Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.0 CrAdmitted-Finance 54 AKASH DEEP COLONY CHAKRATA ROAD DEHRADUN UK PIN 248001 | DEHRADUN | UTTARAKHAND | 248001 | ₹3.0 Cr | L1 | Admitted-Finance |
| 2 | L2₹3.0 CrAdmitted-Finance | ₹3.0 Cr | L2 | Admitted-Finance |
| 3 | L3₹3.1 CrAdmitted-Finance 38 49 D OLD IDGAH COLONY AGRA U P 282001 | AGRA | AGRA | UTTAR PRADESH | 282001 | ₹3.1 Cr | L3 | Admitted-Finance |
| 4 | L4₹3.3 CrAdmitted-Finance | ₹3.3 Cr | L4 | Admitted-Finance |
| 5 | L5₹3.3 CrAdmitted-Finance | ₹3.3 Cr | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | M/S SURAT SINGH AND SONS L1 | Raja enterprises L5 | GUPTA ENGINEERING WORKS L3 | R D Bansal L6 | M/S RAKESH TRADERS L2 | M/s Khialdas Constructions L4 | VEENUS ENGINEERS L7 |
|---|---|---|---|---|---|---|---|---|---|---|
| 1.00Note: (i) Please refer schedule 'A' notes before quoting the tender. (ii) Amount of Schedule of credit shall be deducted off line by the department. | ||||||||||
| 2.00 | Dismantling of cross-arms of M.S. channel or angle sections etc. complete and setting aside for re-use with in 50m complete all as specified and as directed. | 52.8 | Per qtl | 149 ₹7,867.20 | 500 ₹26,400 | 350 ₹18,480 | 150 ₹7,920 | 200 ₹10,560 | 270 ₹14,256 | 200 ₹10,560 |
| 3.00 | Dismantiling of insulator any type /size/ grade from over head electric line and setting aside removing from site complete all as specified and as directed. | 1,923 | EACH | 3 ₹5,769 | 5 ₹9,615 | 3 ₹5,769 | 2 ₹3,846 | 10 ₹19,230 | 9 ₹17,307 | 5 ₹9,615 |
| 4.00 | Dismantiling existing ACSR (of any size or type) from over head electric line carefully with out making any damage and removing from site complete all as specified and as directed. | 86.46 | Per qtl | 499 ₹43,143.54 | 500 ₹43,230 | 350 ₹30,261 | 200 ₹17,292 | 500 ₹43,230 | 180 ₹15,562.80 | 200 ₹17,292 |
| 5.00 | Dismantling of stay any type, any size all as specified and as directed. | 40 | Each | 199 ₹7,960 | 200 ₹8,000 | 50 ₹2,000 | 150 ₹6,000 | 250 ₹10,000 | 180 ₹7,200 | 200 ₹8,000 |
| 6.00 | Dismantling of UG cable with GI pipe any type, any size all as specified and as directed. | 814 | RM | 19 ₹15,466 | 50 ₹40,700 | 50 ₹40,700 | 10 ₹8,140 | 20 ₹16,280 | 9 ₹7,326 | 10 ₹8,140 |
| 7.00 | Dismantling/removing of unserviceable cradle guard/earth continuity conductor/cradle guard supporting wire of any size and setting aside all as directed at site. | 8 | Qtl | 99 ₹792 | 250 ₹2,000 | 400 ₹3,200 | 200 ₹1,600 | 500 ₹4,000 | 270 ₹2,160 | 200 ₹1,600 |
| 8.00 | Dismantling concrete poles/ struts, any size | 202 | Each | 199 ₹40,198 | 700 ₹1.4 L | 500 ₹1.0 L | 200 ₹40,400 | 200 ₹40,400 | 180 ₹36,360 | 300 ₹60,600 |
| 9.00 | Dismantling earthing any type, any size all as specified and as directed. | 20 | Each | 49 ₹980 | 100 ₹2,000 | 100 ₹2,000 | 150 ₹3,000 | 200 ₹4,000 | 90 ₹1,800 | 50 ₹1,000 |
| 10.00 | Removing and Shifting of existing LT panel from site and deposited at AGE E/M Dronachal yard of any size and type as directed | 7 | Each Job | 999 ₹6,993 | 2,000 ₹14,000 | 1,000 ₹7,000 | 500 ₹3,500 | 500 ₹3,500 | 450 ₹3,150 | 500 ₹3,500 |
Updated dates
Tender Value
₹3.6 Cr
EMD Value
₹4.4 L
Closing Date
7 Mar 2026, 6:00 pmClosed
Chief Engineer Bhopal Zone
HQ CHIEF ENGR BHOPAL ZONE, MES SI LINE BHOPAL 462001
UPGRADATION AND CONVERSION OF LT LINE TO UG CABLE WITH ALLIED INFRA UNDER GE DRONACHAL
2026_MES_748153_1
CEBZ/BPL/TOKEN/25 OF 2025-26
Open Tender
Electrical and Maintenance Works
450 days
Dronachal
AS PER NIT DOCUMENTS
5 documents required · 5 mandatory
₹2,000
GE Dronachal
₹4.4 L
18 Mar 2026
12 Jan 2026
9 Mar 2026
12 Jan 2026
7 Mar 2026
21 Feb 2026
Note: (i) Please refer schedule 'A' notes before quoting the tender. (ii) Amount of Schedule of credit shall be deducted off line by the department.
Dismantling of cross-arms of M.S. channel or angle sections etc. complete and setting aside for re-use with in 50m complete all as specified and as directed.
Dismantiling of insulator any type /size/ grade from over head electric line and setting aside removing from site complete all as specified and as directed.
Dismantiling existing ACSR (of any size or type) from over head electric line carefully with out making any damage and removing from site complete all as specified and as directed.
Dismantling of stay any type, any size all as specified and as directed.
Dismantling of UG cable with GI pipe any type, any size all as specified and as directed.
Dismantling/removing of unserviceable cradle guard/earth continuity conductor/cradle guard supporting wire of any size and setting aside all as directed at site.
Dismantling concrete poles/ struts, any size
Dismantling earthing any type, any size all as specified and as directed.
Removing and Shifting of existing LT panel from site and deposited at AGE E/M Dronachal yard of any size and type as directed
Excavation in trenches n. exc. 1.5 mtr in wide and n. exc. 1.5 mtr in depth for laying of underground cable and getting out in hard/dense soil complete all as specified and directed.
Excavation in trenches n. exc. 1.5 mtr in wide and n. exc. 1.5 mtr in depth for laying of underground cable and getting out in soft disintegrated rock all as specified and directed.
Excavation in trenches n. exc. 1.5 mtr in wide and n. exc. 1.5 mtr in depth for laying of underground cable and getting out in hard rock all as specified and directed.
Returning, filling in excavated soil in trenches including spreading, leveling, watering and well ramming in layers and matching with the existing ground n. exc. 25 cm thick complete all as specified and directed
Removing of excavted rock to a distance n. exc. 50 mtr and deposited where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed.
M&L local sand dry, filling in trenches around under ground cable complete all as specified and directed.
Supplying and laying un-reinforced precast concrete cable cover flat, size 250mm x 150mm x 40mm for protection of under ground cable complete all as specified and directed.
Supply and fixing, laying & testing of cable XLPE insulated screened PVC bedded, galvanized steel wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminum conductor of size 10 sqmm 2 core all as per IS , specified & directed.
All as per Item Ser No 18.00 here-in-before but of size 10 Sqmm 4 core all as per IS , specified & directed.
All as per Item Ser No 18.00 here-in-before but of size size 16 sqmm 4 core all as per IS , specified & directed.
All as per Item Ser No 18.00 here-in-before but of size size 25 sqmm 4 core all as per IS , specified & directed.
Supply and fixing, laying & testing of cable XLPE insulated screened PVC bedded, galvanized steel wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminum conductor of size 35 sqmm 3.5 core all as per IS , specified & directed.
All as per Item Ser No 22.00 here-in-before but of size size 50 sqmm 3.5 core all as per IS , specified & directed.
All as per Item Ser No 22.00 here-in-before but of size size 70 sqmm 3.5 core all as per IS , specified & directed.
All as per Item Ser No 22.00 here-in-before but of size size 95 sqmm 3.5 core all as per IS , specified & directed.
All as per Item Ser No 22.00 here-in-before but of size size 120 sqmm 3.5 core all as per IS , specified & directed.
All as per Item Ser No 22.00 here-in-before but of size size 150 sqmm 3.5 core all as per IS , specified & directed.
All as per Item Ser No 22.00 here-in-before but of size size 185 sqmm 3.5 core all as per IS , specified & directed.
All as per Item Ser No 22.00 here-in-before but of size size 240 sqmm 3.5 core all as per IS , specified & directed.
All as per Item Ser No 22.00 here-in-before but of size size 300 sqmm 3.5 core all as per IS , specified & directed.
All as item Ser No 31.00 here-in-before all as specified & directed. (7021-Cook house, Offr Mess, Adm Block, APS-Panel No-01 ) (a) MCCB TPN 100 Amps, Icu=Ics 25 KA adjustable type thermal magnetic based release at 415 Volts - 01 Nos (I/C) (b) MCCB TPN 63 Amps, 16 KA at 415 Volts - 04 Nos (O/G) (b) MCCB TPN 32 Amps, 16 KA at 415 Volts - 02 Nos (O/G) (c) MCB SPN 32 Amps, 10 KA at 230 Volts - 04 (O/G) (d) Phase indicating lamp RYB neon type (Set of three ) -01 Set (e) VAF+PF Meters , Accuracy class 0.5 - 01 No
All as item Ser No 31.00 here-in-before all as specified & directed. ( APS-Panel No-02) (a) MCCB TPN 100 Amps, Icu=Ics 25 KA adjustable type thermal magnetic based release at 415 Volts - 01 Nos (I/C) (b) MCCB TPN 63 Amps, 16 KA at 415 Volts - 04 Nos (O/G) (b) MCCB TPN 32 Amps, 16 KA at 415 Volts - 02 Nos (O/G) (c) MCB SPN 32 Amps, 10 KA at 230 Volts - 04 (O/G) (d) Phase indicating lamp RYB neon type (Set of three ) -01 Set (e) VAF+PF Meters , Accuracy class 0.5 - 01 No (f) Automatic Street Light Switch Three phase with Nature Switch-03 as the controlling unit for automatic switching of street lights based on LUX level of Natural light. The Sensor (Nature switch) along with suitable power contractor, MCB and Support Terminals should be enclosed in pole/wall mountable Enclosure made of Rust proof, Electric Shock proof, Termite proof and FR grade special moulding compound (Sintex make SMC Junction box) confirming to IP66. The contractor, MCB and circuit Wiring should suitable enough to take load 5 KW equally distributed over 3 phase (4 KW/Phase). The contractor rating 32 Amps (4-pole) and MCB(single pole) rating : 32 Amps(SP-03 Nos), complete- 01 Nos
All as item Ser No 31.00 here-in-before all as specified & directed. (7021- Panel MT,) (a) MCCB TPN 63 Amps, Icu=Ics 25 KA adjustable type thermal magnetic based release at 415 Volts - 01 Nos (I/C) (b) MCCB TPN 32 Amps, 16 KA at 415 Volts - 05 Nos (O/G) (c) MCB SPN 32 Amps, 10 KA at 230 Volts - 04 (O/G) (d) Phase indicating lamp RYB neon type (Set of three ) - 01 Set (e) VAF+PF Meters , Accuracy class 0.5 - 01 No. (f) Automatic Street Light Switch Three phase with Nature Switch-03 as the controlling unit for automatic switching of street lights based on LUX level of Natural light. The Sensor (Nature switch) along with suitable power contractor, MCB and Support Terminals should be enclosed in pole/wall mountable Enclosure made of Rust proof, Electric Shock proof, Termite proof and FR grade special moulding compound (Sintex make SMC Junction box) confirming to IP66. The contractor, MCB and circuit Wiring should suitable enough to take load 5 KW equally distributed over 3 phase (4 KW/Phase). The contractor rating 32 Amps (4-pole) and MCB(single pole) rating : 32 Amps(SP-03 Nos), complete- 01 Nos
All as item Ser No 31.00 here-in-before all as specified & directed. (21 CSR- Cook house, Panel KSP) (a) MCCB TPN 63 Amps, Icu=Ics 25 KA adjustable type thermal magnetic based release at 415 Volts - 01 Nos (I/C) (b) MCCB TPN 32 Amps, 16 KA at 415 Volts - 05 Nos (O/G) (c) MCB SPN 32 Amps, 10 KA at 230 Volts - 04 (O/G) (d) Phase indicating lamp RYB neon type (Set of three ) - 01 Set (e) VAF+PF Meters , Accuracy class 0.5 - 01 No.
All as item Ser No 31.00 here-in-before all as specified & directed. (7021-JCO Mess, P-135, 21 CSR-JCO Mess. ) (a) MCCB TPN 100 Amps, Icu=Ics 25 KA adjustable type thermal magnetic based release at 415 Volts - 01 Nos (I/C) (b) MCCB TPN 63 Amps, 16 KA at 415 Volts - 02 Nos (O/G) (b) MCCB TPN 32 Amps, 16 KA at 415 Volts - 02 Nos (O/G) (c) MCB SPN 32 Amps, 10 KA at 230 Volts - 04 (O/G) (d) Phase indicating lamp RYB neon type (Set of three ) -01 Set (e) VAF+PF Meters , Accuracy class 0.5 - 01 No.
All as item Ser No 31.00 here-in-before all as specified & directed. ( 21 CSR-Adm block) (a) MCCB TPN 100 Amps, Icu=Ics 25 KA adjustable type thermal magnetic based release at 415 Volts - 01 Nos (I/C) (b) MCCB TPN 63 Amps, 16 KA at 415 Volts - 02 Nos (O/G) (b) MCCB TPN 32 Amps, 16 KA at 415 Volts - 02 Nos (O/G) (c) MCB SPN 32 Amps, 10 KA at 230 Volts - 04 (O/G) (d) Phase indicating lamp RYB neon type (Set of three ) -01 Set (e) VAF+PF Meters , Accuracy class 0.5 - 01 No. (f) Automatic Street Light Switch Three phase with Nature Switch-03 as the controlling unit for automatic switching of street lights based on LUX level of Natural light. The Sensor (Nature switch) along with suitable power contractor, MCB and Support Terminals should be enclosed in pole/wall mountable Enclosure made of Rust proof, Electric Shock proof, Termite proof and FR grade special moulding compound (Sintex make SMC Junction box) confirming to IP66. The contractor, MCB and circuit Wiring should suitable enough to take load 5 KW equally distributed over 3 phase (4 KW/Phase). The contractor rating 32 Amps (4-pole) and MCB(single pole) rating : 32 Amps(SP-03 Nos), complete- 01 Nos
All as item Ser No 31.00 here-in-before all as specified & directed. (21 CSR-P-41, P-81, Def coy-P-156)) (a) MCCB TPN 200 Amps, Icu=Ics 25 KA adjustable type thermal magnetic based release at 415 Volts - 01 Nos (I/C) (b) MCCB TPN 63 Amps, 16 KA at 415 Volts - 05 Nos (O/G) (b) MCCB TPN 32 Amps, 16 KA at 415 Volts - 04 Nos (O/G) (c) MCB SPN 32 Amps, 10 KA at 230 Volts - 06 (O/G) (d) Phase indicating lamp RYB neon type (Set of three ) -01 Set (e) VAF+PF Meters , Accuracy class 0.5 - 01 No.
All as item Ser No 31.00 here-in-before all as specified & directed. (21 CSR Offr Mess) (a) MCCB TPN 100 Amps, Icu=Ics 25 KA adjustable type thermal magnetic based release at 415 Volts - 01 Nos (I/C) (b) MCCB TPN 63 Amps, 16 KA at 415 Volts - 02 Nos (O/G) (c) MCCB TPN 32 Amps, 16 KA at 415 Volts - 04 Nos (O/G) (d) MCB SPN 32 Amps, 10 KA at 230 Volts - 04 (O/G) (e) Phase indicating lamp RYB neon type (Set of three ) -01 Set (f) VAF+PF Meters , Accuracy class 0.5 - 01 No.
All as item Ser No 31.00 here-in-before all as specified & directed. (21 CSR-MT,P-50) (a) MCCB TPN 63 Amps, Icu=Ics 16 KA adjustable type thermal magnetic based release at 415 Volts - 01 Nos (I/C) (b) MCCB TPN 32 Amps, 16 KA at 415 Volts - 03 Nos (O/G) (c) MCB SPN 32 Amps, 10 KA at 230 Volts - 10 (O/G) (e) Phase indicating lamp RYB neon type (Set of three ) -01 Set (f) VAF+PF Meters , Accuracy class 0.5 - 01 No.
All as item Ser No 31.00 here-in-before all as specified & directed. (21 CSR-MT,P222) ) (a) MCCB TPN 63 Amps, Icu=Ics 16 KA adjustable type thermal magnetic based release at 415 Volts - 01 Nos (I/C) (b) MCCB TPN 32 Amps, 16 KA at 415 Volts - 03 Nos (O/G) (c) MCB SPN 32 Amps, 10 KA at 230 Volts - 10 (O/G) (e) Phase indicating lamp RYB neon type (Set of three ) -01 Set (f) VAF+PF Meters , Accuracy class 0.5 - 01 No. (g) Automatic Street Light Switch Three phase with Nature Switch-03 as the controlling unit for automatic switching of street lights based on LUX level of Natural light. The Sensor (Nature switch) along with suitable power contractor, MCB and Support Terminals should be enclosed in pole/wall mountable Enclosure made of Rust proof, Electric Shock proof, Termite proof and FR grade special moulding compound (Sintex make SMC Junction box) confirming to IP66. The contractor, MCB and circuit Wiring should suitable enough to take load 5 KW equally distributed over 3 phase (4 KW/Phase). The contractor rating 32 Amps (4-pole) and MCB(single pole) rating : 32 Amps(SP-03 Nos), complete- 01 Nos
All as item Ser No 31.00 here-in-before all as specified & directed. (Def Coy Main panel) (a) MCCB TPN 400 Amps, Icu=Ics 36 KA adjustable type thermal magnetic based release at 415 Volts - 01 Nos (I/C) (b) MCCB TPN 200 Amps, 25 KA at 415 Volts - 01 Nos (O/G) (c) MCCB TPN 160 Amps, 25 KA at 415 Volts - 01 Nos (O/G) (c) MCCB TPN 125 Amps, 25 KA at 415 Volts - 02 Nos (O/G) (c) MCCB TPN 63 Amps, 16 KA at 415 Volts - 03 Nos (O/G) (e) Phase indicating lamp RYB neon type (Set of three ) -01 Set (f) VAF+PF Meters , Accuracy class 0.5 - 01 No. (g) Automatic Street Light Switch Three phase with Nature Switch-03 as the controlling unit for automatic switching of street lights based on LUX level of Natural light. The Sensor (Nature switch) along with suitable power contractor, MCB and Support Terminals should be enclosed in pole/wall mountable Enclosure made of Rust proof, Electric Shock proof, Termite proof and FR grade special moulding compound (Sintex make SMC Junction box) confirming to IP66. The contractor, MCB and circuit Wiring should suitable enough to take load 5 KW equally distributed over 3 phase (4 KW/Phase). The contractor rating 32 Amps (4-pole) and MCB(single pole) rating : 32 Amps(SP-03 Nos), complete- 01 Nos
All as item Ser No 31.00 here-in-before all as specified & directed. (Def coy-P-151,) (a) MCCB TPN 160 Amps, Icu=Ics 25 KA adjustable type thermal magnetic based release at 415 Volts - 01 Nos (I/C) (b) MCCB TPN 63 Amps, 16 KA at 415 Volts - 04 Nos (O/G) (c) MCCB TPN 32 Amps, 16 KA at 415 Volts - 02 Nos (O/G) (d) MCB SPN 32 Amps, 10 KA at 230 Volts - 04 (O/G) (f) Phase indicating lamp RYB neon type (Set of three ) -01 Set (g) VAF+PF Meters , Accuracy class 0.5 - 01 No
All as item Ser No 31.00 here-in-before all as specified & directed. ( Provost unit) (a) MCCB TPN 125 Amps, Icu=Ics 25 KA adjustable type thermal magnetic based release at 415 Volts - 01 Nos (I/C) (b) MCCB TPN 63 Amps, 16 KA at 415 Volts - 04 Nos (O/G) (c) MCCB TPN 32 Amps, 16 KA at 415 Volts - 02 Nos (O/G) (d) MCB SPN 32 Amps, 10 KA at 230 Volts - 04 (O/G) (f) Phase indicating lamp RYB neon type (Set of three ) -01 Set (g) VAF+PF Meters , Accuracy class 0.5 - 01 No (g) Automatic Street Light Switch Three phase with Nature Switch-03 as the controlling unit for automatic switching of street lights based on LUX level of Natural light. The Sensor (Nature switch) along with suitable power contractor, MCB and Support Terminals should be enclosed in pole/wall mountable Enclosure made of Rust proof, Electric Shock proof, Termite proof and FR grade special moulding compound (Sintex make SMC Junction box) confirming to IP66. The contractor, MCB and circuit Wiring should suitable enough to take load 5 KW equally distributed over 3 phase (4 KW/Phase). The contractor rating 32 Amps (4-pole) and MCB(single pole) rating : 32 Amps(SP-03 Nos), complete- 01 Nos
All as item Ser No 31.00 here-in-before all as specified & directed. (Def coy--JCO mess, P-429) (a) MCCB TPN 100 Amps, Icu=Ics 25 KA adjustable type thermal magnetic based release at 415 Volts - 01 Nos (I/C) (b) MCCB TPN 63 Amps, 16 KA at 415 Volts - 03 Nos (O/G) (b) MCCB TPN 32 Amps, 16 KA at 415 Volts - 02 Nos (O/G) (c) MCB SPN 32 Amps, 10 KA at 230 Volts - 08 (O/G) (d) Phase indicating lamp RYB neon type (Set of three ) -01 Set (e) VAF+PF Meters , Accuracy class 0.5 - 01 No.
All as item Ser No 31.00 here-in-before all as specified & directed. PH-Main panel) (a) MCCB TPN 200 Amps, Icu=Ics 35 KA at adjustable type thermal magnetic based release 415 Volts - 01 Nos (I/C) (b) MCCB TPN 160 Amps, 25 KA at 415 Volts - 01 Nos (O/G) (c) MCB TPN 100 Amps, 25 KA at 415 Volts - 4 (O/G) (c) MCB TPN 63 Amps, 16 KA at 415 Volts - 2 (O/G) (e) Phase indicating lamp RYB neon type (Set of three ) -01 Set (f) VAF+PF Meters , Accuracy class 0.5 - 01 No. (g) Automatic Street Light Switch Three phase with Nature Switch-03 as the controlling unit for automatic switching of street lights based on LUX level of Natural light. The Sensor (Nature switch) along with suitable power contractor, MCB and Support Terminals should be enclosed in pole/wall mountable Enclosure made of Rust proof, Electric Shock proof, Termite proof and FR grade special moulding compound (Sintex make SMC Junction box) confirming to IP66. The contractor, MCB and circuit Wiring should suitable enough to take load 5 KW equally distributed over 3 phase (4 KW/Phase). The contractor rating 32 Amps (4-pole) and MCB(single pole) rating : 32 Amps(SP-03 Nos), complete- 01 Nos
All as item Ser No 31.00 here-in-before all as specified & directed. (Provost) (a) MCCB TPN 100 Amps, Icu=Ics 25 KA adjustable type thermal magnetic based release at 415 Volts - 01 Nos (I/C) (b) MCCB TPN 63 Amps, 16 KA at 415 Volts - 01 Nos (O/G) (d) MCB TPN 32 Amps, 16 KA at 415 Volts - 04 (O/G) (c) MCB SPN 32 Amps, 10 KA at 230 Volts - 12 (O/G) (e) Phase indicating lamp RYB neon type (Set of three ) -01 Set (f) VAF+PF Meters , Accuracy class 0.5 - 01 No
All as item Ser No 31.00 here-in-before all as specified & directed. (APS) (a) MCCB TPN 250 Amps, Icu=Ics 36 KA adjustable type thermal magnetic based release at 415 Volts - 01 Nos (I/C) (b) MCCB TPN 100 Amps, 25 KA at 415 Volts - 04 Nos (O/G) (c) MCB TPN 63 Amps, 16 KA at 415 Volts - 02 (O/G) (e) Phase indicating lamp RYB neon type (Set of three ) -01 Set (f) VAF+PF Meters , Accuracy class 0.5 - 01 No.
Supply and installation, testing & commissioning self supporting totally enclosed factory fabricated LT bus Each bar panel box made out of 3.15mm thick MS sheet with projected globe roof for rain water protection, dust and vermin proof hinged double shutter doors with neorprene rubber gasket epoxy powder coated including danger plate, earth strip, ventilation louvers, bottam detachable gland plate complete with suitable size zinc chromium plated nuts, bolts, and washers etc outdoor type cubicle panel board suitable for 3 Feeder phase 4 wire 415 volt 50 HZ and 40 mm x 40 mm x 6 mm angle iron frame, weather proof ventilated with locking arrangement incl of PCC pedestal, comprising the following & including taking down the existing Pillar panel board- (i) Aluminium bus- bar 200Amps,supported with suitable size Porcelain standlock with suitable size brass nut, bolts and washers with heat shrinkable colour coded PVC sleeving for 3 phase & neutral . - 01 Set (ii) Incoming- MCCB with microprocessor release ,4 pole, 63amps ,16 KA, 415 Volts, 50 Hz Adjustable - 01 No (ii) Outgoing- MCCB with microprocessor release ,4 pole, 32amps ,16 KA, 415 Volts, 50 Hz Adjustable - 02 No, (iii) MCB SPN 10 KA, 32Amps, 240 Volts- 04. (iii) Note- Spare Din rail to be proveded for additional MCBs. (Near P-170)
Supply and installation, testing & commissioning self supporting totally enclosed factory fabricated LT bus Each bar panel box made out of 3.15mm thick MS sheet with projected globe roof for rain water protection, dust and vermin proof hinged double shutter doors with neorprene rubber gasket epoxy powder coated including danger plate, earth strip, ventilation louvers, bottam detachable gland plate complete with suitable size zinc chromium plated nuts, bolts, and washers etc outdoor type cubicle panel board suitable for 3 Feeder phase 4 wire 415 volt 50 HZ and 40 mm x 40 mm x 6 mm angle iron frame, weather proof ventilated with locking arrangement incl of PCC pedestal, comprising the following & including taking down the existing Pillar panel board- (i) Aluminium bus- bar 400Amps,supported with suitable size Porcelain standlock with suitable size brass nut, bolts and washers with heat shrinkable colour coded PVC sleeving for 3 phase & neutral . - 01 Set (ii) MCCB with microprocessor release ,4 pole, 200amps ,36 KA, 415 Volts, 50 Hz Adjustable - 01 No .(iii) Note- Spare Din rail to be proveded for additional MCBs.( 12 TAC)
Supply and installation, testing & commissioning self supporting totally enclosed factory fabricated LT bus Each bar panel box made out of 3.15mm thick MS sheet with projected globe roof for rain water protection, dust and vermin proof hinged double shutter doors with neorprene rubber gasket epoxy powder coated including danger plate, earth strip, ventilation louvers, bottam detachable gland plate complete with suitable size zinc chromium plated nuts, bolts, and washers etc outdoor type cubicle panel board suitable for 3 Feeder phase 4 wire 415 volt 50 HZ and 40 mm x 40 mm x 6 mm angle iron frame, weather proof ventilated with locking arrangement incl of PCC pedestal, comprising the following & including taking down the existing Pillar panel board- (i) Aluminium bus- bar 400Amps,supported with suitable size Porcelain standlock with suitable size brass nut, bolts and washers with heat shrinkable colour coded PVC sleeving for 3 phase & neutral . - 01 Set (ii) MCCB with microprocessor release ,4 pole, 200amps ,36 KA, 415 Volts, 50 Hz Adjustable - 01 No .(iii) Note- Spare Din rail to be proveded for additional MCBs.( WKSP)
Supply and installation, testing & commissioning self supporting totally enclosed factory fabricated LT bus Each bar panel box made out of 3.15mm thick MS sheet with projected globe roof for rain water protection, dust and vermin proof hinged double shutter doors with neorprene rubber gasket epoxy powder coated including danger plate, earth strip, ventilation louvers, bottam detachable gland plate complete with suitable size zinc chromium plated nuts, bolts, and washers etc outdoor type cubicle panel board suitable for 3 Feeder phase 4 wire 415 volt 50 HZ and 40 mm x 40 mm x 6 mm angle iron frame, weather proof ventilated with locking arrangement incl of PCC pedestal, comprising the following & including taking down the existing Pillar panel board- (i) Aluminium bus- bar 400Amps,supported with suitable size Porcelain standlock with suitable size brass nut, bolts and washers with heat shrinkable colour coded PVC sleeving for 3 phase & neutral . - 01 Set (ii) MCCB with microprocessor release, 4 pole, 200amps, 36 KA, 415 Volts, 50 Hz Adjustable - 01 No . (ii) Outgoing- MCCB with microprocessor release, 4 pole, 32amps, 16 KA, 415 Volts, 50 Hz Adjustable - 02 No, (iii) Note- Spare Din rail to be proveded for additional MCBs. (21CSR Near CH)
Supply and installation, testing & commissioning self supporting totally enclosed factory fabricated LT bus Each bar panel box made out of 3.15mm thick MS sheet with projected globe roof for rain water protection, dust and vermin proof hinged double shutter doors with neorprene rubber gasket epoxy powder coated including danger plate, earth strip, ventilation louvers, bottam detachable gland plate complete with suitable size zinc chromium plated nuts, bolts, and washers etc outdoor type cubicle panel board suitable for 3 Feeder phase 4 wire 415 volt 50 HZ and 40 mm x 40 mm x 6 mm angle iron frame, weather proof ventilated with locking arrangement incl of PCC pedestal, comprising the following & including taking down the existing Pillar panel board- (i) Aluminium bus- bar 200Amps,supported with suitable size Porcelain standlock with suitable size brass nut, bolts and washers with heat shrinkable colour coded PVC sleeving for 3 phase & neutral . - 01 Set (ii) MCCB with microprocessor release ,4 pole, 100amps ,25 KA, 415 Volts, 50 Hz Adjustable - 01 No . (ii) Outgoing- MCB SPN/DP 32A ,240 Volts - 05 No, (iii) Note- Spare Din rail to be proveded for additional MCBs.( 21 CSR Near PT Gd)
Supply and installation, testing & commissioning self supporting totally enclosed factory fabricated LT bus Each bar panel box made out of 3.15mm thick MS sheet with projected globe roof for rain water protection, dust and vermin proof hinged double shutter doors with neorprene rubber gasket epoxy powder coated including danger plate, earth strip, ventilation louvers, bottam detachable gland plate complete with suitable size zinc chromium plated nuts, bolts, and washers etc outdoor type cubicle panel board suitable for 3 Feeder phase 4 wire 415 volt 50 HZ and 40 mm x 40 mm x 6 mm angle iron frame, weather proof ventilated with locking arrangement incl of PCC pedestal, comprising the following & including taking down the existing Pillar panel board- (i) Aluminium bus- bar 200Amps,supported with suitable size Porcelain standlock with suitable size brass nut, bolts and washers with heat shrinkable colour coded PVC sleeving for 3 phase & neutral . - 01 Set (ii) MCCB with microprocessor release ,4 pole, 63amps ,25 KA, 415 Volts, 50 Hz Adjustable - 01 No . (ii) Outgoing- MCCB with microprocessor release ,4 pole, 32amps ,16 KA, 415 Volts, 50 Hz Adjustable - 01 No (iii) MCB SPN/DP 32A ,240 Volts - 06 No, (iV) Note- Spare Din rail to be proveded for additional MCBs. (21 CSR MT)
Supply and installation, testing & commissioning self supporting totally enclosed factory fabricated LT bus Each bar panel box made out of 3.15mm thick MS sheet with projected globe roof for rain water protection, dust and vermin proof hinged double shutter doors with neorprene rubber gasket epoxy powder coated including danger plate, earth strip, ventilation louvers, bottam detachable gland plate complete with suitable size zinc chromium plated nuts, bolts, and washers etc outdoor type cubicle panel board suitable for 3 Feeder phase 4 wire 415 volt 50 HZ and 40 mm x 40 mm x 6 mm angle iron frame, weather proof ventilated with locking arrangement incl of PCC pedestal, comprising the following & including taking down the existing Pillar panel board- (i) Aluminium bus- bar 200Amps,supported with suitable size Porcelain standlock with suitable size brass nut, bolts and washers with heat shrinkable colour coded PVC sleeving for 3 phase & neutral . - 01 Set (ii) MCCB with microprocessor release ,4 pole, 63amps ,25 KA, 415 Volts, 50 Hz Adjustable - 01 No . (ii) Outgoing- MCCB with microprocessor release ,4 pole, 32amps ,16 KA, 415 Volts, 50 Hz Adjustable - 03 No (iii) MCB SPN/DP 32A ,240 Volts - 10 No, (iV) Note- Spare Din rail to be proveded for additional MCBs. (Def coy P-409)
M&L for earthing complete with using galvanized mild steel earth plate (electrode) 600 mmx 600 mmx 6.30 mm thick buried directly in ground, earth pit not less than 2.25 mtr deep below ground level with top edge of the earth plate not less than 1.50 m below ground level and earth plate surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all round the plate using 32X6 mm GI earth strip as earth lead moulded and riveted to earth plate at one end and connected to main equipment at switch/control board at another end, GI earth lead incased in and including 50 mm dia GI ‘light grade’ pipe from upper end of earth plate upto equipment with & including 20 mm dia bore GI pipe ‘light grade’ as water pipe from earth chamber to upper edge of the earth plate, GI funnel with wire mesh fixed on water pipe and provision of PCC 1:2:4 type B1(using 20 mm graded stone agg) as in pits chamber and RCC pit cover 50 mm thick of precast RCC 1:2:4 type B-1 (using 20 mm graded stone agg)duly reinforced with mild steel round bars 6 mm dia @ 150 mm c/c both ways with 10 mm dia mild steel bars as in lifting handles with and including necessary excavation & earth work including laying the GI pipe concealed in floor /wall all as per plate No. 3 of SSR Part I complete all as specified and directed and testing on completion..NOTE :- GI earth wire and protection pipe beyond 7.5 mtr will be measured and paid separately. (Note : 1. If the desired earth resistance is not found earthing shall be re-done by the Contractor at no extra cost paid by Dept.)
M&L earthing complete with galvanised steel earth plate electrode size 600X600X6mm thick burried directly in ground vertically to a depth not less than 2.25m deep below normal ground level with top edge of earth plate not less than 1.5m deep below normal ground level and connected to and including GI earth lead wire 4mm dia by means of bolts, nuts, check nuts & washers of galvanised iron and connected to test point all as shown in electrical plate No 3 of SSR part I-2009 and all as specified or indicated and testing on completion including excavation and earth work in any type of strata available at site, PCC (1:3:6) type C-1 earthing chamber, pre cast RCC slab 50 mm thick in cement concrete (1:2:4) type B-1 using 20 mm graded crushed stone aggregate reinforced with welded steel wire fabric (XPM) weight not less than 4 kg/sqm funnel with GI watering pipe of 20 mm bore medium grade, wire mesh and lugs, GI protection pipe of 15 mm bore light grade up to 7.5 metre long all as specified and directed. NOTE :- GI earth wire and protection pipe beyond 7.5 metre will be measured and paid separately.
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 100 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed.
Supply and fix of light grade Galvanised mild steel pipe 100 mm bore complete with all fittings, laid under roads, drain, paths, fixed to poles/ walls with suitable mild steel clamps , bolts , nuts and washers complete all as specified and directed as for cable proction . Note:- Excavation & earth work shall be measured and paid for separately under appropriate item of this schedule
All as per Item Ser No 59.00 here-in-before but of size 80 mm bore
All as per Item Ser No 59.00 here-in-before but of size 50 mm bore
All as per Item Ser No 59.00 here-in-before but of size 40 mm bore
S&F in replacement of polycarbonate thermoplastic weather proof junction boxes IP-65/66 for street lights size of approx size not less than 205 x 255 x 112 mm with metric knock outs for cable entry, weather proof for outdoor installation, glands and with 4 terminals, terminal rating 32 Amps for three phase and neutral mounted with locking arrangement including fixing to the poles by means of suitable size of clamps, nuts and bolts with and including 01 no SP, MCB, 6-32 Amps,10KA complete all as specified and directed.
S&F of integral LED Street light luminaire of not less than 60 W, luman efficacy not less than 125 lm per watt, comprising of die cast alluminium housing, enclosed with glass cover in frame, IP-66 protection suitable for voltage range should be 170 to 240 Volts with glass cover and with all fixing arrangement, nuts, bolts and washer connecting to electric system with 1.5 sqmm PVC aluminium stranded conductor 3 core connected upto pole box, on pole including testing complete and fixed with bracket made out of GI pipe 40 mm dia (light grade) 1.2 metre long and MS clamp and nut bolts washersall as specified and directed.
M&L for precast cable route Indicator made out of cement concrete 1:2:4, type B1, using (20mm graded stone aggregate) having 10cm square shape at top and 20cm square shape at bottom and total height of 90cm casted as per direction and grouted into PCC 1:2:4, type B-1, 35 cm below ground level as per site requirement including embossed with "LT 1100 V Cable" and also painting in synthetic enamel Paint and necessary excavation and earth work in any type of soil as directed.
M&L for Cutting hard standing ,Roads,Path, plinth protections for laying of cable/ protection pipe complete all as specified and as directed.
M&L for making good the disturbed surface by filling PCC 1:2:4 type, B-2 using 40 mm graded course aggregate to match with existing surfaces all as specified and directed.
M&L for Brick work with sub class ‘B’ bricks, straight or curved on plan with 1:4 cement mortar for wall, plinth foundation pillar or base of pipe/ cable etc complete all as specified and directed
M&L for PCC 1:4:8 type D2 using 40mm graded stone aggregate as in foundations bed of pole/ stay assembly complete all as specified and directed
M&L for PCC 1:3:6 type C2 using 40mm graded stone aggregate as in foundations of pole/ stay assembly complete all as specified and directed
M&L for PCC 1:2:4 type B1 using 20mm graded stone aggregate as in coping of pole including necessary form work complete all as specified and directed
Supply and erection in replacement of Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9.00 meters long) including painting of poles with two coats of aluminium paint over a coat of red oxide primer on all exposed surfaces and black bituminous paint on embedded portion and Zebra marking on pole with black paint up to one meter height above PCC coping including pasting of radium reflector band / strips (Make: 3M or equivalent) of 5cm wide in Green (02 Nos) & White (01 No.) colour shall be provided at a height of 1.25mtr from coping of pole and writing the pole number in black colour on yellow background at a suitable place on the pole including taking down existing unserviceable pole of any description complete all as specified and directed by Engineer-in-Charge. (Note: Excavation and concrete shall be measured and paid separately under relevant items of this BOQ).
Material & labour for three core (for phase , neutral and earth) multistandred aluminium cable 2.5 Sqmm size, 1100 volt grade, PVC insulated unsheathed, cable drawing in steel tubular poles from junction box to street light fitting and testing complete all as directed.
Supply and fixing in replacement for replacement of rusted/corroded security light bracket made out of GI pipe of light grade 1.5 RMx40mm dia and 0.3RM x32 mm dia at one end for inserting of light fitting, properly shaped, bended, & fixed on the pole through MS flat by nut, bolt & washer of suitable sizes incl dismantling the old unsv existing one complete all as specified and directed.
Material and labour for taking down of Street light of any capacity from Electric pole/walls and refixing after repair /replacement complete all as specified and as directed.
M&L indoor/outdoor end terminations Joints kit (Epoxy) Cable Joint Kit including Jointing Materials for making Joints of UG Electric Cable 1100 Volt Grade Heavy Duty with PVC/XLPE insulated Aluminium Stranded Conductor, nominal Cross-Sectional area from 4 Sqmm upto 16 Sqmm, 3½ Core and Testing complete all as specified and as directed.
All as per Item Ser No 76.00 here-in-before but of size 25 sqmm to 50 sqmm
All as per Item Ser No 76.00 here-in-before but of size 70 sqmm to 150 sqmm
All as per Item Ser No 76.00 here-in-before but of size 185 sqmm to 300 sqmm
M&L for straight through Joints kit (Epoxy) Cable Joint Kit including Jointing Materials for making Joints of UG Electric Cable 1100 Volt Grade Heavy Duty with PVC/XLPE insulated Aluminium Stranded Conductor, nominal Cross-Sectional area from 10 Sqmm upto 16 Sqmm, 3½ Core and Testing complete all as specified and as directed.
All as per Item Ser No 80.00 here-in-before but of size 25 sqmm to 50 sqmm
All as per Item Ser No 80.00 here-in-before but of size 70 sqmm to 150 sqmm
All as per Item Ser No 80.00 here-in-before but of size 185 sqmm to 240 sqmm
All as per Item Ser No 80.00 here-in-before but of size 300 sqmm to 400 sqmm
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 5.04 MB
BOQ_837831.xls
BOQ • 0.39 MB
tender.pdf
Tender Documents • 1.56 MB
Download all tender documents and submit your bid