanised steel wire 3.15 or 4 mm including taking down unserviceable cradle complete all as specified and directed.
Supply and fix LT steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-31, 9 metre long complete all as specified and directed. Note : Earth work PCC shall be paid and measured separately.
Excavation in trenches not exc 1.5 metre wide and exc 1.5 metre and n exc 3.00 metre depth and getting out in hard/ dense soil complete all as specified and as directed.
Supply and fix HT steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-55, 11 metre long complete all as specified and directed. Note 1 : Earth work PCC shall be paid and measured separately.
Supply and fix in repair MCCB 4pole, 400 Amps, 36 KA, 415 volts, over load and short circuit protection, adjustable thermal -magnetic release type complete all as specified and directed.
Supply and fix in repair MCCB 4pole, 250 Amps, 36 KA, 415 volts, over load and short circuit protection, adjustable thermal -magnetic release type complete all as specified and directed.
Supply and fix in repair MCCB 4pole, 200 Amps, 25 KA, 415 volts, over load and short circuit protection, adjustable thermal -magnetic release type complete all as specified and directed.
Supply and fix in repair MCCB 4pole, 100 Amps, 25 KA, 415 volts, over load and short circuit protection, adjustable thermal -magnetic release type complete all as specified and directed.
Cutting the tree branches which touches the LT/HT OH lines upto 2.5 metre away from centre line of HT/LT OH line span not exceeding 60 metre between poles and deposting the tree branches/leaves at 30 metre distance away from site complete all as specified and directed. Note : Any number of tree branches cut in one span will be measured as one Job for payment purpose.
Supply, connect, test and commissioning of HT OH AB (air bunch) cable with aluminium conductor 3 core, 185 sqmm,22 KV complete all as specified and directed by Engineer-in-charge. Note : (i) Manpower, T&P and necessary store to hang HT OH AB cable between HT pole should included in the rate quoted. (ii) Any damage/ loss at site during work shall be borne by contractor.
Supplying, laying, jointing, testing and commissioning 22000 volts grade, 3 core 95 Sq mm HT XLPE (Earthed) shielded core type wrapped with galvanised steel strip armoured, PVC sheathed, heavy duty, electric cables, with multistranded aluminium conductor suitable for 22 KV 3 Phase AC, 50Hz, ISI marked, laid in trenches/passing through pipe/duct/ road crossing or fixed on poles, walls with suitable size clamps made out of mild steel flat iron including jointing material such as crimping type lugs, brass cable glands, heavy duty double compression type etc., including taking down unserviceable cable complete all as specified and directed. Note: Earthwork cushioning and cable covers will be measured and paid separately.
Supplying, laying, jointing, testing and commissioning 22000 volts grade, 3 core 185 Sq mm HT XLPE (Earthed) shielded core type wrapped with galvanised steel strip armoured, PVC sheathed, heavy duty, electric cables, with multistranded aluminium conductor suitable for 22 KV 3 Phase AC, 50Hz, ISI marked, laid in trenches/passing through pipe/duct/ road crossing or fixed on poles, walls with suitable size clamps made out of mild steel flat iron including jointing material such as crimping type lugs, brass cable glands, heavy duty double compression type etc., including taking down unserviceable cable complete all as specified and directed. Note 1: Earthwork, cushioning and cable covers will be measured and paid separately.
Supply and fix, connect, test and commissioning LT underground cable XLPE insulated, armoured heavy duty electric cable with multi stranded aluminium conductor heavy duty 1100 Volts grade in trenches/on wall/poles laid in ducts/inside protection pipe of the following sizes including cable glands, lugs and suitable size of MS saddle clips (where ever cable laid in ceilings/walls without cable duct) complete all as specified and directed for the following :- Notes : (i) Excavation, cushioning, cable cover will be measured and paid separately. (ii) Cost of jointing material e.g. lugs, thimbles, nut bolt and washers is deemed to included in the rate quoted. (a) 300 Sqmm 3.5 core
(b) 120 Sqmm 3.5 core
(b) 95 Sqmm 3.5 core
(c) 25 Sqmm 4 core
(d) 16 Sq mm 4 core
Material and labour for GI tube, , light grade with necessary fittings, complete, fixed to walls, pole ceiling or laid in trenches for cable protection complete all as specified and directed for the following size of pipe:- NOTE :- Excavation and earth work where required shall be measured separately. MS Clamps as required for fixing on wall / pole , etc are included in the rate quoted. (a) 150 mm dia Pipe
(b) 80 mm dia Pipe
(c) 40 mm dia Pipe
Material and labour for scraping of old paint from steel pole structure LT pole / street light tublar poles 8.5/9.0 metre long above GL/coping including cross arms, channels, Flat iron,Clamps in LT OH line with wire brush/ sand paper and applying one coat of aluminium paint including writing pole number complete all as specified and directed by Engr-in-charge.
Material and labour for finding fault of UG cable aluminium conductor armoured of any size, by checking and megering complete all as specified and directed. Notes : (i) Excavation/earth work/returning filling/relaying of brick and relaying soft soil for cushioning deemed to be included in the rate quoted. (ii) Cable for rectification will be measured and paid under relevant item. iii) Joint kit required will be measured and paid separately under relevant item. (iv) Before starting the LT/ HT wire, contractor shall ensure safety arrangement and proper shut down of feeders / mains to avoid any unwanted incidents.
Supply and fix in repair LED street light /road way luminaries 48 watts of make Havells Cat ENDURACITYLITEPLAT+SL48WLED757PASYBOPC or techno commercial equivalent in Bajaj, with pressure die cast housing heat sink with IP 66 protection, interchangeable electronic driver high efficiency longer life, protection against high surges , high /low voltage cutoff, open/short circuit protection and high power factor LEDs as light source including fitted on existing street light pole bracket complete all as specified and as directed.
Supply and fix in repair LED street light /road way luminaries 60 watts with pressure die cast housing heat sink with IP 66 protection, interchangeable electronic driver high efficiency longer life, protection against high surges , high /low voltage cutoff, open/short circuit protection and high power factor LEDs as light source including fitted on existing street light pole bracket complete all as specified and as directed. Make : Philips Cat Part BRP 062 LED 84CWSLCSIPSU SPD/ Havells Cat ENDURAPEARLNEOSL60WLED757PASYTOPCAST or techno commercial equivalent in Bajaj/ Crompton.
Supply and fix in repairs street light bracket suitable for 48/60W light made out of 25mm dia light grade GI pipe of 1.5 metre long bend to shape including applying one coat of aluminium paint over a coat of red oxide primer complete all as specified and as directed. NOTE:- Rate quoted is deemed include for MS clamp, nuts & bolts etc.
Supply and fix in repairs pole junction box sheet moulded compound (SMC) type with hinged door and locking arrangement of size 140x140x100mm internal comprising one , one No SP MCB single pole of capacity 6 Amps 240 volts and one No terminal for loop in & loop out suitable for single phase street light system including nuts and bolts and connecting up complete, MS clamp fabricated from 25x3mm MS flat iron complete all as specified and directed. Make : Sintex or techno commerical Equivalent
Supply and fix in repairs pole junction box sheet moulded compound (SMC) type with hinged door and locking arrangement of size 300 X 200 X 105 mm (internal ) comprising one , one No SP MCB single pole of capacity 6 Amps 240 volts and one No terminal for loop in & loop out suitable for three phase street light system including nuts and bolts and connecting up complete, MS clamp fabricated from 25x3mm MS flat iron complete all as specified and directed. Make : Sintex or techno commercial equivalent of any.
Material and labour for 3 single core PVC insulated unsheathed copper conductor cable multistranded 3 x 2.5 sq mm passing through in steel pole to street light luminaires complete all as specified and as directed. NOTE :- 3 run of wire shall be measured as one length
Material and labour for straight through joint for UG cable including joint kit for making joint suitable for the following size :- (a) 10 sq mm to 16 Sq mm, 2 core
(b) 16 sq mm to 25 Sq mm, 4 core
(c) 35 to 95 Sq mm, 3.5 core
(d) 120 to 150 Sq mm, 3.5 core
(e) 300 Sqmm, 3.5 core
Material and labour for disconnecting from existing main taking out from LT panel board for servicing & overhauling of ACB panel of any make 400 to 1000 Amp, 50Hz 415V AC including taking out existing mechanism complete with servicing of operating mechanism, testing of triping mechanism complete to make it funtioning smoothly and including replacement of unserviceable spares and fixing in its original postion with all connections and testing including welding work as requried for the Panel board complete all as specified and as directed. Note : Spare parts shall be measured and paid separately as Supply only.
Supply only Following spare parts suitable for LT ACB 400A-1000 A Capacity. (a) Main isolating contact (Male and Female) jaw type complete including fixing accessories
(b) Shunt Trip coil/ Closing coil 415 VAC suitable for 800 amps ACB
(c) Under voltage tripping divice (UVT) 415 volts
(d) Single phase CTS at rating 800/5A
Material and labour for cutting of roads/ plinth for removal/ laying to a width 0.25 metre, depth 0.25 metre of pipe complete all as specified and directed.
Material and labour for fire point fabricated with MS angles and MS Sheet on top suitable to hang and including 03 Nos bucket filled with sand, 03 Nos fire exinguishers for class ABC fire weight 6.75 Kg, 01 fire beater and hook complete with PCC foundation including painting the fire point with synthetic enamel paint of red shade complete all as specified and directed by Engr-in-Charge. Note : (i) Rate quoted is deemed to include for sand, painting etc complete and nothing extra shall be admissible.
Supply only DO fuse element end soldered standard tinned copper wire solder joint with ferrule and fire resistant ceramic tube suitable for 22 KV size 2.50 Amp to 25 Amp complete all as specified and as directed. Make : Jaipuria/ Biecco Lawrie
Supply only DO fuse element end soldered standard tinned copper wire solder joint with ferrule and fire resistant ceramic tube suitable for 22 KV size 40 Amp complete all as specified and as directed. Make : Jaipuria/ Biecco Lawrie
Supply only DO fuse element end soldered standard tinned copper wire solder joint with ferrule and fire resistant ceramic tube suitable for 22 KV size 75 Amp complete all as specified and as directed. Make : Jaipuria/ Biecco Lawrie
Supply only DO fuse element end soldered standard tinned copper wire solder joint with ferrule and fire resistant ceramic tube suitable for 22 KV size 100 Amp complete all as specified and as directed. Make : Jaipuria/ Biecco Lawrie
Supply and spreading stone aggregates/hard core of gauage not exc 40mm, deposited, spreading and leveling in layers not exc 15 cm thick including leveling and ramming to true surface complete all specified and as directed by Engr in Charge.
Supply and fix in repair SMPS model Dyna DY-31400EH FCBC input voltage 180-270V AC single phase, Frequency 47-53 Hz, Output Voltage 110V DC current capacity 36Amp (max) complete all as specified and as directed. Make: Schienider/lumin or techno commerical equivalent
Supply and fixing ACSR conductor of any size and type from overhead HT/LT poles including binding at site to insulator with suitable size of binding wire etc. Including taking down existing wornout old broken ACSR conductor or any size and type and length at any position from LT/HT pole
Meterial and labour for indoor type touch proof joint, heat shrinkable type including joint kits and labour complete for making joints suitable for aluminium conductor cable XLPE, 3 core 22 KV for the cable size 95 sqmm, 3 core complete including taking down unserviceable joint all as specified and directed by Engr-in-charge. Make M seal/ Denson/Capseal
Meterial and labour for indoor type touch proof joint, heat shrinkable type including joint kits and labour complete for making joints suitable for aluminium conductor cable XLPE, 3 core 22 KV for the cable size 185 sqmm, 3 core complete including taking down unserviceable joint all as specified and directed by Engr-in-charge. Make M seal/ Denson/Capseal
Meterial and labour for stay assembly with accessories and GI stay rod 16mm dia 1900 long, stay wire 7/4 mm stranded galvanized including mild steel stay plate 300mm X 300mm X 6mm and galvanized thimble, galvanized steel 14mm dia 400mm long stay bow and GI nuts, washers including loop type inculator vitreous porecelain white, brown or green big size with over all dimensions 90mm X 140mm clearance of hole 25.5mm complete all as specified and shown in electrical plate no 01 of SSR Part 1 complete all as specified and directed by Engg-in Charge. Note :- Earthwork and concrete will be measured and paid separately.
SKS Electricals
ASHA ASSOCIATES
MAYUR ELECTRIC SERVICES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .