GE NORTH PUNE
Garrison Engineer North General Cariappa Marg Camp Pune 411001
GE (N) P/TOKEN- 04 OF 2021-2022REP/ MAINT OF COOLING APPLIANCES SUCH AS AIR CONDITIONERS, WATER COOLERS DEEP FREEZERS, REFRIGRATORS, DESERT COOLERS ETC INSTALLED AT VARIOUS LOC /BLDG AND OTHER ALLIED WORKS IN THE AREA OF AGE E/M UNDER GE (N) PUNE
2021_MES_437685_1
GE (N) P/TOKEN- 04 OF 2021-2022
Open Tender
Electrical and Maintenance Works
Item Rate
300 days
GE NORTH PUNE
Refer tender documents.
8 documents required · 8 mandatory
₹500
GE NORTH PUNE
₹91,600
Yes
1 Jul 2021
22 Apr 2021
21 May 2021
22 Apr 2021
19 May 2021
7 May 2021
Amount
Servicing only for window type air conditioner in situ of capacity 1.5/2.0 Ton of any make and any type by replacing unserviceable parts (except compressor) from the machine and cleaning of cooling coil, condensing coil, oiling, greasing of blower motor, checking of electrical circuit and replacement of defective thermostat switch, relay, capacitor and over load protector to achieve proper cooling effect and testing commissioning complete all as specified and as directed. Note: Additional quantity of referigerant gas if required shall be measured and paid separately as supply and charging.
Taking out unserviceable window type air conditioner of capacity 1.5/2.0 Ton of any make and any type by replacing unserviceable compressor and other parts from the machine and cleaning of cooling coil, changing of wirings with proper size PVC insulated wires as directed and install the air conditioner after proper repair and testing at location where directed complete all as per the satisfaction of Engineer-in-Charge. Note for item No 1 & 2 :- (i) Compressor where ever is required shall be measured and paid separately under relevant item. (ii) Additional quantity of referigerant gas if required for smooth functioning shall be measured and paid separately under relevant item as supply and charging. iii) Spares parts where ever is required shall be measured and paid separately under relevant item. iv) Unit rate is deemed to be included for minor parts such as capilary tube, machine screw, washer, rubber bush etc required for proper setting of machine.
Supply only for thermostat suitable for window type AC 1.5//2.0 ton capacity for 230 volt 50 Hz AC supply all as per specified.
Supply only for PVC insulated, copper cable, 4 Sqmm , 3 core, complete all as specified.
Supply only for PVC insulated, copper cable, 2.5Sqmm , 3 core, complete all as specified.
Supply only of condenser fan/blower motor with bush and washers as per existing make and model for Window AC up to 2 TR Capacity complete all as specified and directed.
Supply only for capillary tube special annealed double wound copper tubing suitable for 1.5/2 ton window type air conditioner of diameter 0.25" bore as per existing complete all as specified.
Supply only for capillary tube special annealed double wound copper tubing suitable for 1.5/2 ton window type air conditioner of diameter 0.38" bore complete all as specified.
Supply only for cooling coil made out of copper tube of size as per existing coil capacity and specification suitable for 1.5/2 ton window AC of any make and type as per existing complete all as specified.
Supply only for condenser coil made out of copper tube of size as per existing coil capacity and specification suitable for 1.5/1.8/2 ton window AC of any make and type as per existing complete all as specified and as directed.
Removing the old unserviceable sealed compressor unit from window type AC of any make, capacity 1.5 TR and Supply and fix for hermetically/ rotary sealed compressor unit 1.5 TR capacity for window type AC with necessary mounting arrangements suitable for working with non CFC refrigerent including supply and charging of non CFC refrigerant gas and oil at adequate level and jointing all pipe connection and checking gas pressure complete all as specified and as directed. Make : LG/Whirlpool/Blue Star/Godrej as approved.
Removing the old unserviceable sealed compressor unit from window type AC of any make, capacity 2 TR and Supply and fix hermetically sealed compressor unit 2 TR capacity for window type AC with necessary mounting arrangements suitable for working with non CFC refrigerant including supply and charging of non CFC refrigerant gas and oil at adequate level and jointing all pipe connection and checking gas pressure complete all as specified and as directed. Make : LG/Whirlpool/Blue Star/Godrej as approved.
Material and labour for taking out window type air conditioner of any capacity and make for shifting at other place after making necessary opening in window/ wall of any type and thikness, cutting of grill any type/ size fixing of AC after servicing, providing necessary plywood, commerical type, 6 mm thick of suitable size as packing material to cover the hole/ window complete all as specified and as directed. Note :- Transportation for shifting of AC's will be provided by contractor and rate for same is deemed to be included in the quoted rate.
Servicing only split type air conditioner in situ (Split type air conditioner comprises with outdoor and indoor unit complete) of capacity 1.5/ 2.0 TR of any make and any type by replacing unserviceable parts from the machine and cleaning of cooling coil and condenser coil, oiling, greasing of blower motor, checking of electrical circuit and replacement of defective electric blower fan motor, over load protector, relay, capacitor etc to achieve proper cooling effect and also checking of electronic circuit of machine and repair where necessary by replacing electronic parts and changing of wirings with proper size PVC insulated wires as directed and testing commissioning complete all as specified and directed. Note for item No 14 : (i) Compressor where ever is required shall be measured and paid seperately under relevant item. (ii) Additional quantity of referigerant gas if required for smooth functioning shall be measured and paid separately under relevant item as supply and charging. (iii) Spares parts where ever is required shall be measured and paid seperately under relevant item. (iv) Unit rate is deemed to be included for minor parts such as capilary tube, machine screw, washer, rubber bush etc required for proper setting of machine.
Supply only unserviceable swinging motor of indoor unit of split type AC up to 3TR capacity suitable for existing make/model complete all as specified and directed by Engr in charge
Supply only condenser fan/blower motor with bush and washers as per existing make and model for split type AC up to 3 TR Capacity complete all as specified and directed.
Supply only for overload protector for split type AC of capacity 1.5 ton as per site requirement complete all as specified.
Supply only for running capacitor 36 MFD complete all as specified.
Supply only for running capacitor 50+4, 50+6 MFD complete all as specified.
Supply only for running capacitor 45 MFD complete all as specified.
Supply only for starting capacitor 100/120 MFD complete all as specified.
Supply only for out door unit fan blade heavy duty of existing make Split AC of capacity 1.5 ton/ 2.0 ton as per existing complete all as specified.
Supply and fix for copper tubing of size 1/2” for discharge line of any make split AC of capacity 1/1.5 ton with insulation sheet of pipe tube type insulation including taking down of old existing unserviceable one complete all as specified and as directed.
Supply and fix for copper tubing of size 1/4” for discharge line of any make split AC of capacity 1/1.5 ton with insulation sheet of pipe tube type insulation including taking down of old existing unserviceable one complete all as specified and as directed.
Supply and fix for copper tubing of size 3/8” for discharge line of any make split AC of capacity 2 ton with insulation sheet of pipe tube type insulation including taking down of old existing unserviceable one complete all as specified and as directed.
Supply and fix for copper tubes of size 5/8” for suction line of any make split AC of capacity 2 ton including insulation sheet of pipe tube type insulation including taking down of old existing unserviceable one complete all as specified and directed.
Supply and fix for high wall blower fixed on indoor unit of make as per existing split AC 1.5/2 ton capacity including taking down of old existing unserviceable one complete all as specified and as directed.
Supply and fix for indoor unit for split type air conditioner 1.5 ton capacity wall mounted operation on 230 volts + 10% 50 HZ single phase performing on cooling, dehumidifying, cord less, remote and digital temp display system of make as per existing including taking down of old existing unserviceable one complete all as specified and as directed.
Supply and fix for indoor unit for split type air conditioner 2.0 ton capacity wall mounted operation on 230 volts + 10% 50 HZ single phase performing on cooling, dehumidifying, cord less, remote and digital temp display system of make as per existing including taking down of old existing unserviceable one complete all as specified and as directed.
Supply and fix for flexible PVC pipe 40 mm dia heavy duty from outdoor unit to indoor unit including taking down of old existing unserviceable one complete all as specified and as directed.
Removing the old unserviceable sealed compressor unit from split AC of any make, capacity 1.5 TR and supply and fix for new hermetically/ rotary sealed compressor of same make as per site requirement for split AC of capacity 1.5 TR with necessary mounting arrangements suitable for working with non CFC refrigerent including supply and charging of non CFC refrigerant gas and oil at adequate level and jointing all pipe connection and checking gas pressure complete all as specified and as directed. Make : LG/Whirlpool/Blue Star/Godrej as approved.
Removing the old unserviceable sealed compressor unit from split AC of any make, capacity 2.0 TR and supply and fix for new hermetically/ rotary sealed compressor of same make as per site requirement for split AC of capacity 2.0 TR with necessary mounting arrangements suitable for working with non CFC refrigerant including supply and charging of non CFC refrigerant gas and oil at adequate level and jointing all pipe connection and checking gas pressure complete all as specified and as directed. Make : LG/Whirlpool/Blue Star/Godrej approved.
Removing the old unserviceable sealed compressor unit from split AC of any make, capacity 2.5 TR and supply and fix new hermetically/ rotary sealed compressor of same make as per site requirement for split AC of capacity 2.5 TR with necessary mounting arrangements suitable for working with non CFC refrigerant including supply and charging of non CFC refrigerant gas and oil at adequate level and jointing all pipe connection and checking gas pressure complete all as specified and as directed. Make : Shriram/ Kirloskar/ USHA as approved.
Supply and fix for PCB (Printed circuit board) of indoor unit of 1.5 ton capacity split AC including taking down of old existing unserviceable one complete all as specified and as directed. Make:LG/ Voltas/ Blue star/ Samsung/ Wirlpool as approved.
Supply and fix for thermostat switch of any make of split AC 1.5/ 2.0 ton capacity including taking down of old existing unserviceable one complete all as specified and as directed.
Supply and fix for new powder coated mild steel stand suitable for outdoor unit of split AC of existing size to install outdoor unit on wall/ floor as required on site with legs and bracing etc including taking down of old existing unserviceable one complete all as specified and as directed.
Taking down existing unserviceable outdoor unit and supply and fix for new outdoor unit for 1.5 TR capacity split AC suitable for working with and including non CFC refrgerant gas with blower motor fan, cooling coil all pre-wired with compressor of make as per existing complete all as specified and as directed.
Taking down unserviceable outdoor unit and supply and fix for new outdoor unit for 2.0 capacity split AC suitable for working with and icluding non CFC refrgerent gas with blower motor fan, cooling coil all pre-wired with compressor of make as per existing complete all as specified and as directed.
Supply and fix for remote control for AC as per sample of any make, type, capacity including taking down of existing unserviceable one complete all as specified and as directed.
Material and labour for taking out split type air conditioner indoor and outdoor unit complete with copper tubing of any size and make for shifting at other place after making necessary opening size, cutting of wall any type/ thickness and fixing of AC after necessary servicing, making suitable arrangement for fixing of AC complete all as specified and as directed. Note : Transportation for shifting of ACs will be provided by contractor and rate for same is deemed to be included in quoted rate.
Material and labour for comprehensive maintenance of air cooled ductable split air conditioner of capacity 10.00 TR including servicing the entire system, including cleaning the machines, cleaning the filters by water, cleaning the ducting and checking the all electrical connections, contactors, relays, oil greasing to electrical motors etc for smooth functioning of the plant complete all as specified and as directed. (Note: Maintemance of the plant will be carried out once in three months and will be measured as unit "Each Job")
Material and labour for comprehensive maintenance of Package AC of 7.50 TR capacity including servicing the entire system, cleaning the machines, cleaning the filters by water, cleaning the ducting and checking the all electrical connections, contactors, relays, oil greasing to electrical motors etc for smooth functioning of the plant complete all as specified and as directed. (Note :- Maintemance of the plant will be carried out once in three months and will be measured as unit "Each Job")
Material and labour for comprehensive maintenance of Package AC of 5.0 TR capacity including servicing the entire system, cleaning the machines, cleaning the filters by water, cleaning the ducting and checking the all electrical connections, contactors, relays, oil greasing to electrical motors etc for smooth functioning of the plant complete all as specified and as directed. (Note: Maintemance of the plant will be carried out once in three months and will be measured as unit "Each Job")
Material and labour for comprehensive maintenance of Package/ split type AC of 4.0 TR capacity including servicing the entire system, cleaning the machines, cleaning the filters by water, cleaning the ducting and checking the all electrical connections, contactors, relays, oil greasing to electrical motors etc for smooth functioning of the plant complete all as specified and as directed. (Note :- Maintemance of the plant will be carried out once in three months and will be measured as unit "Each Job")
Material and labour for comprehensive maintenance of tower AC of 4.0 TR capacity including servicing the entire system, cleaning the machines, cleaning the filters by water, cleaning the ducting and checking the all electrical connections, contactors, relays, oil greasing to electrical motors etc for smooth functioning of the plant complete all as specified and as directed. (Note: Maintemance of the plant will be carried out once in three months and will be measured as unit "Each Job")
Material and labour for comprehensive maintenance of tower AC of 3.0 TR capacity including servicing the entire system, cleaning the machines, cleaning the filters by water, cleaning the ducting and checking the all electrical connections, contactors, relays, oil greasing to electrical motors etc for smooth functioning of the plant complete all as specified and as directed. (Note: Maintemance of the plant will be carried out once in three months and will be measured as unit "Each Job")
Material and labour for comprehensive maintenance of tower AC of 2.0 TR capacity including servicing the entire system, cleaning the machines, cleaning the filters by water, cleaning the ducting and checking the all electrical connections, contactors, relays, oil greasing to electrical motors etc for smooth functioning of the plant complete all as specified and as directed. (Note: Maintemance of the plant will be carried out once in three months and will be measured as unit "Each Job")
Removing the old unserviceable sealed compressor unit from ductable package/ split AC of any make of capacity 7.50 TR and supply and fixing new hermatically sealed compressor of same existing make for ductable split AC of capacity 7.50 TR suitable for working with non CFC refrigerant including supply and charging of non CFC refrigerant gas and oil at adequate level and jointing all pipe connection and checking gas pressure complete and all as specified and as directed. Make: As per existing as approved
Removing the old unserviceable sealed compressor unit from ductable package/ split AC of any make of capacity 5.0 TR and supply and fixing new hermatically sealed compressor of same existing make for ductable split AC of capacity 5.0 TR suitable for working with non CFC refrigerant including supply and charging of non CFC refrigerant gas and oil at adequate level and jointing all pipe connection and checking gas pressure complete and all as specified and as directed. Make: As per existing as approved
Removing the old unserviceable sealed compressor unit from ductable split/ tower/ package AC of same existing make of capacity 4.0 TR and supply and fixing new hermatically sealed compressor of same make for ductable split AC of capacity 4.0 TR suitable for working with non CFC refrigerant including supply and charging of non CFC refrigerant gas and oil at adequate level and jointing all pipe connection and checking gas pressure complete and all as specified and as directed. Make: As per existing as approved
Removing the old unserviceable sealed compressor unit from ductable split/ tower AC of same existing make capacity 3.0 TR and supply and fixing new hermatically sealed compressor of same make for ductable split/ tower AC of capacity 3.0 TR suitable for working with non CFC refrigerant including supply and charging of non CFC refrigerant gas and oil at adequate level and jointing all pipe connection and checking gas pressure complete and all as specified and as directed. Make: As per existing as approved
Removing the old unserviceable sealed compressor unit from ductable split/tower AC of same existing make of capacity 2.0 TR and supply and fixing new hermatically sealed compressor of same make for ductable split/ tower AC of capacity 2.0 TR suitable for working with non CFC refrigerent including supply and charging of non CFC refrigerant gas and oil at adequate level and jointing all pipe connection and checking gas pressure complete and all as specified and as directed. Make: As per existing as approved
Supply and fix for PCB (Printed circuit board) of ductable type AC unit 7.5 TR of existing make including taking down of existing unserviceable one complete all as specified and directed.
Supply and fix for PCB (Printed circuit board) of ductable type suitable for AC unit 5.0 TR of existing make including taking down of existing unserviceable one complete all as specified and as directed.
Supply and fix for PCB (Printed circuit board) of ductable type package/ tower/ split AC suitable for unit 4.0 TR of existing make including taking down of existing unserviceable one complete all as specified and as directed.
Supply and fix for PCB (Printed circuit board) of ductable type package/ tower/split AC suitable for unit 3.0 TR of existing make including taking down of existing unserviceable one complete all as specified and as directed.
Supply and fix for contactor for smooth functioning of control panel including taking down of existing unserviceable one complete all as specified and as directed. Make: Siemens Cat No. 3TF44 or equivalent from L&T. Note :- If Cat No. is revised, equivalent cat No. from latest Catalogue shall be considered.
M&L for leak detection by nitrogen pressure test in refrigerant system for split type AC 1.5 TR capacity, cutting brazing and making leak-proof the gas system, cleaning, vacuum the gas system and charging suitable gas of any type as required on site of quantity to achieve desire cooling complete all as specified an directed. (Note:- Additional gas required will measured & paid separately under relevant item as supply and charging.)
All as per Srl item No. 58 above but for split type AC 2.0 TR Capacity
All as per Srl item No. 58 above but for split type AC 3.0 TR Capacity
All as per Srl item No. 58 above but for split type AC 4.0 TR Capacity
All as per Srl item No. 58 above but for split type AC 5.0 TR Capacity
All as per Srl item No. 58 above but for split type AC 7.5 TR Capacity
M&L for leak detection by nitrogen pressure test in refrigerant system for window type AC 1.5 TR capacity, cutting brazing and making leak-proof the gas system, cleaning, vacuum the gas system and charging suitable gas of any type as required on site of quantity to achieve desire cooling complete all as specified an directed- (Note:- Additional gas required will measured & paid separately under relevant item as supply and charging.)
All as per Srl item No. 64 above but for window type AC 2.0 TR Capacity
M&L for replacement of unsv contactor with control kit of split type AC as per existing make & model up to 3 TR complete all as specified and directed.
Taking out water cooler of any capacity and make, from site for servicing, cleaning of cooling coil, condenser coil and water storage tank, oiling to blower motor, checking of electrical circuit and replacement of defective spare parts such as capacitor, relay, over load protection, blower motors etc, found defective at site as required, testing for smooth functioning etc complete all as directed. Note: Supply only spare parts shall be measured and paid seperately under relevant item.
Supply only for overload protector of SR-2612 to water cooler complete all as specified.
Supply only for starting capacitor 40/60/80/100 MFD for water cooler any type/size complete all as specified.
Supply only for running capacitor 10 to 36 MFD complete for water cooler any type/size complete all as specified and directed.
Supply only for relay for water cooler of any type and capacity as per existing complete all as specified.
M&L for leak detection by nitrogen pressure test in refrigerant system of Refrigerator of any capacity and make, by cutting brazing and making leak-proof the gas system, cleaning, vacuum the gas system and charging suitable gas of any type as required on site quantity to achieve desire cooling complete all as specified an directed. (Note:- Additional gas required will measured & paid separately under relevant item as supply and charging.)
All as per Srl item No. 72 above but for water cooler of any capacity and make.
All as per Srl item No. 72 above but for deep freezer of any capacity and make.
Supply only for electric blower fan motor 1/20 HP 230 volts single phase with 950 RPM suitable for water cooler complete all as specified.
Supply and fix for brass ball valve, 15 mm dia, ISI marked, high pressure with polythelene float (wall thickness of floats is 1.5 mm ) and fly nut complete screwed for iron pipe or brass ferrule and fixed, minimum finished weight 0.28 Kg each ball valve as specified in SSR Part I including taking down of existing unserviceable one complete all as specified and directed.
Supply and fix for push cock of size 15mm bore, chromium plated, cast copper alloy, heavy duty, screwed for iron pipe or for brass ferrule including taking down of existing unserviceable one complete all as specified and as directed.
Supply and fix for thermostat suitable for water cooler of capacity 40 litres to 300 litres for 230 volt 50 Hz AC including taking down of existing unserviceable one complete all as specified and as directed.
Supply and fix for condensing coil suitable for water cooler of capacity 40 litres/ hr cooling capacity as per existing including taking down of existing unserviceable one complete all as specified and as directed.
Supply and fix for condensing coil suitable for water cooler of capacity 60 litres/ hr cooling capacity as per existing including taking down of existing unserviceable one complete all as specified and directed.
Supply and fix for PVC drain out pipe 32 mm dia bore medium grade as per existing including providing necessary GI clamps, nut bolt etc including taking down of existing one complete all as specified and as directed. Make : Prayag/ Supreme/ Prince as approved.
Material and labour for preparation of old steel surfaces by using wire brush/emery paper etc and making the surface smooth and painting to the outer cover/ external surfaces of water cooler with two coats of synthetic enamel paint and re-writing the SM / MES No etc capacity of water cooler 40/ 60 litres/hr complete all as specified and as directed.
Supply and fix for PVC connection of 450mm long, 15mm bore with chromium plated brass check nuts at both side of superior quality including taking down of existing unserviceable one complete all as specified and as directed. Make: Prayag/ Symet/ Polytuff/ Precision Product (Pearl) as approved.
Removing the old unserviceable sealed compressor unit from water cooler of 40/60/80 litres capacity and supply and fixing new hermetically sealed compressor working with non CFC refrigerant including supply and charging of non CFC refrigerant gas and oil to adequate level and testing complete all as specified and as directed. Make of compressor : Shriram/ Kirloskar/ Usha as approved.
Supply and fix for metal plug socket board in sheet metal enclosure along with 20 Amp MCB including taking down of existing unserviceable one complete all as specified and as directed.
Taking out refrigerator of any capacity and make from the site for servicing, cleaning of evaporator coil, condenser coil, vegetable tray, checking the electrical circuit and replacement of unserviceable spare parts like indicator lamp, evaporator coil , relay as required, testing for smooth functioning etc complete all as specified and as directed. Note: Supply only spare parts shall be measured and paid seperately under relevant item.
Supply only for indicator lamp of refrigerator, any watt, thread/ pin type as per site requirement complete all as specified. Make: Bajaj/ Philips/ Surya as approved.
Supply only for evaporator coil for refrigerator of any type and capacity as per existing and complete all as specified.
Supply only for relay suitable for refrigerators of different capacities and makes for smooth functioning of refrigerator as per existing and complete all as specified.
Supply and fix for condensing coil for refrigerator of any type and capacity as per existing including taking down of existing unserviceable one complete all as specified and as directed.
Supply and fix for thermostat for refrigerator of any type and capacity as per existing including taking down of existing unserviceable one complete all as specified and as directed.
Supply and fix for chiller door of approved brand, for refrigerator of any make and capacity 165/180 litres as ordered and suitable for fitted with existing cooling chamber of refrigerator including taking down of existing unserviceable one complete all as specified and as directed.
Supply and fix for chiller door of approved brand, for refrigerator of any make and capacity 220/ 250/ 300/ 310 litres as ordered and suitable for fitted with existing cooling chamber of refrigerator including taking down of existing unserviceavle one complete all as specified and as directed .
Supply and fix for chiller tray of approved quality/ brand suitable for 165/ 180/ 220/ 250/ 300/ 310 litres capacity refrigerator including taking down of existing unserviceable one complete all as specified and as directed.
Supply and fix for vegitable/ fruit tray of approved quality/ brand suitable for 165/ 180/ 220/ 250/ 300/ 310 litres capacity refrigerator including taking down of existing unserviceable one complete all as specified and as directed.
S & F for Magnatic door gasket any make of refrigerator of capacity 165 to 300 ltr including taking down of extg unsv one complete all as specified and directed.
Material and labour for preparation of old steel surfaces by using wire brush/emery paper etc and making the surface smooth by using putty and painting to the outer cover/ external surfaces of refrigerator of capacity 165/ 170/ 200 litres with two coats of synthetic enamel paint and re-writing the SM/ MES No etc complete all as specified and as directed.
Material and labour for preparation of old steel surfaces by using wire brush/ emery paper etc and making the surface smooth by using putty and painting to the outer cover/ external surfaces of refrigerator of capacity 250/ 286/ 300 litres with two coats of synthetic enamel paint and re-writing the SM/ MES No etc complete all as specified and as directed.
Removing the old and unserviceable sealed compressor unit from refrigerator 310/ 300 litres capacity and supply and fixing new hermetically sealed compressor working with non CFC refrigerant including supply and charging of non CFC refrigerent gas as per existing for refrigerator in exchange of defective uncut sealed unit including making connection and oil at adequate level and testing complete all as specified and as directed. Make: As per existing as approved.
Taking out deep freezer of capacity 165/ 200/ 310 litres from the site for servicing, applying one coat of synthetic enamel paint in side, cleaning of evaporator coil and condenser coil, checking the electrical circuit and replacement of unserviceable spare parts thermostat, over load protection, relay, starting capacitor, running capacitor, testing for smooth functioning etc. complete all as specified and as directed. Note: Supply only spare parts shall be measured and paid separately under relevant item.
Supply only for thermostat suitable for deep freezer of capacity 165 litres to 300 litres for 230 volt 50 Hz AC supply complete all as specified.
Supply only for over load protection suitable for deep freezer of capacity 200/ 300/ 310 litres as per existing complete all as specified.
Supply only for relay suitable for deep freezer of any capacity as above as per existing complete all as specified.
Supply only for starting capacitor suitable for deep freezer of any capacity as above complete all as specified.
Supply only for running capacitor suitable for deep freezer of any capacity as above complete all as specified.
Supply and fix for magnetic door gasket any make of deep freezer of capacity 165 to 310 litres including taking down of existing unserviceable one complete all as specified and as directed.
Removing the old and unserviceable sealed compressor unit from deep freezer 310/ 300 litres capacity and supply and fixing new hermetically sealed compressor working with non CFC refrigerant for deep freezer in exchange of defective uncut sealed unit including making connection and supply and charging of non CFC refrigerant gas and oil at adequate level and testing complete all as specified and as directed. Make: Shriram/ Kirloskar/ Usha.
Supply and fix for wood wool pads of desert coolers including taking down of existing unserviceable pads complete all as specified and directed.
Supply and fix for tullu pump 0.6 KW, 1.25 metres head of desert cooler suitable for operation on 230 volt 50 Hz AC supply including taking down of existing unserviceable one complete all as specified and as directed.
Supply and fix for blower motor of 1/8 HP, 1460 RPM for existing desert cooler suitable for operation on 230 volt, 50 Hz, AC supply including taking down of existing unserviceable one complete all as specified and as directed.
Disconnecting of voltage stabilizer any make/ type/ capacity from conneted equipment opening and checking of stabilizer for fault finding and replacement unserviceable parts and reassembling the same after necessary reapair, cleaning and servicing complete all as directed. Note : Supply only spare parts shall be measured and paid separately under relevant item.
Supply only for PCB card suitable for stabilizer 5.0 KVA of make as per existing complete all as specified.
Supply only for transformer suitable for stabilizer 5.0 KVA of make as per existing complete all as specified.
Supply only for PCB card suitable for stabilizer 0.50 KVA of make as per existing complete all as specified and directed.
Supply only for transformer suitable for stabilizer 0.50 KVA of make as per existing complete all as specified.
Material and labour for attending emergent complaints i.e air conditioners any type, water cooler any type, refrigerator any type including carrying out minor repairs including replacing necessary capacitors, thermostat, relays, PCB etc as required to make the system in order/ functional complete all as specified and as directed. Note: Spare parts shall be measured and paid seperately under relevant item. Minor parts deemed to include in cost of item as decided by Engineer-In Charge.
M & L Submain wiring with 2 runs of single core 4 sqmm PVC insulated unsheated multistranded 1100 volts grade with copper conductor drawn through and including PVC casing and capping heavy duty ISI marked and its accessories including one run of single core 4 sqmm PVC insulated unsheated multistranded 1100 volts grade with copper conductor cable as earth continuty conductor along with the wiring and connected from DB to DB/main board including taking down of extg unsv wiring complete all as specified and directed. Note:- Two runs of 4 sqmm cable,one run of 4sqmm cable and one run of PVC casing caping will be measured as one unit
Supply and charging gas R-22 for air conditioner of any type make and capacity (for additional quantity required) complete all as specified and as directed.
Supply and Charging of non CFC refrigerant Gas R -134 to water cooler, refrigerator and deep freezer of any type, make and capacity (for additional quantity required) complete all as specified and as directed.
Supply and charging of non CFC refrigerant Gas R-410/ 32 complete all as specified and as directed.
Material and labour for replacement of rusted, worn out body sheet of water cooler, deep freezer, refrigerator of any type and make by providing mild steel sheet as per existing gauge and thickness with proper cutting, welding drilling, painting to match with existing colour etc, fabrication work complete all as specified and as directed.
Supply and fix for connecting and testing MCCB 4 pole 63 Amps with thermal magnetic release breaking capacity 25 KA in existing LT Panel, suitable for 415 volts, 50 Hz, capacity, Ics = 100% Icu with extended terminals type, interlocked to prevent opening when the Switch is in ON position, including necessary modification in panel board if required to fix the MCCB complete with replacement of burnt lugs and wire/cable pieces etc as required at site for smooth functioning connecting and testing complete including taking down of existing unserviceable all as specified and as directed.
All as per serial item No.122 here-in-before but for 4 pole 100 Amps with thermal magnetic release breaking capacity 25 KA.
All as per serial item No.122 here-in-before but for 4 pole 160 Amps with thermal magnetic release breaking capacity 25 KA.
Note : 1. Rerformance security:- Refer Condition 22 of Special Conditions. 2. Quoted Contract Sum shall be arrived at after deducting the amount of Credit Schedule (refer Schedule of Credit in pdf form for quantity, rate and amount etc.) for old unserviceable materials retrieved from site.
M/s. ANAND ENTERPRISES
M/s Vijay Airconditioning Pvt Ltd
M R ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .