Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹98.3 LAccepted-AOC 24 A RAGHBIR MARG NEAR 22 NO PHATAK PATIALA 147001 PB | PATIALA | PATIALA | PUNJAB | 147001 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹1.0 Cr+₹2.7 L (2.71%)Rejected-Finance 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | L2 | Rejected-Finance Being L2 | |
| 3 | L3₹1.1 Cr+₹6.5 L (6.55%)Rejected-Finance 195 MAHESH NAGAR AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | L3 | Rejected-Finance Being L3 | |
| 4 | L4₹1.1 Cr+₹11.3 L (11.4%)Rejected-Finance NO 9 BYRAVESHWARA INDUSTRIAL ESTATE ANDRAHALLI MAIN ROAD NEAR PEENYA 2ND STAGE BENGALURU 560 091 | BENGALURU URBAN | KARNATAKA | 560091 | L4 | Rejected-Finance Being L4 | |
| 5 | L5₹1.2 Cr+₹22.2 L (22.4%)Rejected-Finance 26 36 EAST PATEL NAGAR NEW DELHI DELHI 110008 | WEST DELHI | DELHI | 110008 | L5 | Rejected-Finance Being L5 |
| Sl No | Description | Qty | Unit | MAHESH KUMAR SINGLA CONTRACTOR L1 | Vijay Electricals L4 | Raman Electric Trading Co L3 | R D Bansal L2 | JAY BEE Industries L5 |
|---|---|---|---|---|---|---|---|---|
| 1.00 | Taking down carefully existing BER transformer of any cap and size shifting of transformer from any location in cantt area to MES E/M yard complete all as specified and directed. | 7 | Each Job | 3,500 ₹24,500 | 5,000 ₹35,000 | 2,000 ₹14,000 Lowest | 2,000 ₹14,000 Lowest | 21,252.09 ₹1,48,764.62 |
| 2.00 | Supply, installing, testing and commissioning of outdoor type plinth mounted step down transformer, 11 KV/433 Volts (at no load) AC 3 phase 50 Hz, 400 KVA capacity, core type, double copper wound, oil immersed, naturally cooled, Oil Natural-Air Natural (ON AN), with external cooling tubes, delta connected on primary side (HV) and star connected on secondary side (LV) in accordance with vector group DYn-11, Neutral brought out on secondary side (LV side) and having tapings at -7.5% to 7.5% on HV side and to be changed by means of hand operated off load tap changer gear. The maximum temperature rise should not exceed 45 degree celsius in oil and 55 degree celsius in HV/LV winding when measured by resistance method after continuous full load run on an ambient temp of 40 degree celsius. The transformer shall be conforming to EEL-3 as per IS-1180 (Part - I) 2014 with latest ammendment 1,2,3 & 4 having total losses as per EEL -3 and shall comprise of the following:- (a) One cable box on HT side (primary side) consisting of three nos porcelain bushing with copper rods, complete with nuts and washers, with cable glands
(b) One cable box on LT side (Secondary side) consisting of four nos porcelain bushing with copper rods, complete with nuts and washers, with cable glands
(c) Oil conservator with drain valve and oil level guage.
(d) De-hydrating breather with first fill of dehydrating agent (silica gel).
(e) Exhaust vent, air release valve, Thermometer pocket on tank cover, Lifting lugs, Oil filling hole with cap / plug and four nos plain solid cast iron detachable rollers.
(f) One no 100 mm dia, dial type thermometer, vapour pressure type, having range 0-120 degree celsius with metal guard having maximum perimeter temperature reading indicator with re-setting device.
(g) Two earthing terminals on tank cover for earthing of body. (h) Name, Rating and diagram plate.
(j) Extra bushing for neutral, in the LT cable box for providing independent set of earthing for neutral.
(k) First fill of new transformer oil, IS-335 marked, filtered and tested upto 55 KV dielectric strength
(l) Providing adequate size and nos of channels, embeded in floor, for movement of transformer. | 1 | Each | 13,00,000 ₹13,00,000 | 13,50,000 ₹13,50,000 | 12,90,000 ₹12,90,000 | 12,91,000 ₹12,91,000 | 11,63,197.64 ₹11,63,197.64 Lowest |
| 3.00 | -- do-- all as per items No 2 here in befor but 315 KVA | 1 | Each | 10,85,000 ₹10,85,000 | 12,00,000 ₹12,00,000 | 11,30,000 ₹11,30,000 | 11,92,000 ₹11,92,000 | 10,20,808.65 ₹10,20,808.65 Lowest |
| 4.00 | -- do-- all as per items No 2 here in befor but 250 KVA | 3 | Each | 8,55,000 ₹25,65,000 | 10,50,000 ₹31,50,000 | 9,10,000 ₹27,30,000 | 9,40,000 ₹28,20,000 | 8,50,083.54 ₹25,50,250.62 Lowest |
| 5.00 | -- do-- all as per items No 2 here in befor but 200 KVA | 1 | Each | 7,55,000 ₹7,55,000 Lowest | 10,00,000 ₹10,00,000 | 8,70,000 ₹8,70,000 | 8,50,000 ₹8,50,000 | 8,06,870.96 ₹8,06,870.96 |
| 6.00 | -- do-- all as per items No 2 here in befor but 100 KVA | 1 | Each | 5,00,000 ₹5,00,000 Lowest | 6,50,000 ₹6,50,000 | 5,70,000 ₹5,70,000 | 6,25,000 ₹6,25,000 | 5,92,224.87 ₹5,92,224.87 |
| 7.00 | M&L for construction of platform with PCC Block masonry of size 6m x 3m x 1.2 m hight , PCC(1:3:6) type C1 using 20mm graded stone aggregate built in CM 1:4 complete with and including necessary excavation & earth work , PCC 1:4:8 type D-2 as in foundation , rendering 15 mm thick rendering in CM 1:6 on sides and top of the brick work , upto 300 mm below ground level , supply and fixing of 02 Nos MS Channels of size MC 100 for balancing of Transformer embedded in PCC (1:2:4) type B-1 , top surface of plateform shall be provided with 100 mm Thick RCC (1:2:4) type B1 using 20mm graded stone aggregate reinforced with 10 mm steel TMT bar , including provn of steps in one side of plateform and all the outer face of platform shall be given with two coat of white wash, complete all as specified and directed . | 2 | Each Job | 1,97,878 ₹3,95,756 | 50,000 ₹1,00,000 | 75,000 ₹1,50,000 | 49,000 ₹98,000 | 8,500.84 ₹17,001.67 Lowest |
| 8.00 | M&L for earthing complete with galvanized steel earth plate electrode 60cmx60cmx6mm thick burried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of plate not less than 1.5 m deep below normal ground level and connected to and including galvanized iron earth streep 25x4 mm by means of GI welding thimbles, etc as shown in electrical plate No 3 of SSR Part-I and connection to main switch board/Test point/panel/equipment and testing on completion including excavation and earth work in any type of soil, returning filling in, and removal of surplus spoil to a distance not exc 50 metre, charcoal and salt in alternate layer 15 cm thick all around the earth plate electrode, MS funnel with wire mesh, GI pipe medium grade 20 mm bore for watering and 40mm bore upto 7.50 metre long GI pipe light grade for earth wire protection fixed with poles/wall with two clamps, made from MS flat 25 mmx3mm, welding, PCC chamber (1:3:6) type C1, 40mm thick precast RCC cover 1:2:4 type B1 shall be provided on CI frame etc complete including taking down existing u/s earthing and site clearance complete all as specified & as directed. | 28 | Each Set | 4,500 ₹1,26,000 | 4,500 ₹1,26,000 | 4,000 ₹1,12,000 Lowest | 4,500 ₹1,26,000 | 7,863.27 ₹2,20,171.64 |
| 9.00 | Supply, installation, commissioning and testing of LT Panel out door type ,LT 415 Volts, 50 Hz , 3-phase, 4 wire supply, size of LT panel not less than 1.5 m high x 2.5 m width x 0.7 m depth CPRI approved/tested, factory assembled ,out door type, weather and vermin proof (Protection Class IP-54) made out of 3.15 mm (for external) and 2.00 mm (for internal) thick MS Sheet CRCA sheet with both side (front and back) hinged, double door opening for external, rubber lining, locking arrangement, painted internally and externally with powder coating of grey shade (RAL-7032) as per seven tank process complete mounted on angle iron 65mm x 65mm x 6 mm legs 45 cm high above GL and 15 cm embedded in ground with and including blocks of PCC 1:2:4 type C1 of block size 30x30x30 cm comprising of the following. (a) Bus bar chamber having 4 nos air insulated Aluminium strip bus bars of rating not less than the 1.5 times the rated capacity of the incomer ACB/MCCB, bus bar must be colour coded heat shrinkable as well as outgoings shall have aluminium four pole (bus bar) of current carrying capacity not less than 1.5 times the rated capacity of individual MCCBs.:- (a) INCOMING :- (i) ACB 4 pole , LT 415 Volts, 50 Hz AC grade of 800 Amps rating 50 KA rupturing capacitiy with Adjustable Thermal and Fixed Magnetic setting - 01 No. (ii) Voltmeter 0-500 V digital type with 3 way rotary selector switch - 01 No (iii) Ammeter 0-800 Amp digital type with 3 way rotary selector switch - 01 No
(iv) Indicating lamp one set of three (v) CT of suitable size class-1 ISI marked - 01 Set of three (b) OUTGOINGS (i) MCCB 4 pole, 415 Volts, 50 Hz AC, 250 Amps 36 KA rupturing capacitiy with Microprocessor release IPR3+ -8 Nos. (ii) MCCB 4 pole, 415 Volts, 50 Hz AC, 63 Amps 25 KA rupturing capacitiy with Microprocessor release IPR3+ - 1 No.
No. Note:(i) All incoming and outgoing feeder shall be connected by cable through suitable size glands & thimples.(ii) The various feeders shall be indicated by 50mm size letters in synthetic enamel white paint (iii) All MCCB should be connected to Bus bar directly through expended links
Note:(i) All incoming and outgoing feeder shall be connected by cable through suitable size glands & thimples.(ii) The various feeders shall be indicated by 50mm size letters in synthetic enamel white paint (iii) All MCCB should be connected to Bus bar directly through expended links | 2 | Each | 3,00,000 ₹6,00,000 | 2,50,000 ₹5,00,000 Lowest | 5,80,000 ₹11,60,000 | 2,65,000 ₹5,30,000 | 5,58,221.52 ₹11,16,443.05 |
| 10.00 | Supply and laying in replacement, testing and commissioning of HT Underground XLPE insulated, screened PVC bedded galvanized steel strip armoured electric power cable (heavy duty) with aluminium conductor 11 KV grade (Earthed) of sizes3 Core 95 Sqmm cable confirming to IS-7098 Pt-II cable laid in trenches / walls / ducts / poles including taking out the old one complete all as specified and directed. | 300 | RM | 925 ₹2,77,500 Lowest | 1,100 ₹3,30,000 | 1,030 ₹3,09,000 | 1,048 ₹3,14,400 | 1,379.97 ₹4,13,990.68 |
Tender Value
₹1.1 Cr
EMD Value
₹1.8 L
Closing Date
8 Nov 2025, 6:00 pmClosed
COMMANDER WORKS ENGINEER
HQ CWE HISAR, HISAR MIL STN HISAR
SPL REPAIR FOR REPLACEMENT AND RATIONALIZATION OF BER TRANSFORMERS AND ALLIED SERVICES IN HISAR MIL STN UNDER GE HISAR
2025_MES_734646_1
CWE/HSR-52 OF 2025-26
Open Tender
Civil Works
Item Rate
180 days
HISAR
Please refer Tender documents.
7 documents required · 7 mandatory
₹1,000
GE HISAR
₹1.8 L
22 Dec 2025
10 Oct 2025
10 Nov 2025
10 Oct 2025
8 Nov 2025
1 Nov 2025
11 Oct 2025 - 18 Oct 2025
Amount
Taking down carefully existing BER transformer of any cap and size shifting of transformer from any location in cantt area to MES E/M yard complete all as specified and directed.
Supply, installing, testing and commissioning of outdoor type plinth mounted step down transformer, 11 KV/433 Volts (at no load) AC 3 phase 50 Hz, 400 KVA capacity, core type, double copper wound, oil immersed, naturally cooled, Oil Natural-Air Natural (ON AN), with external cooling tubes, delta connected on primary side (HV) and star connected on secondary side (LV) in accordance with vector group DYn-11, Neutral brought out on secondary side (LV side) and having tapings at -7.5% to 7.5% on HV side and to be changed by means of hand operated off load tap changer gear. The maximum temperature rise should not exceed 45 degree celsius in oil and 55 degree celsius in HV/LV winding when measured by resistance method after continuous full load run on an ambient temp of 40 degree celsius. The transformer shall be conforming to EEL-3 as per IS-1180 (Part - I) 2014 with latest ammendment 1,2,3 & 4 having total losses as per EEL -3 and shall comprise of the following:- (a) One cable box on HT side (primary side) consisting of three nos porcelain bushing with copper rods, complete with nuts and washers, with cable glands (b) One cable box on LT side (Secondary side) consisting of four nos porcelain bushing with copper rods, complete with nuts and washers, with cable glands (c) Oil conservator with drain valve and oil level guage. (d) De-hydrating breather with first fill of dehydrating agent (silica gel). (e) Exhaust vent, air release valve, Thermometer pocket on tank cover, Lifting lugs, Oil filling hole with cap / plug and four nos plain solid cast iron detachable rollers. (f) One no 100 mm dia, dial type thermometer, vapour pressure type, having range 0-120 degree celsius with metal guard having maximum perimeter temperature reading indicator with re-setting device. (g) Two earthing terminals on tank cover for earthing of body. (h) Name, Rating and diagram plate. (j) Extra bushing for neutral, in the LT cable box for providing independent set of earthing for neutral. (k) First fill of new transformer oil, IS-335 marked, filtered and tested upto 55 KV dielectric strength (l) Providing adequate size and nos of channels, embeded in floor, for movement of transformer.
-- do-- all as per items No 2 here in befor but 315 KVA
-- do-- all as per items No 2 here in befor but 250 KVA
-- do-- all as per items No 2 here in befor but 200 KVA
-- do-- all as per items No 2 here in befor but 100 KVA
M&L for construction of platform with PCC Block masonry of size 6m x 3m x 1.2 m hight , PCC(1:3:6) type C1 using 20mm graded stone aggregate built in CM 1:4 complete with and including necessary excavation & earth work , PCC 1:4:8 type D-2 as in foundation , rendering 15 mm thick rendering in CM 1:6 on sides and top of the brick work , upto 300 mm below ground level , supply and fixing of 02 Nos MS Channels of size MC 100 for balancing of Transformer embedded in PCC (1:2:4) type B-1 , top surface of plateform shall be provided with 100 mm Thick RCC (1:2:4) type B1 using 20mm graded stone aggregate reinforced with 10 mm steel TMT bar , including provn of steps in one side of plateform and all the outer face of platform shall be given with two coat of white wash, complete all as specified and directed .
M&L for earthing complete with galvanized steel earth plate electrode 60cmx60cmx6mm thick burried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of plate not less than 1.5 m deep below normal ground level and connected to and including galvanized iron earth streep 25x4 mm by means of GI welding thimbles, etc as shown in electrical plate No 3 of SSR Part-I and connection to main switch board/Test point/panel/equipment and testing on completion including excavation and earth work in any type of soil, returning filling in, and removal of surplus spoil to a distance not exc 50 metre, charcoal and salt in alternate layer 15 cm thick all around the earth plate electrode, MS funnel with wire mesh, GI pipe medium grade 20 mm bore for watering and 40mm bore upto 7.50 metre long GI pipe light grade for earth wire protection fixed with poles/wall with two clamps, made from MS flat 25 mmx3mm, welding, PCC chamber (1:3:6) type C1, 40mm thick precast RCC cover 1:2:4 type B1 shall be provided on CI frame etc complete including taking down existing u/s earthing and site clearance complete all as specified & as directed.
Supply and laying in replacement, testing and commissioning of HT Underground XLPE insulated, screened PVC bedded galvanized steel strip armoured electric power cable (heavy duty) with aluminium conductor 11 KV grade (Earthed) of sizes3 Core 95 Sqmm cable confirming to IS-7098 Pt-II cable laid in trenches / walls / ducts / poles including taking out the old one complete all as specified and directed.
All as per Item Sl No 10 above but size of cable 3 Core 120 Sqmm
Disconnecting and taking down HT UG cable from HT pole / Transformer and cutting faulty end portion of the cable, dressing properly and making good end termination, out door type fixed with and including suitable size of heat shrinkable new jointing kit 11000 voltage grade and aluminium lugs duly crimped with crimping tool for HT XLPE cable size 50 sqmm to 95 sqmm.
All as per Item Sl No 12 above but size of cable 120 Sqmm to 185 Sqmm 3 Core
Disconnecting and taking down HT UG cable from HT pole / Transformer and cutting faulty end portion of the cable, dressing properly and making good end termination, indoor type fixed with and including suitable size of heat shrinkable new jointing kit 11000 voltage grade and aluminium lugs duly crimped with crimping tool for HT XLPE cable size 50 sqmm to 95 sqmm.
All as per Item Sl No 14 above but size of cable 120 Sqmm to 185 Sqmm 3 Core
Supply installation, connecting and testing gang operated air break switch, mounted on insulators HT 11KV 200 Amps rating, triple pole, nine/twelve insulator suitable for horizontal mounting fixed and spring loaded revolving tinned brass / copper contacts, galvanized steel base frame, 32 mm bore medium grade pipe Galvanized operating rod (Medium Grade), operating handle, locking arrangement MS clamps, bolts, nuts & washers etc, including drop out fuse assambly triple pole 11 KV including two coats of aluminium paint over a coat of red oxide primer complete all as specified and directed. NOTE :- (i) The rate includes ACSR conductors PVC sleeves, PG clamps and thimbles reqd for jumpers / connections to OH lines of 2 poles / 4 poles structures and outgoings feeders.
M&L for lightning arresters expulsion type complete with all fittings, transmission class discharge capacity 65 Kilo Amps 11000 volts complete including taking down the existing lightening arrestor complete all as specified and directed.
Supply , laying, jointing, testing and commissioning LT underground cable, 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors IS-7098, laid in trenches /fixed on wall /floor /road /culverts /pole or encased in GI pipe of cable size 400 sqmm 3.5 core complete all as specified.
All as per item No 18.00 (here-in-before) but 240 Sqmm 3.5 core.
All as per item No 18.00 (here-in-before) but 185 Sqmm 3.5 core.
All as per item No 18.00 (here-in-before) but 120 Sqmm 3.5 core.
All as per item No 18.00 (here-in-before) but 95 Sqmm 3.5 core.
All as per item No 18.00 (here-in-before) but 35 Sqmm 3.5 core.
Boring of hole under road/pavement/hard standing or any other situation by mannual means and suitable for passing of GI pipe 100 mm bore and making good both ends all specified and directed
Supply and laying double wall corrugated pipe (DWC) in replacement conforming to IS 16098 Part - I of size 180mm outer dia and 152 mm inner dia complete all as specified and as directed
Supply and laying double wall corrugated pipe (DWC) in replacement conforming to IS 16098 Part - I of size 50mm outer dia and 38 mm inner dia complete all as specified and as directed
Excavation in trenches not exc 1.5m wide and not exc 1.5m in depth for laying of cable etc, and for foundation of poles, stays etc. not exc 10sqm on plan and getting out in soft / loose soil complete all as specified and directed.
M&L for Sand cushioning 230mm thickness with dry sand (one layer of 80mm thickness before laying of cable and other layer of 150mm thickness after laying of cable) and punned down to 180mm after laying of cable in trenches for protection of cable complete all as directed. Note :- For the purpose of payment only punned thickness shall be measured.
Taking up PCC cable cover/bricks laid as cable covers and stacking serviceable brick for reuse at site etc complete all as specified and directed.
M&L for brick covering to underground electric cable using sub class ‘B’ bricks, laid dry, flat, perpendicular to the direction of cable etc complete all as specified and directed. .
Supplying and laying un-reinfoced precast concrete cable cover of class HV type 1 with flat size 300 x 180 x 40mm compete all as specified and directed.
M&L for returning filling in approved excavated soil including spreading levelling and well ramming in layers n.exc 25cm thick complete all as specified and directed.
M&L for removing surplus soil to a distance not exceeding 50 m & depositing at a level not exceeding 1.5 m above the starting point complete all as specified and directed.
Demolition of path /concrete in ground floors and pavings (below or above ground level) .complete all as specified and as directed. Note : The rate inclusive of taking down and refixing of any type of cheqered tiles, interlocking tiles complete as per existing to make good.
M/L for cement concrete type B-2, 1:2:4 (40mm graded aggregate) complete all as specified and as directed.
R D Bansal (BID ID -3475190)
Raman Electric Trading Co (BID ID -3474352)
Vijay Electricals (BID ID -3470278)
JAY BEE Industries (BID ID -3469888)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.24 MB
8868tender.pdf
Tender Documents • 1.10 MB
BOQ_822615.xls
BOQ • 2.90 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .