GE AF KALAIKUNDA
GE (AF) Kalaikunda PO Kalaikunda Air Field Dist Paschim Medinipore St West Bengal Pin 721303
SPECIAL REPAIR TO CERTAIN EARTH PITS, LIGHTENING ARRESTERS AND REPLACEMENT OF UG CABLE AT VARIOUS LOCATION PH-I PROVISON OF GEYSERS, WASH HAND BASIN AND SINK IN CERTAIN SMQs PH-I AND CERTAIN MINOR WORK AT AIR FORCE STATION KALAIKUNDA
2021_MES_474918_1
8704/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AF STN KALAIKUNDA
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE AF KALAIKUNDA
₹8.2 L
16 Dec 2021
13 Sept 2021
13 Oct 2021
13 Sept 2021
12 Oct 2021
29 Sept 2021
Amount
Taking down old unserviceable GI/Copper earth plate from soft and hard soil from any location as directed by Engineer -in- charge.
M&L earthing complete with copper earth plate electrode 600 mm x 600 mm x 3 mm thick burried directly in ground (Earth pit not less than 4 mtr deep below ground level) with top edge of the plate not less than 3.25 mtr below ground level connected to copper strip 20 x 3 mm as earth lead by brass nut bolts washer including brazing the copper strip with copper plate as shown in electrical plate No 3 connected to earth test point including necessary excavation in hard dense soil / disintergate rock, filling charcoal and salt around the plate in layers , filling the pit with low resistivity agriculture soil free from stones, to be bring from out side defence land and mixed with Bentonite , (3 bags of 25 Kg each ), construction of inspection pit ( earth pit chamber) of brick work of size 600 x 600 x 600 mm with PCC copping of 1 :2: 4 , 12.5 mm aggregate A1 with MS sheet 2.8 mm plate cover on frame of angle iron of size 40 x 40 x 5 mm with , wire mess, funnel, test point, 40 mm dia GI protection pipe light grade and 32 mm GI peforated pipe for watering etc complete and testing on completion. The electrode and lead shall be of copper all as specified and directed by Engr-in-charge (Copper strip upto 7.5 RM will be included in the item rate and copper strip beyond 7.5 RM will be measured seperately (Note : (i) Contractor shall use low reistivity fresh agriculture soil , mixed with 3 x Bags of bentonite clay of 25 Kg each for refilling the pit to achive the desired resistance. (ii) copper strip will be laid below 60 cm from ground level and connected to test point through plinth protection (iii) Necessary cost of repair to plinth protection and connected plate and earth continuity conductor by providing 2 x brass nuts bolts and brazing of joints, bringing argiculture soil from out side defence land and cost of 3 x 25 Bags of bentonite deemed to be included in the item rate. (iv) Contractor has to clear the side and disposed off the excavated soil from pit on completion of work. (v) Contractor has to submit test report of earthing after completing the earthing. (vi) Bentonite clay should be Conf to IS 6186: 1986
Taking out old unserviceable GI/aluminium/copper earth strip or for relaying/ refixing the same existing strip by providing procline insulators of any size and type in any height and any location as directed by Engineer In charge.
Supply and fixing copper strip of size 20 x 3 mm as earth continuity conductor or main earthing lead fixed on "V" type porcelain insulator, 4 BM, heavy duty ( ceramic bus bar support insulator off white colour of suitable for mounting strip of 20 mm wide x 3 min thick) saddle to wall, buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 20 x 3 mm copper strip brazing to each joints and connected with by providing brass nut bolts and washer all as specified and directed by Engr in Charge. Note : Insulators to be provided on every 50 cm. (Minimum 2 x insulators to be provided in every 1 x metre of strip)
Supply and fixing copper strip of size 32 x 6 mm as earth continuity conductor or main earthing lead fixed on "V" type porcelain insulator 10 BM heavy duty ( ceramic bus bar support insulator off white colour of min size of 36 mm width x 60 mm length with 36 mm width bus bar mounting base) saddle to wall, buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 20 x 3 mm copper strip brazing to each joints and connected with by providing brass nut bolts and washer all as specified and directed by Engr in Charge.Note : Insulators to be provided on every 50 cm. (Minimum 2 x insulators to be provided in every 1 x metre of strip)
Supply and fixing copper strip of size 50 x 6 mm as earth continuity conductor or main earthing lead fixed on "V" type porcelain insulators, 10 BM heavy duty ( ceramic bus bar support insulator off white colour of min size of (ceramic bus bar support insulator off white colour of min size of 50 mm width x 70 mm length with 50 mm width bus bar mounting base)) saddle to wall, buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for earthing etc. as required 50 x 6 mm copper strip brazing to each joints and connected with by providing brass nut boltsand washer all as specified and directed by Engr in Charge. Note : Insulators to be provided on every 50 cm. (Minimum 2 x insulators to be provided in every 1 x metre of strip)
Supply and fixing aluminium strip of size 25 x 3 mm as earth continuity conductor or main earthing lead fixed on "V" type porcelain insulators, 4 BM, heavy duty ( ceramic bus bar support insulator off white colour of suitable size for mounting strip of 20 mm wide x 3 min thick)) saddle to wall, buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required and connected with by providing brass nut bolts and washer all as specified and directed by Engr in Charge. Note : Insulators to be provided on every 50 cm. (Minimum 2 x insulators to be provided in every 1 x metre of strip)
M & L for Refixing of existing serviceable copper / aluminium / GI strip taken out under item No. 3 above, on top of "V" type procelain insulator ( ceramic bus bar support insulator off white colour of suitable size for mounting of insulator) fixing strip on insulator with brass nuts and bolt ,screws, aluminium cleats etc.( Procelain insulator if replaced shall be measured separetly) duly straightened properly and fixing in neat dressed manner as directed by Engineer in charge. Note : - (i) Proclelain insulator to be measured and paid seperately under relevant item
M& L for porcelin insulater 10 BM heavy duty (ceramic bus bar support insulator off white colour of min size of 50 mm width x 70 mm length with 50 mm width bus bar mounting base for fixing strip of width above 32 mm to 50 mm fixing on wall for supporting the copper strip including suitable size brass nuts and bolts, washers, drilling hole on wall to fix porcelain insulator , fixing insulator by providing steel screws etc complete all as specified and directed by Engineer-in-charge.( Note : Cost of brass nut bolt and washer and steel screw for fixing insulator is deemed to be included in unit rate of item).
M& L for porcelin insulater 4 BM heavy duty (ceramic bus bar support insulator off white colour of min size of 36 mm width x 60 mm length with 36 mm width bus bar mounting base for fixing strip of width up to 32 mm fixing on wall for supporting the copper strip of size 20 x 3 mm and up to 32 mm width including suitable size brass nuts and bolts, washers, drilling hole on wall to fix porcelain insulator , fixing insulator by providing steel screws etc complete all as specified and directed by Engineer-in-charge. ( Note : Cost of brass nut bolt and washer and steel screw for fixing insulator is deemed to be included in unit rate of item).
M&L for carrying out brazing work of copper earth strip joints, after removing the nut bolt, scraping and cleaning the strip surface all as specified by Engr-in-charge. Note : Size of earth strip is 20 x 3 mm to 25 x 3.15 mm
S&F for thermoplastic(polycarbonate) junction box for test point without terminal block of dimension 130 x 180 x 77 mm IP 66 halogen free and weather proof including four hexagonal anticorrosive screws for out door installation including taking down unserviceable one. Make : Hensel- Cat part No. KF 0600 H or as equivalent in Sintex.
M&L in repair for Test point terminal block made of gun metal or phosphorus bronze size 75 x 75 x 25 mm drilled and screwed incl 3 Nos 8mm dia 25mm long hexagonal head screws for fixing strips to test point including necessary fixing arrangement to fix test point terminal block in junction box all as specified and directed. including taking down unserviceable one.
Supply & Fixing hexagonal head brass nut bolt and washer (Bolt size not less than 30 mm long from under side of head to end and not less than 6 mm dia) as specified and directed by Engr-in -charge.
Supply & Fixing hexagonal head brass nut bolt and washer (Bolt size not less than 50 mm long from under side of head to end and not less than 7 mm dia) as specified and directed by Engr-in -charge.
Taking down old broken and damaged earth pit chamber and M & L for construction of new earth pit chamber of brick work with plaster in outer and inner surface , copping of of PCC 1:2:4 Type A-1. Earth pit shall be of size 600 x 600 x 600 mm embedded in ground below GL 150 mm with openable cover made up of MS sheet of minimum 2.8 mm thickness fixed in angle iron frame and handle including GI funnel and wire mesh , including painting the complete pit with two coat of synthetic enamel paint as per colour code all as specified and directed by Engineer-in-charge. Colour to be painted on complete pit to be obtain from Eng in Charge.
M & L GI tubing medium grade 40mm bore for fixing the air termination rods on top of pipe with necessary clamping arrangement .The GI pipe should embedded in PCC bed blocks and tied with Stainless steel wire rope for free stand alone of pipe compete all as directed. Note:- PCC bed blocks shall be measured and paid saperately under relevant item of this schedule.
M&L for PCC (1:3:6), type C-2 (using 40 mm graded stone aggregate) for foundation for pole mass concrete etc including demolition of existing one complete all as specified and directed.
M&L for PCC (1:2:4), type B-1 (using 20 mm graded stone aggregate) for foundation for pole mass concrete etc including demolition of existing one all as specified and directed.
M & L in repair Air termination, single pointed, aluminium rod 12mm dia and 300mm long complete fixed on wall/roof including all fitting and fixing arrangement all as specified and directed..
M & L in repair Air termination, single pointed, copper rod 12mm dia and 300 mm long complete fixed on wall/roof including fixing arrangement all as specified and directed..
Supply and fixing stainless steel wire rope PVC insulated of minimum thickness 6 mm for holding GI pipe of 50/ 40 mm dia to stand straight vertical mounted with lightening arrester spike complete all specified and directed by Engineer -in-charge
Supply and fixing stainless steel wire rope clamp grip for rope clamping 'U' with nut bolts washer etc all as specified and directed by Engineer -in-charge
Supply & laying of UPVC pipe of size 25 mm dia for protection of copper earth strips complete all as specified and directed by Engineer -in-charge
S&F in repairs PVC insulated, Single core flexible copper conductor cable, 1100 Volt, Conf to IS 694, ISI marked of size 70 Sqmm including fixing it on tower of 40 mtr height by providing GI strip clamp and also by using Heavy duty PVC tye from LA at top of tower to earthing pit on ground, and any other locations like on wall or laying on floor by providing saddles, including connecting terminals by providing copper lugs, brass nut and bolt with washer of suitable size as per site requirement to connect the cable including taking down u/s deterioted aluminium complete all as specified and directed by Engineer in Charge. Make : Havells / Polycab/ Finolex.
S & F Brass Copper lightening arrester 9.2 mm diameter and 915 mm in length with 5 spikes and base plate 8.5 x 8.5 cm for building protection coverage of 45 degress from the top point 1.85 m all as specified and directed by Engineer in Charge.
M & L for fabrication of display board for earth pit nos, lacation and periodical test results for power circuit earthing, machinary earthing ,lightening conductor earthing, made of MS sheet 3.0 mm thick sheet, rectangular welding on angle iron of 25 x25 x4 mm of 600 mm height from ground level 30 cm including fixing in PCC 1:2:4 with 20 cm X 20 cm X 20 cm (below ground level) grade aggregate foundation to be carried out at different location technical area/domestic area . Dimention of board shall be 30 cm X 25 cm. or any other dimention not more than 0.075 sq mtr of MS Board The instruction shall be written black painted board in white letters not less than 2 " size for all type of boards complete all as specified and dierected by the Engineer -in-charge including taking down unsv one. Note : (a) All necessary MS sheet, aluminium screws and PCC works etc are deemed to the rate quoted by the contractor (b) The matter to be write on board should be collected from Engineer-in-charge.
Taking down old unserviceable chemical earthing/ pipe earth electrode from soft and hard soil from any location as directed by Engineer -in- charge.
M&L for Advance encapsulated compound based Marconite compound earthing maintenance free , with copper electrode of 88 mm dia (strip in pipe technology upgraded earthing system conforming IS 3043. The outer copper pipe shall be of 80 mm dia and inner copper strip shall be of 25 x 3 mm respectively of 3 mtrs long with terminal size 50 x 6 mm . The annular space between the pipe and strip to be filled up with Compact fill (CF) (Crystalline Conductive) mixture. The job includes excavation of pit in any type of hard dense soil/ disinterigated rocky strata of size 1000 mm x 1000 mm x 3050 mm depth and taking out all excavated soil, lowering and placing copper electrode in centre of pit and filling of back fill marconite compound having excellent moisture retaining capacity in sourrounding of electrode in 200 mm dia all around the electrode( Min 4 bags of 25 Kg each of Marconite back fill compound per pit per unit to be fill).The remaining portion of earth pit to be filled with agriculture soil / back cotton soil free from stones etc to be bring from out side defence land . The earth pit should be provided with a FRP earth pit cover for protection and safe guard of terminals. The material of earth electrode should have good electrical conductivity & anti corrosion property in wide range of soil conditions. The job also include M & L for in PCC(1:2:4) type B1 around the FRP cover for support and foundation and colouring the PCC work with desired colour.complete all as specified and directed.
Make : Copper electrode : True Power Earthing Pvt Ltd. Model No. 88MTPPC ( 3 MTR Long, 88 mm dia) Product code CE -E-003 or equivalent make as approved by GE Back fill compound : Marconite : Product of Carbon International Ltd. UK. "Marconite" electrically conductive aggregate, to be used as backfill to enhance the effect of earth electrode and suitable for rock and all type of ground condition having low resistivity up to 0.001 Ohm meter, inert PH material, Corrosion free green product in bag of 25 Kg each) Note :- (i) Design of earth electrode should be of Strip -in-pipe technology . (ii) Contractor have to submit literature of earth electrode and get the make approved of GE before procurement. (iii) The earth electrode shall be CPRI approved. (iv) Contarctor has to fill pure back fill compound all around the earth electrode in 200 mm bore up to full depth of bore. (v) Copper strip will be laid below 20 cm from ground level and connecting the test point through plinth protection using HDPE pipe for protection, necessary cost of repair to plinth protection and brazing and welding deemed to be included in the item. (vi) Contarctor shall submit the test report of earthing after completing the work of earthing. (vii) Contractor shall remove and disposed off the soil excavated from boring and clear the site before completion of work. (viii) Contractor has to submit the test certificate of electrode and back fill compound before claiming the payment.
Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in soft/ loose soil complete all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in soft/ loose/ hard/ dense soil complete all as specified and as directed.
Removing excavated material (soils) not exceeding 50 m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and as directed.
Supply & spreading in trenches dry river sand cushioning to underground cable in trenches including spreading, levelling hand punning down complete all as specified and directed Note:- Depth of sand cushioning will be measured after punning down and levelling the sand properly.
Material and labour for fly ash brick laid flat in trenches over sand cushioning for cable protection complete all as specified and directed.
Material and labour for 100 mm dia galvanized iron tube Medium grade for cable protection, supporting to poles, plinth protections, road crossing, trenches, footpath etc, including including all fitting clamps, nut, bolt and washers complete all as specified and directed.
Supply, fixing, grouting and painting cable route indicator made up of Factory made Precast RCC slab of size 100 cm x 40 cm x 80 mm thick duly embossed with "MES LT Cable", Size of Cable and grouting on the route of LT cable complete. Note :- (i) Unit rate of item includes excavation, PCC foundation for erection of route indicator. (ii) Slab of route indicate to be provided with min 4 Nos x 8 mm diameters TMT bars along length of slab with 7 Nos cross bar 6 mm dia in reinforcement with shuttering. (iii) Route indicator RCC slab to painting with two coat of red colour synthetic enamel paint over on one coat of white primer base all as specified and directed by Engr - in - Charge.
Horizontal boring of holes, under road/ pavement / hard standing etc.,not exceeding 15 Metres in length, in any type of soil, suitable for passing through 80 to 100 mm bore, galvanised steel tubing,complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade, as per IS 7098 Part - I 1988 with upto latest date ammendments, extruded PVC type ST2 outer sheathed, with stranded aluminium conductor of size 240 sq mm 3.5 core in trench in underground and on wall as per requirement including providing bimetallic (aluminium copper lugs) at end terminations and connecting cable to LT panel , providing MS clamp to fix the cable on wall in protection pipe etc complete all as specified and directed by Engr-in-Charge.
Supply of "Marconite" electrically conductive aggregate, to be used as backfill to enhance the effect of earth electrode and suitable for rock and all type of ground condition having low resistivity up to 0.001 Ohm meter, inert PH material, Corrosion free green product in bag of 25 Kg each. Make : Marconite ® Product of Carbon International Limited UK. Note : Contractor has to submit the test certificate and purchase voucher befor claiming the payment from department.
S&F, Installing and testing, energy efficient, 5 Star BEE rated, Storage water heater (geyser) 25 Ltr capacity, white colour, vertical storage type cylindrical shape, metallic body electrically operated, Single Phase, 230 Volt, 50 Hz, with maximum working presure 8 Kg/cm3, heating element of 2000 watt, having thermostat, Thermal cut off indicator, suitable for hard water, having rated power input of 2000 Watt, including supply and fixing heavy duty Hot and Cold water flexible corrugated SS Connection pipe connection having high temperature resistant EPDM material with SS braiding, having 450 mm long, 15mm dia brass coupler etc, flexible pipe suitable to withstand upto 90 degree Celsius for hot water, Geyser shall having steel inner tank, with feroglas dry power coating for corrosion resistance, tank to withstand high pressure rating upto 8 bar, Incoloy glass coated heating element, Adjustable knob for temperature setting, having Whirflow technology to avoid direct contract between cold and hot water flow for a faster heating and energy saving, CFC free Puff insulation, having heating indicator, having multi function safety valve, including all accessories anchor fastener -04 Nos of suitable size for mounting geyser 3 core PVC insulated, multistranded copper conductor cable for power supply with shock safety plug complete all as specified and directed by Eng in Charge. Make : Havells Model No. Monza or equivalent in USHA / Bajaj /Crompton/JAQUAR
NOTE :- (i) Contract shall submit the brochure of geyser with detail technical specification and take approval of GE before procurement. (ii) All civil work required on site for hanging the geyser and to make good to match the surface as existing to be done by contractor without any extra cost. (iii) All the necessary accessories and T&P require on site for installation of geyser shall be provided by contractor. (iv) Geyser shall have min warranty for inner tank of 7 year and having comprehensive warranty of min 2 years for body and other electrical components and 4 year heating element warranty from certified date of completion by GE. Contract shall submit the manufacturer warranty card to the department. (v) If extra cable (PVC insulated sheated 2.5 Sqmm x 2 core copper conductor) required on site for extension of electric supply connection from Geyser to Metal Plug socket the same (upto 3 mtr) shall be provided by the contractor without any extra cost. (vi) Geyser should have IP x64 technology to protect electrical part from water splash. (vii) The geyser shall have shock safety plug.
S&F, Installing and testing, energy efficient, 5 Star BEE rated, Storage water heater (geyser) 25 Ltr capacity, white colour, vertical storage type cylindrical shape, metallic body electrically operated, Single Phase, 230 Volt, 50 Hz, with maximum working presure 8 Kg/cm3, heating element of 2000 watt, having thermostat, Thermal cut off indicator, suitable for hard water, having rated power input of 2000 Watt, including supply and fixing heavy duty Hot and Cold water flexible corrugated SS Connection pipe connection having high temperature resistant EPDM material with SS braiding, having 450 mm long, 15mm dia brass coupler etc, flexible pipe suitable to withstand upto 90 degree Celsius for hot water, Geyser shall having steel inner tank, with feroglas dry power coating for corrosion resistance, tank to withstand high pressure rating upto 8 bar, Incoloy glass coated heating element, Adjustable knob for temperature setting, having Whirflow technology to avoid direct contract between cold and hot water flow for a faster heating and energy saving, CFC free Puff insulation, having heating indicator, having multi function safety valve, including all accessories anchor fastener -04 Nos of suitable size for mounting geyser 3 core PVC insulated, multistranded copper conductor cable for power supply with shock safety plug including taking down old unserviceable geyser and depositing to MES stores complete all as specified and directed by Eng in Charge. Make : Havells Model No. Monza or equivalent in USHA / Bajaj /Crompton/JAQUAR
NOTE :- (i) Contract shall submit the brochure of geyser with detail technical specification and take approval of GE before procurement. (ii) All civil work required on site for hanging the geyser and to make good to match the surface as existing to be done by contractor without any extra cost. (iii) All the necessary accessories and T&P require on site for installation of geyser shall be provided by contractor. (iv) Geyser shall have min warranty for inner tank of 7 year and having comprehensive warranty of min 2 years for body and other electrical components and 4 year heating element warranty from certified date of completion by GE. Contract shall submit the manufacturer warranty card to the department. (v) If extra cable (PVC insulated sheated 2.5 Sqmm x 2 core copper conductor) required on site for extension of electric supply connection from Geyser to Metal Plug socket the same (upto 3 mtr) shall be provided by the contractor without any extra cost. (vi) Geyser should have IP x64 technology to protect electrical part from water splash. (vii) The geyser shall have shock safety plug. (viii) Contactor has to obtain RV of all deposited geyser from AGE E/M and Same shall be submitted to GE while claiming RAR/FB.
S & F 15 mm nominal size, screw down fancy type stop valves, brass cast copper alloy body and body components with crutch handle, bright finished complete all as specified and as directed.
S&F 15 mm nominal size, screw down bib taps, fancy type choromium plated cast copper alloy body and body components with crutch handle, bright finished complete all as specified and as directed of Make- Parryware / Hindware / Jaquar.
S&F 15 mm nominal size, Fancy pillar taps, CP brass cast copper alloy body and body components with swan necky 18 cm height, left hand operated with screwed shanks and back nut, with or without lettered hot or cold, nickel-chromium plated finish complete completed all as specified and as directed of Make- Parryware / Hindware / Jaquar
S & F 32 mm nominal size, copper alloy, nickel chromium plated finish waste fittings with including silicone sealant complete all as specified and as directed.
Cutting chases in brick walls to ends or edges of landings, steps, cills, sunshades, shelves, lintels, etc.; and cutting chases for concealed water tubing or concealed conduit wiring, etc., not exceeding 10 cm girth and making good the same with cement concrete M15 (Nominal Mix) using 12.5 mm nominal size coarse aggregate or cement mortar 1:3 including necessary plaster and pointing in cement mortar 1:3 complete all as specified and as directed.
S & F in repairs 15 mm nominal size, nonrising spindle type fancy angle stop valves as per IS 8931: 1993 made of cast brass including Knob, knob components, divertor & components, nickel-chromium plated finish complete all as specified and as directed.
S&F flexible (coil shaped) PVC waste pipe for sink and wash basin 32 mm dia with length not less than 700 mm connected to PVC waste fittings complete all as specified and as directed and as directed of Make- Prayag / Shakti.
M & L for PVC connections 15 mm size with PTMT nuts of length 450 mm complete all as specified and as directed.
S&F, sinks with drainage board made of stainless steel 1mm thick, kitchen or laboratory with plugs, washers and wastes including all fittings;and bedding in cement mortar to dwarf wall or including fixing cantilever brackets and connecting union to pipe overall size 950mm x 510mm bowl size 410mm x 410mm x 230mm with complete all as specified and directed.
Supplying & fixing to walls and ceiling 15 mm nominal bore, medium grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed. Note :- Union to be provided on branch line for inlet cold water line on insertion /taking branch line after cutting existing pipe line.
Supplying & fixing to walls and ceiling 20 mm nominal bore, medium grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed.
M & L for cutting existing steel tubing for alterations or additions in position without taking down of pipe complete all as specified and directed (Note cutting of existing pipe to be done for insersation of geyser cold water inlet connection pipe.
M & L for screwing existing steel tubing or alterations or additions in position without taking down of pipe complete all as specified and directed
M & L for point wiring for one 3 pin/ 5 pin 15 Amps socket outlet on independent board complete with and including single core PVC insulated, unsheathed flexible conductor FR-LSH cables 4.00 sqmm as per IS 694: 2010, ISI marked, annealed, multistranded copper conductor drawn through & including heavy mechanical stresses class and -5 temperature class PVC casing/capping of suitable size as required at site including all accessories/ fittings/ junction boxes/ inspection cover etc. ISI marked and sunk terminal boxes flush galvanised metal boxes suitable for fixing with 4.00sqmm copper conductor PVC insulated, unsheathed flexible multistranded copper conductor FR-LSH cable as continuous earth wire connected to metallic body at one end and common earth dolly to other end complete all as specified and as directed.
Supply and fix switch piano, flush button, single pole, one way, 15 Amps, complete all as specified and directed.
M&L socket combined outlet 2 in 1, 3 pin flush type 5 and 15 Amp multi purpose complete all as specified and directed.
Supply and fix concealed sub main wiring complete with and including two Nos single core PVC insulated, unsheathed flexible conductor FR-LSH cables 4 sqmm as per IS 694: 2010, ISI marked, annealed, multistranded copper conductor drawn through and including medium mechanical stresses class PVC conduit as per IS 9537 (Part-III): 1983 of suitable nominal size as required at site dia but not less than 25 mm nominal size including all accessories and fixed on walls and 4.00 sqmm one No single core copper conductor PVC insulated, unsheathed flexible multistranded copper conductor FR-LSH cable for earthing and connected to common earth dolly complete all as specified and directed by Engineer-in-charge. Note - Two runs of 4.00 sqmm cable, one run of 4.00 sqmm cable and one run of conduit will be measured and paid as one unit length. (i) The chases in the wall shall be cut with elect cutter (ii) The disturbed surfaces of wall shall be made good with cement plaster 1:4 including matching the surfaces with as per existing finishes and to the entire satisfaction of Engineer in Charge (iii)Wiring to be done as per approved colour code in IE rule.
Supply and fix concealed sub main wiring complete with and including two Nos single core PVC insulated, unsheathed flexible conductor FR-LSH cables 6 sqmm as per IS 694: 2010, ISI marked, annealed, multistranded copper conductor drawn through and including medium mechanical stresses class PVC conduit as per IS 9537 (Part-III): 1983 of suitable nominal size as required at site dia but not less than 25 mm nominal size including all accessories and fixed on walls and 6.00 sqmm one No single core copper conductor PVC insulated, unsheathed flexible multistranded copper conductor FR-LSH cable for earthing and connected to common earth dolly complete all as specified and directed by Engineer-in-charge. Note - Two runs of 6.00 sqmm cable, one run of 6.00 sqmm cable and one run of conduit will be measured and paid as one unit length. (i) The chases in the wall shall be cut with elect cutter (ii) The disturbed surfaces of wall shall be made good with cement plaster 1:4 including matching the surfaces with as per existing finishes and to the entire satisfaction of Engineer in Charge (iii)Wiring to be done as per approved colour code in IE rule.
Supply and Fixing Sub main wiring with two runs of single core PVC insulated unsheathed cable 1100 volts grade, multistranded copper conductor FRLSH cable of 6.0 Sqmm (with colour code), drawn in but including PVC casing caping not less than 25 mm width, ISI marked, double locking type including one run of PVC insulated unsheathed, multistranded copper conductor FRLSH cable of 6.0 Sqmm (Green colour) as contineous earth conductor cable connected to earth dolly in surface complete all as specified and directed by EIC.
Supply and Fixing Sub main wiring with two runs of single core PVC insulated unsheathed cable 1100 volts grade, multistranded copper conductor FRLSH cable of 4.0 Sqmm (with colour code), drawn in but including PVC casing caping not less than 25 mm width, ISI marked, double locking type including one run of PVC insulated unsheathed, multistranded copper conductor FRLSH cable of 4.0 Sqmm (Green colour) as contineous earth conductor cable connected to earth dolly in surface complete all as specified and directed by EIC.
S & F sheet metal enclosure for MCB, DB, SPN, 240 Volts, 100 amps rated copper busbar, 8 way Double door (with metal) door enclosure made up of CRCA sheet steel, RAL 9003 powder coated, IP 43, IK 09, Conf to IS 8623-1&3 , IEC 61439-3, having Neutral and earth bar , cable ties for cabel management, fully shrouded neutral bar, reversible door option, blanking plate including fixing the DB box flush in wall of any type and making good the distrubed surface to match as the existing with all as specified and directed by Engr-in-charge.
S & F sheet metal enclosure for MCB, DB, SPN, 240 Volts, 100 amps rated copper busbar,4 way Double door (with metal) door enclosure made up of CRCA sheet steel, RAL 9003 powder coated, IP 43, IK 09, Conf to IS 8623-1&3 , IEC 61439-3, having Neutral and earth bar , cable ties for cabel management, fully shrouded neutral bar, reversible door option, blanking plate including fixing the DB box flush in wall of any type and making good the distrubed surface to match as the existing with all as specified and directed by Engr-in-charge. :
S&F DB Box, in sheet metal enclosure VT DB TPN, MCCB DB TPN 6 way, double door with 63 Amp, 25 KA, TP MCCB as incomer (Vertical type double door, 63 Amps, TP, 25 kA MCCB rate inclusive) and suitable for SP/TP DB in outgoing, enclosure made up of CRCA sheet steel, RAL 9003 powder coated, IP 43 IK 09, As Per IEC 61439-3, with 250 Amp copper bus bar for each phase, with 2 Neutral bar, 2 Earth bar and cable ties for cable management, with fully insulated busbar and shrouded neutral bar, reversible door provision, with colour coded interconnecting wire set, providing balnking plate on vacant outlet way including flushing and fixing DB box in neaty in wall completed all as specified and directed by Engr-in-Charge. Make - Legrand Cat Part No. 507746 Model : (Ekinox-3), MCCB 63 Amp Cat No.420043, Model DPX-3 or equivalent in Siemens / Schneider Note (i) MCCB and DB box shall be of same make.
S & F circuit breakers (MCB), single pole (SP), unenclosed, panel board type, screw type terminals for external copper conductors, C-type instantaneous tripping, rated voltage single phase, rated frequency 50 Hz, Rated current 6A to 32 A, Rated Short circuit capacity 10 kA, any type of fixation, Protection IP 20 complete all as specified and as directed.
S & F circuit breakers (MCB), two pole with one protected pole (SPN), unenclosed, panel board type, screw type terminals for external copper conductors, C-type instantaneous tripping, rated voltage single phase, rated frequency 50 Hz, Rated current 6A to 32 A,, Rated Short circuit capacity 10 kA, any type of fixation, Protection IP 20 complete all as specified and as directed.
S & F circuit breakers (MCB), two pole with one protected pole (SPN), unenclosed, panel board type, screw type terminals for external copper conductors, C-type instantaneous tripping, rated voltage single phase, rated frequency 50 Hz, Rated current 40 A,, Rated Short circuit capacity 10 kA, any type of fixation, Protection IP 20 complete all as specified and as directed.
S & F sheet metal enclosure with socket plug top and MCB single pole and neutral enclosure with two pin & earth plug and socket complete with MCB SP 20 Amps 240 volts complete all as specified and as directed.
Taking down cement plaster from brick or concrete surfaces of any description including racking out joints, hacking for key, scrubbing down with water etc complete all as directed.
Dismantling floor, hearth or wall tiling including cement mortar bedding (but not backing), removing serviceable tiles to store and rubbish off the premises
Materials and Labour for rendering 15 mm thick, cement plaster, in cement mortar (1:6) on surface fair face of brickwork in walls and finishing surface even and smooth without using extra cement, complete all as specified and directed.
Material and labour for plastering 15 mm thick (in two coats of 10 mm and 5 mm thick) on fair faces of brick work or concrete surfaces (on vertical surfaces) in cement mortar 1:4 with integral water proofing compound finished even and fair complete all as specified and as directed. Note: - Water proofing compound will be deemed to included in Quoated rates).
Material and Labour for applying two coats of cement-based paint, white or tinted to new plastered surfaces on walls including priming with alkali resistant priming paint and including preparation of surfaces complete all as specified and directed.
M&L for preparation of new plastered or un -plastered from walls, and applying two coats acrylic distemper on walls, over and including a coat of 1 mm thick white wall care putty and a coat of primer as per manufactrer,s instruction complete all as specified and as directed.Make;Berger (Bison)/J&N(Jensolin)/Asain Piants(Tractor) /Nerolac (Beauty)
M&L providing and fixing of false ceiling with powder coated exposed GI grid suspension system (E-grid T-2420 or equivalent of Armstrong having load carrying capacity of 12.5 Kg/M3 with mid span deflection not exceeding 1/360 span with hanger spacing of 1200 mm c/c) consisting of Main Runner 3600 mm long, Cross Tee 1200/600 mm long and Wall Angle. The wall angle shall be fixed on PVC dash fasteners on the perimeter of the wall with steel screws with distance 300 mm c/c. The main runners to be placed @ 1200 mm, the cross tee 1200 mm will be inserted in the pre-cut slots of Main Runner at regular interval of 600 mm to form a modular grid of 1200x600mm. Additional cross tees of 600 mm shall be placed perpendicular to the Cross Tee 1200 mm long to finally form a grid of 600 mm x 600 mm with and including 6 mm thick HSPC (High pressure steam cured) oceanic pre primed, self embossed, textured designer board, water, termite & fire resistant for insulation and acoustic purpose to be placed in the grid system duly suspended with 4 mm dia GI bar hangers fixed with steel dash through fasteners from purlins with butterfly clips (wt 0.007 kg/clip), hold down clips (wt-0.0035 Kg/clip), with provn of light fixture complete all as per manufacturer instructions and as directed. Make Armstrong or equivalent make as mentioned in PS
S & F wash basins with half pedastal , vitreous china, white, flat back, size 550 mm X 400 mm all as per Make Hindware Wash basin Cat. No.: 10091 and Pedastal Cat no. . 11027 with and including cast iron brackets (embedded in wall upto 110 mm depth with and including cement concrete M15 (Nominal Mix) using 20 mm nominal size graded crushed stone aggregate or fixing on wall with and including rawl plug and screws), 32 mm nominal size, copper alloy, nickel chromium plated finish waste fittings, including painting of fittings and brackets, sealing gap between wall and basin with silicone sealant, cutting and making good the walls wherever required and connecting to supply pipes, waste pipes, waste fittings etc. with silicone sealant complete all as specified and as directed.
Materials and Labour for, Digital Non - skid Ceramic tiles, coloured, 7 to 8 mm thick area of each tile exceeding 0.11 sqm but not exceeding 0.18 sqm,conforming to IS 15622, Grade B II, in floors etc., set and jointed in neat cement slurry and pointed in white or coloured cement to match, over and including 15 mm thick screed bed or bedding layer of cement mortar (1:4),complete all as specified and directed.
Materials and Labour for, Digital glazed ceramic coloured tiles, 600 X 300 X 8mm thick, conforming to IS 15622, Grade B III, on vertical surface of wall such as dados,skirting etc, set and jointed in neat cement slurry and pointed in white or colour cement to match over and including 10 mm thick screed bed or bedding layer of cement mortar (1:4), complete all as specified and directed.
Preparation of newly plastered surfaces on walls and applying three coats of white wash complete all as specified and as directed.
Mondal Construction
NATIONAL CONSTRUCTION CO
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .