Garrison Engineer North General Cariappa Marg Camp Pune - 411001
GE (N) P/TOKEN- 75 OF 2026-2027 REPAIRS AND MAINTENANCE TO DG SETS AND AMF PANELS ALONGWITH ALLIED WORKS IN THE AOR OF AGE E/M (NORTH) UNDER GE (N) PUNE
2026_MES_799651_1
GE (N) P/TOKEN- 75 OF 2026-2027
Open Tender
Electrical and Maintenance Works
Item Rate
330 days
GE NORTH PUNE
Refer tender documents.
8 documents required · 8 mandatory
₹500
GE NORTH PUNE
₹80,000
Yes
20 Nov 2026
20 Nov 2026
18 Dec 2026
20 Nov 2026
11 Dec 2026
4 Dec 2026
21 Nov 2026 - 26 Nov 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | M&L for routine ‘A’ Check, maintenance and servicing of 380 KVA Diesel Generator Set installed at Southern Command Signal Centre, including connected alternator, engine, control panel, starting system and associated accessories, for ensuring smooth, reliable and trouble-free operation of the DG set, every 50 running hours or one month, whichever is earlier, strictly in accordance with the manufacturer's/OEM recommendations and as directed by the Engineer-in-Charge, complete in all respects.
The ‘A’ Check shall include, but shall not be limited to, the following:
(a) Engine and Lubrication System
General inspection of engine and connected accessories. Check engine oil level and condition and top-up wherever required. Check lubrication system for leakage and proper functioning.
Lubrication/greasing of all applicable moving parts, linkages, joints and other points as recommended by OEM. Check and tighten accessible nuts, bolts, fasteners and connections wherever required.
(b) Fuel System
Check fuel system, fuel lines, hoses, joints and connections for leakage.
Drain accumulated sediment/water from fuel tank as required.
Drain fuel filter/water separator and check for presence of water/sediments.
Check fuel filter condition and replace where required, as per OEM recommendations.
Check fuel tank, fuel lines and associated fittings for proper condition. | 11 | Each month | - | - |
| 1.01 | (c) Air Intake System
Clean pre-cleaner dust pan weekly/as required.
Check air cleaner restriction indicator.
Inspect air cleaner element and clean/change the same as required in accordance with OEM recommendations.
Check air intake piping, hoses, clamps and connections for leakage/damage.
(d) Cooling System
Check radiator coolant level and top-up as required.
Check radiator, coolant hoses, clamps and joints for leakage.
Check radiator fan, fan belt and associated components.
Check and adjust belt tension wherever required.
Clean radiator exterior and remove accumulated dust/dirt affecting cooling efficiency. Check cooling system for proper circulation and abnormal temperature rise.
(e) Starting and Battery System
Check battery condition, terminal connections and electrolyte level, where applicable. Clean and tighten battery terminals and connections. Check battery charging voltage and functioning of battery charger. Check starting motor and starting circuit for proper operation.
(f) Exhaust System
Check exhaust manifold, exhaust piping, flexible connection, silencer and associated joints for leakage/damage.
Check exhaust system supports and clamps and tighten/rectify wherever required.
(g) Alternator and Electrical System
General inspection of alternator and associated electrical connections. Check alternator terminals, cable connections and accessible electrical joints for tightness. Check voltage, frequency, current, kW and power factor during operation. Check alternator for abnormal noise, heating and vibration. Check functioning of control panel, indicating instruments, meters, alarms and protective devices. | - | - | - | - |
| 1.02 | (h) General Checks and Safety
Check and rectify oil, fuel, coolant and other accessible leakages. Check drain tank and drain accumulated liquid wherever required. Check belts, hoses, clamps and flexible connections and adjust/replace as required. Check DG set for abnormal noise, vibration or overheating. Check functioning of emergency stop and other safety/interlocking arrangements.
Clean engine, alternator, control panel and DG set area after completion of maintenance. Check all accessible nuts, bolts, fasteners and mounting arrangements and tighten wherever required.
(i) Operational Testing
After completion of the ‘A’ Check, the DG set shall be started and operated to verify proper functioning. The following parameters shall be checked and recorded:
Engine oil pressure
Coolant temperature
Battery charging voltage
DG output voltage
Frequency
Load current
kW and power factor
Engine RPM
Running hours
Any abnormal noise, vibration, smoke or leakage
The contractor shall maintain a DG Set Periodical Testing/Maintenance Register at site, recording the date, running hours, maintenance carried out, readings/parameters observed, defects noticed and rectification carried out. The register shall be produced to the Engineer-in-Charge and got signed on monthly basis.
Note:
Engine oil and radiator coolant required for top-up/replacement shall be measured and paid separately.
Major spare parts/components costing above ₹300/- per item shall be measured and paid separately.
Minor spare parts/consumables costing up to ₹300/- per item shall be deemed included in the quoted rate for routine ‘A’ Check and maintenance.
All tools, tackles, cleaning materials, lubricants/grease required for routine servicing, stationery, registers and other incidental items necessary for completion of the work shall be deemed included in the quoted rate, unless specifically excluded above.
All works shall be carried out strictly as per OEM/manufacturer's recommendations and as directed by the Engineer-in-Charge.
The DG set shall be left in a clean, safe and fully operational condition after every ‘A’ Check. | - | - | - | - |
| 2 | All as per serial item No.1.00 here-in-before but capacity 250 KVA DG set installed at PCDA Southern Command. | 11 | Each month | - | - |
| 3 | All as per serial item No.1.00 here-in-before but capacity 200 KVA DG set installed at Old Telephone Exchange. | 11 | Each month | - | - |
| 4 | All as per serial item No.1.00 here-in-before but capacity 200 KVA DG set installed at SC Signal Centre. | 11 | Each month | - | - |
| 5 | All as per serial item No.1.00 here-in-before but capacity 200 KVA DG set installed at Sewage Treatment Plant. | 11 | Each month | - | - |
| 6 | All as per serial item No.1.00 here-in-before but capacity 160 KVA DG set installed at PCDA Pump House. | 11 | Each month | - | - |
| 7 | All as per serial item No.1.00 here-in-before but capacity 125 KVA DG set installed at SCOM Pump House. | 11 | Each month | - | - |
| 8 | All as per serial item No.1.00 here-in-before but capacity 125 KVA DG set installed at Star Auditorium. | 11 | Each month | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.30 MB
BOQ_897191.xls
BOQ • 15.12 MB
tenderdoc75.pdf
Tender Documents • 0.83 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .