Karnataka Power Transmission Corporation Limited
Kumar
Replacement of existing 22nos 11kv 20/25/26.3kA MCVCB SWG by new 11kV 31.5kA MCVCB SWG at Metagally S/s on PTK basis.
KPTCL/2024-25/EL/WORK_INDENT1440
KPTCL/2024-25/EL/WORK_INDENT1440
Open
Electrical
Two Tender Document System(Two Cover)
KPTCL SEE Works and Mantainance Circle Mysuru
15 documents required · 15 mandatory
Qualification and experience of the key technical and management personnel in permanent employment with the tenderer and those that are proposed to be deployed on this contract, if awarded
Qualifying Requirements for SUB-STATIONS and LINES as per 3.2(b) of ITT of standard tender documents
Minimum Average Annual Turnover (MAAT) of the bidder for best two years out of last preceding five financial years ending on March or December as the case may be, shall not be less than Rs.2.34 Crores as per 3.2(a) of std tender documents(ITT).
Construction equipment owned by the tenderer and equipment proposed to be deployed on this contract, if awarded
Reports on the financial standing of the tenderer, such as profit and loss statements and auditors reports for the last five years as per 3.10(iv) of ITT.
Qualification and experience of the key technical and management personnel in permanent employment with the tenderer and those that are proposed to be deployed on this contract, if awarded as per 3.10(xvi) of ITT.
Even though the Tenderers meet the above criteria, they are subject to be disqualified if they have:- Made misleading or false representations in the forms, statements and attachments submitted in proof of the qualification requirements and/or- Record of poor performance such as abandoning the works, not properly completing the contract, inordinate delays in completion, litigation history, or financial failures etc. and/or- Participated in the previous Tender for the same work and had quoted unreasonably high Tender prices and could not furnish rational justification.
valid Super grade Electrical Contractor License issued by the Government of Karnataka as on the date of opening of techno-commercial bid (refer 2.3 of ITT)
Tenderers who meet the above specified minimum qualifying criteria, will only be qualified, if their available tender capacity is more than the total tender value. The available tender capacity will be calculated as under:Assessed Available Tender Capacity:( AxNx1.5-B)Where A-Maximum value of works executed (KPTCL & Non-KPTCL) in any one year during the last five years (updated to FY 2024-2025) taking into account the completed as well as works in progress.N-Number of years prescribed for completion of the works for which tenders are invited.B-Value, at FY 2024-2025 price level of existing commitments (KPTCL & Non-KPTCL) and on-going works (KPTCL & Non-KPTCL) to be completed during the next 1(One)year.Note:(i)The statements showing the value of existing commitments and on-going works as well as the stipulated period of completion remaining for each of the works listed should be countersigned by the Employer in charge, not below the rank of an Executive Engineer or equivalent.(ii)A self-declaration is to be uploaded by the Tenderer stating that the information with regard to assessed available tender capacity (Works on Hand) furnished are correct.
List of Financial Resources with Certificates
Bidder shall ensure that soft copies of i. Letter of undertaking for Non performance ii. Letter of undertaking for Risk and Cost iii. Letter of undertaking for Litigation iv. Letter of undertaking to source the supply of equipment material from KPTCL approved Vendors only (if applicable) are uploaded besides submitting the Originals to the office of the Superintending Engineer, Electy., Transmission circle, KPTCL, Mysuru, after the last submission date and on or before the date and time of opening of techno commercial bids as per 3.10(xviii) of ITT
Letter of undertaking to source the equipment/material for the work from the approved Vendors who meet the eligibility clauses regarding restrictions on procurement from a country which shares a land border with India (Annexure-XIX) ii. Letter of undertaking as per clause No.1.5 of Annexure-XVIII iii. Letter of undertaking as per clause No.1.6 of Annexure-XVIII (if applicable) are uploaded besides submitting the Originals to the office of the Superintending Engineer, Electy., Transmission circle, KPTCL, Mysuru after the last submission date and on or before the date and time of opening of techno commercial bids.
ESI certificate
Bidder shall upload selfdeclaration stating that no such actions against the bidder haven been taken by KPTCL in the last 6 months as on date of bid submission invoking Risk & cost, failing which the offer is liable to be rejected (refer clause 3.10(ii) of ITT.
Valid EPF Certificate
Clause 3.2b page 5 KW-1,2/3/4a)Mandating satisfactory completion as a prime contractor for atleast one similar work to an extent of 50% of the cost of the work, for all works costing up to and Rs. 100 lakhs.b)Mandating satisfactory completion as a prime contractor for atleast one similar work to an extent of 80% of the cost of the work, for all works costing more than Rs.100 lakhs. The PWG form 65 will be discontinued. The relevant Paragraphs of the KPWD Code will be amended.( Proceedings of the Government of Karnataka & Government order No. FD4 PCL 2008 Bangalore dated 14.10.2008)
As per 3.3(b) of K/W-4, , Each tenderer should further demonstrate Liquid assets and/or availability of credit facilities of no less than Rs.0.33 Crores (Credit lines/letter of credit/certificates from banks for meeting the fund requirements etc.(usually the equivalent of the estimated cash flow for three months in the peak construction period)
Bidder shall ensure that soft copies of Power of Attorney, Letter of Undertaking, No Deviation CERTIFICATE as revised in Annexure , Any other undertaking / agreement (if applicable) are uploaded besides submitting the Originals to the office of the Superintending Engineer Tr circle, Mysore, after the last submission date and on or before the date & time of opening of techno commercial bids.
The bidder should furnish the works on hand details as per 3.10(v) of ITT.
₹3,320
₹2.0 L
15 Nov 2024
15 Nov 2024
2 Dec 2024
22 Nov 2024
22 Nov 2024
Supply-Replacement of existing 22nos 11kv 20/25/26.3kA MCVCB SWG by new 11kV 31.5kA MCVCB SWG at Metagally S/s on PTK basis.
LTAC panel (indoor), 415V as per technical
specification comprising of voltmeter and ammeter, 1 I/C MCCB 200A + 2 nos. 3-Phase 63A O/G SFU, + 2 nos. 3 Phase 32A O/G SFU 100A + 14 O/G SFU, 6 nos. 3 Pha...
DC distribution panel (Indoor) as per technical
specification comprising of earth fault indicator,
indication circuit for AC mains failure, 1 no. 100A
SFU for I/C + 12 nos. 32A SFU for O/G
AC Distribution Box Single front (Outdoor type)
6 Terminal, one I/C of 100A MCCB 20kA + 6 O/G
MCB 16A + 1 O/G of 100A, HRC fuse, complete as
per technical specification
Additional 1CX1000 Sqmm UG Cable Supply and Laying
Additional 3CX240 Sqmm UG Cable Supply and Laying
Copper Plates for connection of 11kV Bushing to UG cable
( Width=76.2m, Thickness=5mm)
Weight of copper/meter = A*B*0.0085
= 3.2385Kg/meter
Total Length required = 40Mtrs = 40*3....
Beam out of Channel 100 x 50 with
arrangements for stringing power conductor on
11 kV side, 1B2 4.00 metre Long (0.038MT)
Fabrication, galvanising and supply of High tensile
steel tower materials
Solid Core Insulator 33kV class (Pedestal Insulator)
For UG Cable support at transformer
Providing burnt bricks to cover on power cable
1X1000 Sqmm heat shrinkable termination kit (Indoor)
1X1000 Sqmm heat shrinkable termination kit (Outdoor)
3X240Sqmm heat shrinkable termination kit (Outdoor)
3X240Sqmm heat shrinkable termination kit (Indoor)
Providing DP Structure with 9 Mtrs RCC Poles
Labour Charges Complete (Including Erection, Excavation & Fixing)
Providing 11 kV GOS - D/B 400 A
Fixing of GOS including wiring (11kV DB 400A)
Providing H-Frame for mounting GOS
Errection of H Frame.
9 kV, 10 kA Lightning Arrestor (Metal oxide type)
Fixing of 3 Nos lightning arrestors including wiring.
Pad Clamps-Coyote ACSR
Coyote ACSR Conductor
4core 10sqmm copper control cable
4core x 2.5sqmm Copper Control cable
19 core x 2.5sqmm Copper Control cable (New Cable)
4core x 6sqmm Copper Control cable (New Cable)
Grounding of equipments by providing cast iron pipe of 100mm ID 13mm thickness, 2.75 Mtrs long with 2 part clamp out of G.I.Flat 50X6mm continuously welded alround the pipe using cast iron welding ele...
Releasing and Re Fixing of Grounding of equipments by providing cast iron pipe of 100mm ID 13mm thickness, 2.75 Mtrs long with 2 part clamp out of G.I.Flat 50X6mm continuously welded alround the pipe ...
Supplying and laying of MS flats of various sizes, welding and applying ACB paint to welded portion and covering with sodium bentonite clay, as per the drawing/standard specifications and consolidatio...
Multi Function Transducers(MFT)(For SCADA REINTEGRATION Purpose)
As per KPTCL Std, Interface: RS-485 Daisy Chain to RTU Com port,wiring: Both 3ph 4wire, supply: self powered, Measuring range voltage: ...
Opto Coupler(For SCADA REINTEGRATION Purpose)
Input Vtg:110V DC, input indicated by LED, input range 110VDC to 140V DC, sourcing Vtg output 48VDC, No of iputs: 12, No of outputs: 8, Source current: 5m...
Terminal Blocks (knife type)(For SCADA REINTEGRATION Purpose)
(8 TB's per Feeder) = (8x1 nos = 8)
Current Cable (For SCADA REINTEGRATION Purpose)-2.5 Sq-mm multistrand copper wire for CT termination (Each color 15mtrs-R-Y-B) (15mts x 3 x 1 feeder = 45mtr)
Voltage Cable(For SCADA REINTEGRATION Purpose) - 2.5 Sq-mm multistrand copper wire for PT termination
(Each color 5mtrs-R-Y-B-N)
(5mts x 4 x 1 feeder = 20mtr)
Control Cable(For SCADA REINTEGRATION Purpose) - 10 Copper core x 1.5sqmm
(From remote contol desk to RTU)
(17mtrs x 12 nos = 204 mtrs)
Signal Cable(For SCADA REINTEGRATION Purpose) - 10 Copper core x 0.5sqmm
Feeder to Feeder loop = 05mts x 1 nos =05 mtrs)
Remote control desk to RTU (for DI):17mtrs x 12 Nos =204 mtrs
RTU to B1&B2+Fee...
1.5 Sqmm Grey wire for interfacing of DI and DO(For SCADA REINTEGRATION Purpose)
(20 mtrs for each panel)(20x23=460mtr)
Supplying tinned copper lugs and crimping and wiring to terminal point for wire of the size 2.5 sqmm
(80 lugs/panel x 23 = 1840)(For SCADA REINTEGRATION Purpose)
C-type channel of size 50x100x50x6mm
(50cm/panel) = (0.5m x 1 nos = 0.5 Mtrs)(For SCADA REINTEGRATION Purpose)
Supplying and fixing of heavy duty cable glands suitable for UG cable of 1.1 KV class (metal only)
(Size: 32mm dia)(For SCADA REINTEGRATION Purpose)
CT TB's - 6 nos for each panel
(1 x 6 = 6 nos)(For SCADA REINTEGRATION Purpose)
Annunciation panel: 2I/C+12F+1BC for each bank with remote wireless Announciator panel
Erection-Replacement of existing 22nos 11kv 20/25/26.3kA MCVCB SWG by new 11kV 31.5kA MCVCB SWG at Metagally S/s on PTK basis.
Supply :- 11 kV MCVCB, 500 MVA, 31.5 kA, 2000 A
Incomer Panel (Scada Compatible)
Erection :-Erection, alignment and fixing to the foundation, indoor/outdoor 11 kV switchgear panel/unit including movem...
Supply :- 11 kV MCVCB, 500 MVA, 31.5 kA, 1600A
Feeder Panel (Scada Compatible)
Erection :-Erection, alignment and fixing to the foundation, indoor/outdoor 11 kV switchgear panel/unit including movemen...
11 kV MCVCB, 500 MVA, 31.5 kA, 2000 A incomer 1600 A feeder(Scada Compaitable)Bus Coupler
Announciation Panel:- 2I/c+12F+1BC
For Each Bank with Remote wirless Annouciator Panel
LTAC panel (indoor), 415V as per technical
specification comprising of voltmeter and ammeter, 1 I/C MCCB 200A + 2 nos. 3-Phase 63A O/G SFU, + 2 nos. 3 Phase 32A O/G SFU 100A + 14 O/G SFU, 6 nos. 3 Pha...
DC distribution panel (Indoor) as per technical
specification comprising of earth fault indicator,
indication circuit for AC mains failure, 1 no. 100A
SFU for I/C + 12 nos. 32A SFU for O/G
AC Distribution Box Single front (Outdoor type)
6 Terminal, one I/C of 100A MCCB 20kA + 6 O/G
MCB 16A + 1 O/G of 100A, HRC fuse, complete as
per technical specification
Releasing and re-errection of 66kV C&R Panels
(20MVA TR-1 & TR-2, RTCC Panels)
Releasing and re erection of Battery charger
Additional 1CX1000 Sqmm UG Cable Supply and Laying
Releasing & Relaying of 3CX240 Sqmm 11kV XLPE UG Cable
Additional 3CX240 Sqmm UG Cable Supply and Laying
Releasing & Relaying of 3CX400 Sqmm 11kV XLPE UG Cable
Copper Plates for connection of 11kV Bushing to UG cable
( Width=76.2m, Thickness=5mm)
Weight of copper/meter = A*B*0.0085
= 3.2385Kg/meter
Total Length required = 40Mtrs = 40*3....
Beam out of Channel 100 x 50 with
arrangements for stringing power conductor on
11 kV side, 1B2 4.00 metre Long (0.038MT)
Fabrication, galvanising and supply of High tensile
steel tower materials
Solid Core Insulator 33kV class (Pedestal Insulator)
For UG Cable support at transformer
Labour charges for spreading of Brick below and above the UG cable. (for this mazdoor labour per day is considered 4 mazdoor labour x 2 days)
Providing M-Sand : Supplying and filling in plinth,
foundations / UG cable work with approved M-sand including watering, ramming, consolidating and dressing. The rate includes the cost of material, la...
Earth work excavation for pipelines/cables by Manual means upto 600 mm trench width, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights...
1X1000 Sqmm heat shrinkable termination kit (Indoor)
1X1000 Sqmm heat shrinkable termination kit (Outdoor)
3X240Sqmm heat shrinkable termination kit (Outdoor)
3X240Sqmm heat shrinkable termination kit (Indoor)
Providing DP Structure with 9 Mtrs RCC Poles
Labour Charges Complete (Including Erection, Excavation & Fixing)
a Base concreting 1:2:4, 650x650x150 mm
b Pole concreting 1:2:4, 650x650x1700 mm
c Coping 1:2:4 (as per actuals)
Providing 11 kV GOS - D/B 400 A
Fixing of GOS including wiring (11kV DB 400A)
Providing H-Frame for mounting GOS
Errection of H Frame.
9 kV, 10 kA Lightning Arrestor (Metal oxide type)
Fixing of 3 Nos lightning arrestors including wiring
4core x 10sqmm Copper Control cable
4core x 2.5sqmm Copper Control cable
19 core x 2.5sqmm Copper Control cable (New Cable)
4core x 6sqmm Copper Control cable (New Cable)
Supply and fixing of
2.5,4,6 sqmm lugs and ferrules for Copper Control cable
25mm Glands for Copper Control cable
19mm Glands for Copper Control cable
Grounding of equipments by providing cast iron pipe of 100mm ID 13mm thickness, 2.75 Mtrs long with 2 part clamp out of G.I.Flat 50X6mm continuously welded alround the pipe using cast iron welding ele...
Releasing and Re Fixing of Grounding of equipments by providing cast iron pipe of 100mm ID 13mm thickness, 2.75 Mtrs long with 2 part clamp out of G.I.Flat 50X6mm continuously welded alround the pipe ...
Grounding of equipment with 50 x 6 mm G.I. Flat and connecting Equipment to the earthmat/ground pit. Each point of earthing with all formation works like bending, twisting, drilling of holes and conne...
Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution li...
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations and other similar works etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by r...
Supplying & Providing 450 mm dia 450mm height 1.5" to 2" thick hume pipe collar (non pressure type) for earth pits including all lead and lifts etc.,
(5nos for deep bore earthing)
Providing nameplates and painting for earth elecrodes, hiring charges for welding machine for welding,cutting and drilling.
Multi Function Transducers(MFT)(For SCADA REINTEGRATION Purpose)
As per KPTCL Std, Interface: RS-485 Daisy Chain to RTU Com port,wiring: Both 3ph 4wire, supply: self powered, Measuring range voltage: ...
Control Cable(For SCADA REINTEGRATION Purpose) - 10 Copper core x 1.5sqmm
(From remote contol desk to RTU)
(17mtrs x 12 nos = 204 mtrs)
Signal Cable(For SCADA REINTEGRATION Purpose) - 10 Copper core x 0.5sqmm
Feeder to Feeder loop = 05mts x 1 nos =05 mtrs)
Remote control desk to RTU (for DI):17mtrs x 12 Nos =204 mtrs
RTU to B1&B2+Fee...
1.5 Sqmm Grey wire for interfacing of DI and DO(For SCADA REINTEGRATION Purpose)
(20 mtrs for each panel)(20x23=460mtr)
CT TB's - 6 nos for each panel
(1 x 6 = 6 nos)(For SCADA REINTEGRATION Purpose)
Miscellaneous items like, Ferrules, cable ties, insulation tape, & Labour for cutting, weldind, drilling, etc(For SCADA REINTEGRATION Purpose)
Configuration of RTU and Engineering along with validation of data at SLDC(For SCADA REINTEGRATION Purpose)
Opto Coupler(For SCADA REINTEGRATION Purpose)
Input Vtg:110V DC, input indicated by LED, input range 110VDC to 140V DC, sourcing Vtg output 48VDC, No of iputs: 12, No of outputs: 8, Source current: 5m...
Testing-Replacement of existing 22nos 11kv 20/25/26.3kA MCVCB SWG by new 11kV 31.5kA MCVCB SWG at Metagally S/s on PTK basis.
wiring, testing & commissioning of 11 kV MCVCB, 500 MVA, 31.5 kA, 2000 A
Incomer Panel (Scada Compatible) 2I/C, 20 feeder panel, 1 bus coupler and 2nos of remote wireless announciation panel for each ...
LTAC panel (indoor), 415V as per technical
specification comprising of voltmeter and ammeter, 1 I/C MCCB 200A + 2 nos. 3-Phase 63A O/G SFU, + 2 nos. 3 Phase 32A O/G SFU 100A + 14 O/G SFU, 6 nos. 3 Pha...
DC distribution panel (Indoor) as per technical
specification comprising of earth fault indicator,
indication circuit for AC mains failure, 1 no. 100A
SFU for I/C + 12 nos. 32A SFU for O/G
AC Distribution Box Single front (Outdoor type)
6 Terminal, one I/C of 100A MCCB 20kA + 6 O/G
MCB 16A + 1 O/G of 100A, HRC fuse, complete as
per technical specification
Decommission-Replacement of existing 22nos 11kv 20/25/26.3kA MCVCB SWG by new 11kV 31.5kA MCVCB SWG at Metagally S/s on PTK basis.
Decomissioning of existing 11kV Indoor / Outdoor Switchgear.
De- wiring 11kV Indoor/Outdoor Switchgear
Decomissioning of existing Announciation Panel
De- wiring of existing Announciation Panel
Dismantling of existing old type ACDB
Dismantling of existing old type DCDB
Releasing of various sizes of 11kV UG Cable
Releasing of various sizes of control cables
Loading of 11 kV Switchgears, ACDB, DCDB & UG Cable
(Loading at Metagalli S/s)
Unloading of 11 kV Switchgears, ACDB & DCDB
(Unloading at KPTCL store, Hootagally)
Transportation of released Breakers etc from 66/11kV Metatagally S/s to Divisional Major works store, Hootagalli Mysore.
Civil-Replacement of existing 22nos 11kv 20/25/26.3kA MCVCB SWG by new 11kV 31.5kA MCVCB SWG at Metagally S/s on PTK basis.
Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution li...
Earth work in surface excavation by mechanical means for lowering & leveling the ground for all works other than foundation in all kinds of soils & upto depth not exceeding 300mm as per drawing and te...
Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes...
Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with supe...
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations and other similar works etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by r...
Removal of Unserviceable Soil with Disposal upto a suitable distance as directed by the Engineer incharge of work
Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes...
Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/tra...
Steel Fabrication: Supplying, fitting and placing TMT FE 550 / 550D Steel Reinforcement including cost of all materials, machinery, labour, cleaning, straightening, cutting, bending, hooking, laping/w...
Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/tra...
Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with supe...
Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direct...
Fencing with G.I. barbed wire Angle iron post placed at required distance embedded in cement concrete blocks, every 15th post, last but one end post and corner post shall be strutted on both sides and...
Providing Size Stone masonry with hard stone in foundation & plinth with Cement mortar 1:6 (1 cement : 6 coarse sand)
Clearing and grubbing road land including uprooting rank vegetation, grass, bushes, shrubs, saplings and trees girth up to 300 mm, removal of stumps of trees cut earlier and disposal of unserviceable ...
Providing Flush/ Ruled pointing: Pointing on stone work with cement mortar 1:3 (1 cement : 3 fine sand) after raking joints to depth nicely lining, including cost of materials, labour, curing as per s...
Jelly Spreading (20-25 mm) : Supplying and providing jelly in the station yard of uniform thickness of 100 mm including the cost of materials, labour charges, required tools and plants etc., complete....
Grounding of equipment with 50 x 6 mm G.I. Flat and connecting equipment to the earthmat/ground pit. Each point of earthing with all formation works like bending, twisting,
drilling of holes and conne...
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
4.Qualifying requirements-metagally.docx
Tender Document • 0.04 MB
1. NIT- metagally doc.docx
Tender Document • 0.02 MB
7.Vol II A Tech Spec NH.zip
Tender Document • 19.58 MB
6. CIVIL Tech specs NH.doc
Tender Document • 0.18 MB
2. Tender documents-metagally.docx
Tender Document • 0.41 MB
5. Work on Hand details (Tender).doc
Tender Document • 0.15 MB
3.Annexure.doc
Others - annexure • 0.19 MB
8.Vol II B CNH.zip
Tender Document • 0.53 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .