Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.8 LAccepted-AOC 8 TOWNSHEND ROAD KOLKATA 700025 | KOLKATA | KOLKATA | WEST BENGAL | 700025 | L1 | Accepted-AOC Lowest rate quoted | |
| 2 | L2₹4.8 L+₹1,126 (0.23%)Rejected-Finance A 8 SAKHARAM GANESH DAUSKAR SARANI KOLKATA 700 025 | KOLKATA | KOLKATA | WEST BENGAL | 700025 | L2 | Rejected-Finance Due to higher rate offered. | |
| 3 | L3₹4.9 L+₹14,025 (2.92%)Rejected-Finance B 16 280 KALYANI NADIA 741235 | KALYANI | NADIA | WEST BENGAL | 741235 | L3 | Rejected-Finance Due to higher rate offered. | |
| 4 | L4₹5.0 L+₹23,677 (4.93%)Rejected-Finance 620 DIAMOND HARBOUR ROAD BEHALA INDUSTRIAL ESTATE PLOT NO F A KOLKATA 34 | KOLKATA | WEST BENGAL | L4 | Rejected-Finance Due to higher rate offered. | |
| 5 | L5₹5.6 L+₹75,114 (15.6%)Rejected-Finance 111 M C GARDEN ROAD KOL 30 | KOLKATA | WEST BENGAL | L5 | Rejected-Finance Due to higher rate offered. |
Tender Value
Refer Docs
EMD Value
₹10,000
Closing Date
5 Sept 2018, 12:00 pmClosed
EE II CKHED PWDte
12 CIT RD 1ST FLOOR KOL 14
Construction of Nephrology OPD at Ground floor of OPD Building Under NRSMCH Air conditioning arrangement
2018_WBPWD_188077_1
WBPWD/EE-II/CKHED/NIT-04/ 18-19 (4th call)
Open Tender
A/C ORG
Item Rate
15 days
NRS Medical College and Hospital
As per NIT
4 documents required · 4 mandatory
₹10,000
30 Sept 2020
28 Aug 2018
7 Sept 2018
28 Aug 2018
5 Sept 2018
28 Aug 2018
Amount
Supply 7.5TR capacity concealed type Split Air Conditioner of rated cooling capacity of 90000 BTU/hr. with 3Nos. twin rotary compressor, 3nos. IDU of rated power supply-230V-1ph-50Hz. , 1no. ODU of rated power supply-400V-3ph-50Hz. Air-flow/per IDU:- 1000CFM. ( Make: Hitachi/Mitsubishi-Electric)
Erection & Commissioning Charges for 7.5 TR Air Conditioner
Supply & Charging Refrigerant-22
Copper Refrigeration pipe line for liquid and suction line with fittings, elbows, bends, supports & brackets (Make-Ryoku)
a) Liquid Line (3/8" OD with 0.6 mm thick)
b) Suction Line (5/8" OD with 0.7mm thick)
Supply & Fixing Pipe Insulation in liquid & suction line with 9mm nitrile rubber tube (Accoflex)
a) Liquid Line (3/8" OD with 0.6 mm thick)
b) Suction Line (5/8" OD with 0.7mm thick)
Control copper Cabling from Condensing Unit to control panel (Make: polycab/finolex)
a) 4 core 2.5 sq.mm communication cable
Supply and fixing flexible canvass connection for concealed split air-conditioners.
Supplying, fabrication & fixing M.S u-channel of 6 mm thick of size (75 mm x 40 mm x 40 mm) for making platform for installation of outdoor unit of 7.5 TR Concealed split AC incl. drilling 2 nos holes in each channel including cutting holes into the wall & grouting the same with cement concrete (1:1 ½ :3) etc. fabricated with horizontal angle of 25 mm x 25 mm x 6 mm including supporting angle 50 mm x50mm x 6 mm in each platform in outer edge for transmitting the load centrally through 2Nos. (50 mm x 50 mm x 6 mm) Angle inserted into the exiting wall. The entire structure should be baricated & safe for ODU maintenance. Area of the platform is 3Mtr. x 1.2Mtr.
Supply and fixing of Al powder coated continuous Grill (Make- Premier)
S & L of Drain Water piping work out of PVC / HDPE hard pipes of following sizes incl. fitting, accessories, bends, elbows, tees, flanges, tapings, wall sleeves, hangers, supports, anchors.
a) 25 mm dia
Charges for scaffolding arrangement incl. lifting for outdoor & indoor units
Supplying, fitting & fixing in position suspended boxing for return air arrangement & indoor units of concealed split airconditioner with frame work of aluminium hollow section of size 50mm x25mm (2.0mm thickness) combined with aluminium corners of size 38mm x 25mm, suspended by aluminium hollow tube section of size 38mm x 25mm ,25mm x 25mm powder coated wall angle with aluminium composit panel of thickness 3.0mm comprising of protective film, polyester coating, primer, aluminium coil, adhesive film, polyethylene core again with one layer adhesive film, aluminium bottom coating and finally service coating as per manufacturer's specification finished with aluminium screw and silicon sealent including suitable arrangement for grill fixing complete in all respect as per direction of EIC.
charges for trap door of 1600 mm x 600 mm and 9 mm thickness made of aluminium channel & ply wood for IDU maintenance.
Supply of 2 ton capacity [BEE- 3 Star rated ; ISEER(W/W):- 3.10-3.29] split Air-conditioner machine, Rated Cooling capacity 24000 BTU/Hr fitted with Rotary compressors (Make- OGeneral).
Installation, testing & commissioning of 2 ton capacity split Air-conditioner machine
Supply & laying extra refrigeration Copper pipe with thermal insulation along with other accessories on the surface of wall.
Supplying, fabrication & fixing M.S platform structure made with 50 mm x 50 mm x 6 mm sizes main angle(3 nos. angle of each legth-1.3m & 4 nos. angle of each legth-1m), 50 mm x 50 mm x 6 mm sizes supporting angle(3 nos.) of length 1.3m, 25 mm x 25 mm x 6 mm sizes horizontal cross angle(7 nos.) of each length 2.4m for making platform in respect of placement as well as easy maintenance of outdoor unit of the above-said 2 nos. Hi-wall type split AC including cutting holes into the wall & grouting the same with cement concrete (1:1 ½ :3) etc. as per direction of E.I.C.
Rate should be quoted incl. of all taxes and cess.
MAXCOOL REFRIGERATION CO.
REFRICON
WEATHER MAKERS INDIA
Chatterjee Enterprise
SUPER COOLING AGENCY
P. M. COOLING AND ENGINEERING CO
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .