| 1 | L1₹14.1 LAccepted-AOC | ₹14.1 L Quoted ₹14.4 L | L1 | Accepted-AOC Accepted |
| 2 | L2₹15.9 L+₹1.4 L (9.94%)Rejected-AOC 1001 B BHAVESHWAR BLDG NO 03 BHAVESHWAR LANE GHATKOPAR EAST MUMBAI 400077 | MUMBAI SUBURBAN | MAHARASHTRA | 400077 | ₹15.9 L+₹1.4 L (9.94%) | L2 | Rejected-AOC Not Accepted |
Tender Value
₹15.5 L
EMD Value
₹31,000
Closing Date
21 Jan 2023, 6:00 pmClosed
GE North Mumbai
Garrison Engineer North Mumbai Military Engineer Services Santacruz East, Mumbai
Repair / replacement of UG cable, LT panel, feeder pillar boxes, dg sets, street lights, perimeter lights with connected items at Malad, Kandivali and Marve under GE North Mumbai
2022_MES_570976_1
8118/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Garrison Engineer North Mumbai
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Garrison Engineer North Mumbai
₹31,000
Yes
31 Jan 2023
23 Dec 2022
23 Jan 2023
23 Dec 2022
21 Jan 2023
7 Jan 2023
24 Dec 2022 - 5 Jan 2023
Amount
Excavation in trenches, not exceeding 1.50 m wide and not exceeding 1.5 m in depth, for foundation, cable trenches etc, not exceeding 10 sqm on plan and getting out soft / loose soil complete all as specified and as directed by Engineer-in-Charge.
Returning, filling in including spreading, levelling, watering and well ramming in layer not exceeding 25cm in soil complete all as specified and as directed by Engineer-in-Charge.
Removing excavated material to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and as directed by Engineer-in-Charge
Supply and lay double wall corrugated (DWC) HDPE pipe 63mm bore, as per IS-16205 including couplers and bend for cable protection laid in trenches etc complete all as specified and as directed by Engineer-in-Charge Make : TELEREX 450N or equivalent as approved by GE
Supply and lay double wall corrugated (DWC) HDPE pipe 90mm bore, as per IS-16205 including couplers and bend for cable protection laid in trenches etc complete all as specified and as directed by Engineer-in-Charge Make : TELEREX 450N or equivalent as approved by GE
Supply and Lay LTUG XLPE insulated, heavy duty, 1100 V grade electric cable with aluminium conductor, served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed, laid in trenches or passing through pipe, making all connections with and including provision of necessary glands, lugs, bushing etc as required including taking down old unserviceable cable complete all as specified and as directed by Engineer-in-Charge of following sizes:- Note : Earthwork excavation, DWC pipe for cable protection shall be measured and paid separately in their respective items
10 Sqmm x 2 core
10 Sqmm x 4 core
16 Sqmm x 4 core
25 Sqmm x 4 core
35 Sqmm x 3.5 core
50 Sqmm x 3.5 core
70 Sqmm x 3.5 core
95 Sqmm x 3.5 core
Material and labour for straight Through Heat shrinkable type Cable Joint Kit including Jointing Materials for making Joints of LT UG Electric Cable 1100 Volt Grade Heavy Duty with XLPE insulated Aluminium Stranded Conductor of size 25/35Sqmm x 3½ Core and Testing complete all as specified and as directed. Make: Densons/ M Seal/ Raychem/ Siemens / Birla 3M/ Mahindra & Mahindra
All as per item No 7 described here-in-before but of size 50 Sqmm to 95 Sqmm x 3½ Core and Testing complete all as specified and as directed.
All as per item No 7 described here-in-before but of size 120 Sqmm to 150 Sqmm x 3½ Core and Testing complete all as specified and as directed.
Supply and fix in repairs copper strip bus bar chamber 100 Amp 4 phase four pole 415 volts all as specified. Make: BENTEC or equivalent in C&S / Havells / Indoasia.
Refixing / relaying of existing disturbed / uprooted existing LT electric cable of size upto 300 Sqmm to the existing places with the steel saddles from ground level to four storey bldg distribution box etc complete with using electric drill machine, nut & bolt and proper grouted all as specified and as directed.
Supply and fix galvanised iron pipe, light grade, 40mm bore for cable protection on wall, trenches, road crossings etc. with suitable size of GI saddle, wherever necessary complete all as specified and as directed by Engineer-in-Charge. Make: TATA/SWASTIK/JINDAL/Bharat Steel tube/ZENITH/Indian Tube Company
Supply and fix galvanised iron pipe, light grade, 50mm bore for cable protection on wall, trenches, road crossings etc. with suitable size of GI saddle, wherever necessary complete all as specified and as directed by Engineer-in-Charge. Make: TATA/SWASTIK/JINDAL/Bharat Steel tube/ZENITH/Indian Tube Company
Supply and fix galvanised iron pipe, light grade, 80mm bore for cable protection on wall, trenches, road crossings etc. with suitable size of GI saddle, wherever necessary complete all as specified and as directed by Engineer-in-Charge. Make: TATA/SWASTIK/JINDAL/Bharat Steel tube/ZENITH/Indian Tube Company
Material and labour for finding cable fault with electronic fault detector in LT UG cable of size upto 185 sqmm x 3.5core complete including necessary earth work excavation all as specified and as directed by Engineer-in-Charge.
Supply and fix MCCB 4 pole, 100/125 Amps, 415 Volts, 50 Hz, 25 KA breaking capacity, thermal & magnetic adjustable type with extended copper terminals including all connections and testing including taking down of old unserviceable MCCB complete all as specified and as directed by Engineer-in-charge. Make: Schneider / Havells / L&T / ABB / Legrand / Siemens / C&S
All as per item No 16 described here-in-before but rating 160 Amps 25 KA
All as per item No 16 described here-in-before but rating 200 Amps 36 KA
All as per item No 16 described here-in-before but rating 250 Amps 36 KA
All as per item No 16 described here-in-before but rating 400 Amps 36 KA
All as per item No 16 described here-in-before but rating 63 Amps 25 KA
Supply, install, test and commissioning suitable size factory made out door type, dust and vermin proof, LT feeder pillar box, double door, cubical and compartmentalized type, 415 volts, AC, 50 Hz, fabricated with non corrosive 3 mm thick CRCA sheet for outer side and 2 mm thick inside complete with and including mounted on angle iron frame stand of size 50 x 50 x 6 mm thick, 50 cm long leg, grouted in PCC (1:2:4) type B1 (using 20 mm graded stone aggregate), spray painted inside and outside, powder coated of approved colour by Engineer-in-Charge, including openable shutters butt hinged, locking arrangement, PCC work, excavation & earth work complete including comprising for following and taking down existing etc complete all as specified and as directed by Engineer-in-Charge:-
INCOMING (i) MCCB, 4 pole, 250 Amps, 415 volts, 36 KA, 50 Hz with adjustable thermal and adjustable magnetic setting - 01 No. (ii) 3 Phase digital multifunctional meter - 01 No (iii) LED type indicator lamps RYB - 01 Set (iv) CT (150/5A) - 03 Nos OUTGOING (i) MCCB, 4 pole, 160 Amps, 415 volts, 25 KA, 50 Hz with adjustable thermal and adjustable magnetic setting - 02 Nos. (ii) MCB, TPN, 32 Amps, breaking capacity 10KA, 415 volts, 50 Hz - 01 No (iii) MCB 2 pole of capacity 16 Amps, breaking capacity 10KA - 01 No (for timer) (iv) Austro time switch - 01 No (for timer) (v) Power contactor 3 pole AC with 230V coli, 20 Amps rating - 01 No (for timer) (vi) 250Amps rated aluminium busbar TPN duly insulated with cloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator busbar support (Square / round) insulators of suitable size and good insulation resistance Note: (i) Contactor shall be submit the drawings of panels for approval before fabrication in factory. (ii) Feeder pillar box / panel board shall be CPRI approved.
Material and labour for cutting the existing bituminous road / hard standing of size not exceeding 45cm wide and depth exceeding 30cm and not exceeding 45cm for passing of UG cable through GI pipe and making good the disturbed surface filled with excavated material and top 200mm depth with plain cement concrete 1:3:6, type C1 using 20mm graded aggregate complete all as specified and directed by Engineer-in-Charge.
Material and labour for cutting of grasses by manually / grass cutter etc, cleaning and levelling surroundings of substation (Approx area of installation is 10 Sqm) including removal of spoil, wastage materials etc to a distance not exceeding 50m complete all as specified and directed by Engineer-in-Charge.
Supply and fix in replacement of multifunctional meter in existing panel/ feeder 3 phase 4 wire CT operated with necessary CT copper wournt out of rating 300/5 Amps for 3 phase, 15 VA, Class-I accuracy suitable for recording KWH, KVA, KW, kVAh, PF etc, flush mounted 96x96mm, input voltage measurement range 50-520 VAC, including necessary wiring for connections all as specified and as directed by Engineer-in-Charge. Make: L&T Cat No. WL4405110000 / C&S
Supply and fix indicator lamp LED type, 220 with holder all as specified and as directed by Engineer-in-Charge.
Material and labour for painting the old LT panel board / feeder panel boxes including scraping and removing the old painted surfaces and painting with same colour paint matching properly with two coats of synthetic enamel paint and without disturbing the existing electric system complete all as specified and as directed by Engineer-in-Charge.
Supply and fix in replacement of street light bracket arm fabricated out of 40mm dia GI tubing medium grade 1.2 meter long bend to shape fixed on pole with including 2 pair of clamps of fitted with suitable size nuts, bolts washers including one coat of paint complete all as specified and as directed by Engineer-in-Charge.
Supply and fix in repairs cable junction box made out of thermoplastic sheet, IP66 protected outdoor installation of size 200 x 160 x 98mm with 4 way bakelite cable terminals including 03 Nos polyimide gland with check nut (M-32- 2 Nos) fixed on poles with flat iron clamps of size 25x3mm, nut, bolt, washers etc including applying two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer and provision of one single pole MCB 6 amps for controlling light etc complete all as specified and as directed by Engineer-in-Charge. Make : Sintex GS-JB-2014 / K-8250 of Hensel or equivalent in National
Supply and fixing 3 core PVC insulated and unsheathed 1100 volt grade multicore cable 1.5 sqmm with stranded copper conductor cable drawn inside the pole whereas required with making necessary holes on bottom and top of pole from looping box to security light fitting etc complete all as specified and as directed by Engineer-in-Charge. Make: Finolex / Plaza / Anchor / Havells / Polycab
Supply and fix in repairs Analog timer switch, single phase, 240 volt complete all as specified and as directed by Engineer-in-Charge. Make: L&T Cat Part No. J6107B204 or equivalent as approved by Engineer-in-Charge.
Supply and fix in repairs ML-3, three pole power contactor 40Amps rating, coil voltage 240V, 50Hz complete all as specified and as directed by Engineer-in-Charge. Make: L&T Cat Part No. SS90721 or equivalent as approved by Engineer-in-Charge.
Supply, install, test and commission LED street light fitting 70 watts, rating, separate individual peanut plated lens and aluminium reflector housing made of LM6 pressure die cast aluminium. Optical cover toughened glass/fibre only, impact resistance>IK05 IP protection not less than IP66, protection should be class I vibration as per IEC 60598, product standard IS 10322/IEC60598, all the component such as driver, surge protector should be of same make. Driver should be moulded type with operating voltage 140V270V, driver frequency 50 Hz power factor >0.9, Lumen output should not be less than 130 lumen/watt and luminaire driver ckt, moulded type weather proof construction with separate surge protection device 5 KA rating and separate connector block for termination of incoming cable connection all as specified and directed by Engineer-in-Charge. Make - Phillips Cat part No - BRP40970V3 SPD or Equivalent to Crompton / Havells / General electric (GE)
Supply, install, test and commission LED Street light fittings minimum 90 watt rating, separate individual peanut plated Lens and housing should be made of LM6 Pressure die Cast aluminium. Optical cover should be only Toughened Glass only, Product Standard IS 10322/IEC 60598, all the component such as driver, surge proctor should be of same Make. Driver should be moulded type with Operating Voltage should be 140V - 270V, Driver frequency 50Hz Power Factor>0.9, Lumen output should not be 110 lun/watt, moulded type weather proof construction, with separate surge protection device 5 KA rating and separate connector block for termination of incoming cable connection all as specified and as directed by Engineer-in-Charge. Make: Phillips Cat Part No BRP033 LED90 CW SLR GR PSU or equivalent to Bajaj / Crompton.
Supply and erect 9.0 metre long steel tubular swaged poles type 410 SP-31 complete with cast iron base plate, finial taper plug, bolts, nuts & screws including taking down existing etc complete all as specified and as directed by Engineer-in-Charge. Note: Earth work excavation, PCC for foundation and coping will be measured and paid separately. Make: India Tube and Co / India Electric Poles Mfg Co,Maharashtra / Bombay Tubes / Kalinga Tubes / Singh Profile, Pune
Material and labour for Plain Cement Concrete 1:3:6 type C1 using 20mm graded stone aggregate as in coping of poles including necessary formwork etc complete all as specified and as directed by the Engineer-in-charge
Material and labour for Plain Cement Concrete 1:4:8 type D2 using 40mm graded stone aggregate as in foundation / mass concrete including necessary formwork etc complete all as specified and as directed by the Engineer-in-charge
Material and labour for complete removal of existing paint of steel tubular / rail poles length up to 9 mtr including preparation of outer surface and applying two coats of aluminium paint over a coat of red oxide and two strip of yellow and black colour paint of size 30 cm width from bottom of pole height 30 cm, including numbering to pole with base paint of yellow colour and Black for numbering should not be less than 100 mm in height and 10 mm in width complete all as specified and as directed by Engr-in-Charge
Supply and fix aluminium bus bar chamber 63 Amps 4 pole 415 volts with all fixing accessories etc complete all as specified and as directed by Engineer-in-Charge. Make : C&S / Havells / L&T / Legrand
Supply and fix in repairs MCB TPN 63 Amp, 16KA braking capacity 230/240 volt AC complete all as specified and as directed. Make : C&S / Havells / L&T / Legrand
Supply and fix in repairs MCB SPN 32 Amps, 240V, 10KA 'C' curve complete all as specified and as directed. Make : C&S / Havells / L&T / Legrand
Supply and fix in repairs MCB SP 5 to 32 Amps, 240V, 10KA 'C' curve complete all as specified and as directed. Make : C&S / Havells / L&T / Legrand
Material and labour for trimming the branches of tree surrounding street light pole etc complete all as specified and as directed by Engineer-in-Charge.
Labour only for servicing of 60 KVA DG Set with draining out of engine oil/lubricant coolant, taking out of unserviceable Oil Filter element, Fuel filter element, fuel flexible pipe, V belt for water pump and alternator, air filter element, cleaning of Fuel tank, filling of oil, lubricant etc complete all as specified and as directed. Make : Kirloskar. (Location. : Kandivali) Note : Spares and lubricant, oil shall be measured and paid separately as supply only under respective items here-in-after.
Supply only Fuel Filter element
Supply only Lub Oil Filter element
Supply only Air Filter Element (Inner & Outer)
Supply only 'V' Belt
Supply only Hose pipe
Supply only Engine oil 15W40 to top-up/refilling of 60 KVA DG set as per the standard practice. (Make: Servo / Castrol / HP / Valvoline.
Supply only of coolant suitable for DG set Make: Castrol / Servo / Purokool / K-Kool)
Supply and fix maintenance free lead acid battery, 12 volt 150 AH all as specified and as directed. Make: Exide or Amaron.
Supply and fix flexible fuel/oil pressure pipe of existing size and length upto 1.8 mtrs and connecting complete suitable for DG set of 60 KVA all as specified and as directed. Make Kirloskar.
Dismantling of self starter and provision of rewinding and refixing the same all as per manufacturers instructions and as directed by Engineer-in-Charge .
Supply and fix for SMPS battery charger 12 volts, 10 Amps, DC output and 285 volts AC input with MCB of suitable size both for AC & DC ammeter, two stage charging (first mode plus trickle mode) with manual current setting 1 to 10 Amps complete with over load cut off system all as specified and as directed. Make : Magic power / Bosch .
Material and labour for Earthing complete with Galvanised steel earth plate electrode 60 cm x 60 cm x 6.0 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of earth the plate not less than 1.5 metres below normal ground level, connected to and including galvanised earth strip of size 25 x 4mm, 7.5m long, by means of bolts, nuts, check nuts and washers made out of galvanised iron or steel with provision of charcoal & common salt packed upto minimum 150 mm all around the earth plate, and protected by 15 mm bore medium grade galvanised iron pipe and connected to control board / panel / equipment complete all as shown in electrical plate No.3 of MES schedule Part I with PCC pit in PCC 1:2:4 type B1 using 20 mm graded stone aggregate, MS angle iron frame of size 50mm x 50mm x 5mm, cast iron cover with locking arrangements, GI 20 mm bore medium grade pipe and CI funnel with wire mesh for watering arrangement including necessary excavaion and earth work in any type of soil/strata & testing complete all as specified and as directed by Engineer-in-Charge.
Material and labour for Earthing complete with Galvanised steel earth plate electrode 60 cm x 60 cm x 6.0 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of earth the plate not less than 1.5 metres below normal ground level, connected to and including galvanised earth lead wire 4 mm dia, 7.5m long, by means of bolts, nuts, check nuts and washers made out of galvanised iron or steel with provision of charcoal & common salt packed upto minimum 150 mm all around the earth plate, and protected by 15 mm bore medium grade galvanised iron pipe and connected to control board / panel / equipment complete all as shown in electrical plate No.3 of MES schedule Part I with PCC pit in PCC 1:2:4 type B1 using 20 mm graded stone aggregate, MS angle iron frame of size 50mm x 50mm x 5mm, cast iron cover with locking arrangements, GI 20 mm bore medium grade pipe and CI funnel with wire mesh for watering arrangement including necessary excavaion and earth work in any type of soil/strata & testing complete all as specified and as directed by Engineer-in-Charge.
Note: Deduct Credit for demolished / dismantled material of Rs. (-) 32,751.00 (Minus) as listed in Schedule of Credit. Tenderers will not quote against this item being a tentative amount to be considered to arrive at the 'Contract Sum'
EVEREST POWER CONTROL ENGINEERS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .