Loading…
Loading…
Tender Value
Refer Docs
EMD Value
₹76,300
Closing Date
5 Jan 2026, 3:00 pmClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
Above/Below/Par
Electrical work in connection with the work of "Upgradation of infrastructure facility at SDH at Kanpur".
ELG-132-2526~NCR
ELG-132-2526
Open
Works - General
6 Months
Prayagraj, Uttar Pradesh
₹0
₹76,300
5 Jan 2026
13 Dec 2025
22 Dec 2025
62 items across 1 schedule · ₹38,14,344.59 total
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| 1 | Wiring for circuit / sub main wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/recessed PVC conduit as required. 2 x 4 sq. mm+ 1 x 4 sq. mm earth wire | Metre | 600.00 | 198.12 | 1,18,872 |
| 2 | Wiring for circuit / sub main wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/recessed PVC conduit as required. 2 x 6 sq. mm+ 1 x 6 sq. mm earth wire. | Metre | 1500.00 | 243.1 | 3,64,650 |
| 3 | Wiring for light/power plug with 2x4 sq.mm FRLS PVC insulated copper conductor single core cable insurface/recessed medium class PVC conduit, along with 1 No. 4 sq.mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. | Point | 2000.00 | 195.25 | 3,90,500 |
| 4 | Supply, Erection, Testing and Commissioning of following Modular Type switch 10 A (1- way) complete in all respect. Inspection by- Consignee. | Numbers | 450.00 | 62.06 | 27,927 |
| 5 | Supply, Erection, Testing and Commissioning of following Modular type Plug socket outlet 2/3 Pin 10 A complete in all respect. Inspection by- Consignee. | Numbers | 350.00 | 102.61 | 35,913.5 |
| 6 | Supply, Erection, Testing and Commissioning of following Modular Type switch 20 A (1- way) complete in all respect. Inspection by- Consignee. | Numbers | 100.00 | 126.62 | 12,662 |
| 7 | Supply, Erection, Testing and Commissioning of following Modular type Plug socket outlet 5/3 Pin 20 A complete in all respect. Inspection by- Consignee. | Numbers | 100.00 | 146.46 | 14,646 |
| 8 | Supply and Erection of Modular type switch blanking set to fill the blank space White finished mounting cover plate complete in all respect. Inspection by-Consignee. | Numbers | 30.00 | 7.51 | 225.3 |
| 9 | Supply and Erection of white finish single mounting cover plate with base frame suitable 3 module suitable for mounting of Modular type piano switches/ plug Socket, fan regulator and connection to wiring. Inspection by-Consignee. | Numbers | 100.00 | 66.2 | 6,620 |
| 10 | Supply and Erection of white finish single mounting cover plate with base frame suitable 8 module suitable for mounting of Modular type piano switches/ plug Socket, fan regulator and connection to wiring. Inspection by-Consignee. | Numbers | 100.00 | 139.85 | 13,985 |
| 11 | Supply and Erection of white finish single mounting cover plate with base frame suitable 12 module suitable for mounting of Modular type piano switches/ plug Socket, fan regulator and connection to wiring. Inspection by-Consignee. | Numbers | 80.00 | 201.91 | 16,152.8 |
| 12 | Supply and Erection of Modular Metal boxes concealed Boards suitable for mounting of 3 module white finish single mounting cover plate with Frame and Modular type piano switches/ plug Socket, fan regulators. Metal board boxes are to be concealed in wall. Inspection by-Consignee. | Numbers | 100.00 | 43.43 | 4,343 |
| 13 | Supply and Erection of Modular Metal boxes concealed Boards suitable for mounting of 8 module white finish single mounting cover plate with Frame and Modular type piano switches/ plug Socket, fan regulators. Metal board boxes are to be concealed in wall. Inspection by-Consignee. | Numbers | 100.00 | 76.14 | 7,614 |
| 14 | Supply and Erection of Modular Metal boxes concealed Boards suitable for mounting of 12 module white finish single mounting cover plate with Frame and Modular type piano switches/ plug Socket, fan regulators. Metal board boxes are to be concealed in wall. Inspection by-Consignee. | Numbers | 50.00 | 122.47 | 6,123.5 |
| 15 | Supply and Installation of Ceiling rose 3 plate as per IS No. 371/1999 (Latest Version) including connections, Testing and commissioning as per Tech. Specification. Inspection by-Consignee. | Numbers | 500.00 | 14.44 | 7,220 |
| 16 | Fabrication, Supply and Fixing of Fan Hook with clamp duly painted madeof 50x6 mm MS Flat with nut bolts suitable to fix on PP shelter bracing angle as required. Inspection by-Consignee. | Numbers | 10.00 | 103.72 | 1,037.2 |
| 17 | Supply and Erection of Fan Box cover POP typecomplete in all respect including hardware material for fixing. Inspection by-Consignee. | Numbers | 50.00 | 10.26 | 513 |
| 18 | Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. Inspection by- Consignee. | Numbers | 50.00 | 2,208.91 | 1,10,445.5 |
| 19 | Termination of LT XLPE cables of various sizes (One Job means all 4 cores of cables). Inspection by- Consignee. | Numbers | 10.00 | 111.69 | 1,116.9 |
| 20 | Supply and laying of B class, 50 mm dia, GI pipe of for cable riser/road crossing as required and as per relevant technical specification. Inspection by-Consignee. | Numbers | 20.00 | 115.9 | 2,318 |
| 21 | Supply, erection, testing and commissioning of One phase distribution board comprising of one no. 32/40 amps DP MCB with 40 A ELCB/RCCB as incoming and 4 nos. 10 amps SP MCB , 4 nos. 20 A SP MCB as outgoing complete with copper bus bars, neutral link and other accessories housed in CRCA sheet enclosure with double door type. Inspection by-Consignee. | Numbers | 10.00 | 3,184.95 | 31,849.5 |
| 22 | Drilling of bituminous road/track and laying charges of cable in road crossing for laying 110 mm dia HDPE pipe through it. | Metre | 100.00 | 274.81 | 27,481 |
| 23 | Supply and laying of HDPE Pipes (Upto PN 8.0 Pressure Rating Material Grade: PE 63, Pressure Rating: PN 8.0, Nominal Dia(mm): 110) as per IS-4984:2016 suitable for HT/LT XLPE cable & as required and as per relevant technical specification. Inspection by-Consignee. | Metre | 100.00 | 247.32 | 24,732 |
| 24 | Collecting, Transporting from SSE/PS/ store to site, laying, testing, and commissioning of above LT cable . Laying direct in ground (Including excavation, sand cushioning, protection brick covering and refilling the trench etc.), direct in RCC/Metal pipes in rod/track crossings and on surface/required in wall/in concrete floor by cutting recessed and finished originally as required as per relevant technical specifications. | Metre | 1000.00 | 63.91 | 63,910 |
| 25 | Supply, fixing, testing, connecting and commissioning of 300 mm sweep Exhaust Fan suitable for 230 volts, 50 Hz AC supply, 1400 RPM heavy duty with wiring and flexible PVC pipe as required. Inspection by- Consignee. | Numbers | 10.00 | 1,565.53 | 15,655.3 |
| 26 | Supply, replacement, fixing, testing, connecting and commissioning of energy efficient luminaries complete with all accessries of capacity 18/20 watt, 4 feet length, T8 LED lamps with sutable current control driver circuit ,suitable for surface/recessed mounting.LED Luminaries:-(1) A complete LED lighting unit consisting of a light source and potted driver together with parts of distribute light,to position and protect the light source,and to connect the light source to a branch circuit.The light source itself may be an LED array and LED module, or an LED lamp. (2):-Supplied LED luminaries shall confirm to IS:16101(2012) IS :16106(2012) .Light Source (LED) in the Luminaries should be of make:- (1):-NICHIA/ CREE/OSRAM/ SEOUL/ PHILIPS/LUMILEDS /LEDNIUM. (2):-LEDs to IS: 16105(2012). IS:16108(2012), IEC:62471.1.Input operating voltage :- 105-295 V AC. 2:-Normal Voltage-220V AC.3.Driver type: constant current driver with short circuit protection(For tube light). 4.Control of distribution:-Full cut off. 5.Drive component :Industrial grade only .6.Efficiency of driver electronic: > 85% (For tube light).7.Colour temperature:5000-6500K(For tube light). 8.Colour rendering index(CRI):>75(For tube light). 9.Ingress protection :IP-20. 10.Lumen output: >100 lumens/[email protected] drive current(For tube light). 11.Power factor:->0.90(For tube light). 12.Total hormonics distrotion(THD):-<20% (For tube light). 13. Lamp cover :Acrylic cover which does not result in loss of lumens. 14. Finishing:Power coated /Anodized. 15.Secondry optics:poly corbonate reflector/ poly carbonate lens. 16. Construction of housing: extruded aluminum/CRCA/Pressure die cast aluminum. 17.Mounting :Suitable for surface mounting/recessed mounting. 18. Certificate: Firm to submit LM80(In respect of LED used) & LM79 (In respect of luminare used) test certificate from National/International accredited Laboratory and OEM certificate for complience of BIS/IEC. 19.Warranty:Firm to submit warranty certificate for five year along with the supply.All fittings shall be fitted as surface mounting/recessed mounting with twisted twin flexible cord of minimum size 16/0.2 mm copper conductor as per relevant technical specification. Materials praMtrs.s must remain unchanged during entire warranty period. 1x18/20 watt. Inspection by- Consignee. | Numbers | 100.00 | 313.49 | 31,349 |
| 27 | Supply, fixing, testing, connecting and commissioning of 24/36 watt 2x2 LED lights fittings as per IS:10322 , recess LED Fitting 24/36 watt, suitable for surface/ recessed mounting. LED Luminaries:-(1) A complete LED lighting unit consisting of a light source and driver together with parts of distribute light, to position and protect the light source, and to connect the light source to a branch circuit.The light source it self may be an LED array and LED module, or an LED lamp.(2):-Supplied LED luminaries shall confirm to IS:16101(2012) IS :16106 (2012). Light Source (LED) in the Luminaries should be of make:- (1):-NICHIA/CREE/ OSRAM/ SEOUL /PHILIPS / LUMILEDS /LEDNIUM. (2):-LEDs to IS:16105(2012). IS: 16108(2012), IEC:62471. 1. Input operating voltage :- 105-295 V AC.2:-Normal Voltage-220 VAC. 3. Driver type: constant current driver with short circuit protection. 4.Control of distribution:- Full cut off. 5. Lumens-2880/4320 . 6. Efficiency of driver electronic: > 85%. 7. Colour temperature:4000K. 8.Colour rendering index (CRI):>75. 9. Ingress protection : IP-20. 10.Lumen output: >=120 lumens/ watt @ Max. 350 mA drive current. 11. Power factor:->0.97. 12. Total harmonics distortion (THD):-<20%. 13.Lamp cover :Acrylic cover whichdoes not result in loss of lumens. 14. Finishing: Power coated/Anodized. 15. Secondry optics: poly carbonate reflector/ poly carbonate lens. 16. Construction of housing: extruded aluminum/ CRCA/Pressure die cast aluminum. 17. Mounting: Suitable for surface mounting/ recessed mounting. 18. Certificate:Firm to submit LM80 (In respect of LED used) & LM79 (In respect of luminare used) test certificate from National/International accredited Laboratory and OEM certificate for complience of BIS/IEC. 19. Warranty: Firm to submit warranty certificate for five year along with the supply. All fittings shall be fitted as surface mounting/recessed mounting with twisted twin flexible cord of minimum size 16/0.2 mm copper conductor as per relevant technical specification. Material parameters must remain unchanged during entire warranty period. Inspection by-Consignee. | Numbers | 50.00 | 1,474.65 | 73,732.5 |
| 28 | Supply, fixing, testing, connecting and commissioning of wall mounted Bracket Fan 400 mm sweep including supply of M.S. fixing clamps & its hardware with flexible copper cable twin twisted size 24/0.20 01 mtr long for each fittings as required. Inspection by-Consignee. | Numbers | 20.00 | 1,438.62 | 28,772.4 |
| 29 | Supply, erection, testing and commissioning of single earth electrode of 50 mm. dia 4000 mm long GI pipe class B complete with earth box with CI cover hinged to CI frame including connection from earth electrode to MDB/SDB/poles/with 8 swg GI wire/strip as per attached drawing. Inspection by-Consignee. | Numbers | 10.00 | 2,563.18 | 25,631.8 |
| 30 | "Variable Refrigerant flow system" Supply, Installation, testing and commissioning of modular type variable refrigerant flow air conditioning system suitable for both heating and cooling with Inverter Scroll Compressor suitable for 415±10% V for outdoor unit including fully charged with refrigerant R410A suitable to operate at-5° to 52 C ambient temperature to outdoor unit and all running refrigerant pipe. It shall include anti vibration isolator pad for outdoors unit. The unit shall be complete in all respect as per site requirement. The unit shall have auto phase corrector so that unit can work in case of phase reversal and accumulator should be present in outdoor units to prevent liquid back flow in compressor. 16 HP VRF/VRV OUTDOOR UNIT (Cooling & Heating ). Inspection by- Consignee. | Numbers | 1.00 | 4,10,981.04 | 4,10,981.04 |
| 31 | "Variable Refrigerant flow system "Supply, Installation, testing and commissioning of modular type variable refrigerant flow air conditioning system suitable for both heating and cooling with Inverter Scroll Compressor suitable for 415 ±10% V for outdoor unit including fully charged with refrigerant R410A suitable to operate at -5° to 52 C ambient temperature to outdoor unit . It shall include anti vibration isolator pad for outdoors unit. The unit shall be complete in all respect as per site requirement. The unit shall have auto phase corrector so that unit can work in case of phase reversal and accumulator should be present in outdoor units to prevent liquid back flow in compressor. 12 HP VRF/VRV OUTDOOR UNIT (Cooling & Heating). Inspection by- Consignee. | Numbers | 1.00 | 2,58,674.32 | 2,58,674.32 |
| 32 | Supply, installation, testing and commissioning of MS fabricated outdoor unit stand for placing outdoor unit of VRV system. The stand shall be manufactured from MS C channel of minimum 3-4 mm thick. It shall be finished with enamel paint as per client/architect approval. Inspection by- Consignee. | Numbers | 2.00 | 3,369.56 | 6,739.12 |
| 33 | Supply, fixing, testing and commissioning of 63 A 300 mA 4 pole RCCB complete with box complete as per IS, IE rules and site requirement. Inspection by- Consignee. | Numbers | 2.00 | 3,390.36 | 6,780.72 |
| 34 | "INDOOR UNITS"Supply, Installation, testing, commissioning, Loading, Unloading of the indoor unit. Unit shall be complete in all respect and suitable for 230 ±5% volts and suitable for both heating and cooling option, include wired thermostat having a display showing temperature and control of temperature inside the room. Indoor unit shall include hanging arrangement of the unit with necessary supporting rod, nut & bolts, fasteners and accessories for complete installation of Indoor unit. User shall be able to adjust the temperature as per their comfort level requirement. The units shall be compatible with BMS system in open protocol with MODBUS/BACnet. Supply, installation, testing & commissioning of Hi Wall units 2.0 Tr. Inspection by- Consignee. | Numbers | 8.00 | 36,826.32 | 2,94,610.56 |
| 35 | Supply, installation, testing & commissioning of T- joints and headers etc. Inspection by- Consignee. | Numbers | 10.00 | 4,815.97 | 48,159.7 |
| 36 | Supply & testing of Cordless Remote Controls. Inspection by- Consignee. | Numbers | 10.00 | 4,136.64 | 41,366.4 |
| 37 | Supply & testing of Cordless receiver for indoor units. Inspection by- Consignee. | Numbers | 10.00 | 4,079.65 | 40,796.5 |
| 38 | Supply, laying, testing & commissioning of Communication cable (1.5 sqmm x 2 Core). Inspection by- Consignee. | Numbers | 80.00 | 161.01 | 12,880.8 |
| 39 | Supply of Refrigerant (R410a) charge to the outdoor unit and connected pipes between outdoor unit and AHU as per site requirement. Inspection by- Consignee. | Kg | 8.00 | 891.01 | 7,128.08 |
| 40 | "CONDENSATE DRAIN UPVC PIPE" Supply, installation, testing and commissioning of uPVC Pipe, complete with fittings, supports, U trap arrangement, Clean Plug and accessories for AHU/IDU as per site requirement. 40 mm dia (with 9mm Nitrile). Inspection by- Consignee. | Metre | 25.00 | 218.01 | 5,450.25 |
| 41 | "REFRIGERANT PIPING" Supplying, laying/ fixing, testing and commissioning of following nominal sizes of inter connecting refrigerant piping duly insulated with AL foiled closed cell polyethylene foam insulation (XLPE) of 30 (+/-3) kg/m3 density and fire rated Class 1 as per BS 476 Part 7. All the refrigerant pipe in outside exposed area shall be provided with 26 G aluminium cladding as per site requirement. The insulation shall be provided with protective coating. All piping inside the room shall be properly supported with MS hanger/tie rod. 28.6 mm O.D (wall Thickness-1.0 mm) (insulation : 19 mm). Inspection by- Consignee. | Metre | 35.00 | 1,290.84 | 45,179.4 |
| 42 | "REFRIGERANT PIPING" Supplying, laying/ fixing, testing and commissioning of following nominal sizes of inter connecting refrigerant piping duly insulated with AL foiled closed cell polyethylene foam insulation (XLPE) of 30 (+/-3) kg/m3 density and fire rated Class 1 as per BS 476 Part 7. All the refrigerant pipe in outside exposed area shall be provided with 26 G aluminium cladding as per site requirement. The insulation shall be provided with protective coating. All piping inside the room shall be properly supported with MS hanger/tie rod. 22.2 mm O.D (wall Thickness-1.0 mm) (insulation : 19 mm). Inspection by- Consignee. | Metre | 35.00 | 1,066.49 | 37,327.15 |
| 43 | "REFRIGERANT PIPING" Supplying, laying/ fixing, testing and commissioning of following nominal sizes of inter connecting refrigerant piping duly insulated with AL foiled closed cell polyethylene foam insulation (XLPE) of 30 (+/-3) kg/m3 density and fire rated Class 1 as per BS 476 Part 7. All the refrigerant pipe in outside exposed area shall be provided with 26 G aluminium cladding as per site requirement. The insulation shall be provided with protective coating. All piping inside the room shall be properly supported with MS hanger/tie rod. 19.5 mm O.D (wall Thickness-1.0 mm) (insulation : 19 mm). Inspection by- Consignee. | Metre | 40.00 | 807.79 | 32,311.6 |
| 44 | "REFRIGERANT PIPING" Supplying, laying/ fixing, testing and commissioning of following nominal sizes of inter connecting refrigerant piping duly insulated with AL foiled closed cell polyethylene foam insulation (XLPE) of 30 (+/-3) kg/m3 density and fire rated Class 1 as per BS 476 Part 7. All the refrigerant pipe in outside exposed area shall be provided with 26 G aluminium cladding as per site requirement. The insulation shall be provided with protective coating. All piping inside the room shall be properly supported with MS hanger/tie rod. 15.9 mm O.D (wall Thickness-1.0 mm) (insulation : 13 mm). Inspection by- Consignee. | Metre | 65.00 | 736.32 | 47,860.8 |
| 45 | "REFRIGERANT PIPING" Supplying, laying/ fixing, testing and commissioning of following nominal sizes of inter connecting refrigerant piping duly insulated with AL foiled closed cell polyethylene foam insulation (XLPE) of 30 (+/-3) kg/m3 density and fire rated Class 1 as per BS 476 Part 7. All the refrigerant pipe in outside exposed area shall be provided with 26 G aluminium cladding as per site requirement. The insulation shall be provided with protective coating. All piping inside the room shall be properly supported with MS hanger/tie rod. 12.7 mm O.D (wall Thickness-1.0 mm) (insulation : 13 mm). Inspection by- Consignee. | Metre | 70.00 | 531 | 37,170 |
| 46 | "REFRIGERANT PIPING" Supplying, laying/ fixing, testing and commissioning of following nominal sizes of inter connecting refrigerant piping duly insulated with AL foiled closed cell polyethylene foam insulation (XLPE) of 30 (+/-3) kg/m3 density and fire rated Class 1 as per BS 476 Part 7. All the refrigerant pipe in outside exposed area shall be provided with 26 G aluminium cladding as per site requirement. The insulation shall be provided with protective coating. All piping inside the room shall be properly supported with MS hanger/tie rod. 9.5 mm O.D (wall Thickness-1.0 mm) (insulation : 13 mm). Inspection by- Consignee. | Metre | 70.00 | 463.15 | 32,420.5 |
| 47 | "REFRIGERANT PIPING" Supplying, laying/ fixing, testing and commissioning of following nominal sizes of inter connecting refrigerant piping duly insulated with AL foiled closed cell polyethylene foam insulation (XLPE) of 30 (+/-3) kg/m3 density and fire rated Class 1 as per BS 476 Part 7. All the refrigerant pipe in outside exposed area shall be provided with 26 G aluminium cladding as per site requirement. The insulation shall be provided with protective coating. All piping inside the room shall be properly supported with MS hanger/tie rod. 6.35 mm O.D (wall Thickness-1.0 mm) (insulation : 13 mm). Inspection by- Consignee. | Metre | 70.00 | 408.87 | 28,620.9 |
| 48 | "CABLE TRAY FOR REFRIGERANT PIPING" Supplying and installing of following size of perforated hot dip galvanized G.I cable tray with perforations joined with connectors, suspended from ceiling with G.I suspenders including bolts and nuts, etc. for carrying refrigerant pipe in outdoor application as required. 300 mm width x 75 mm depth x 1.6 mm thickness. Inspection by- Consignee. | Metre | 12.00 | 1,469.04 | 17,628.48 |
| 49 | Supply, fixing, testing and commissioning of 4Cx16 sq.mm. size copper armoured cable complete conforming to IS:7098 (Part-1 & 2), 1988. Laying, testing and commissioning of LT PVC /XLPE 1.1 KV armored power cable in ground/ under the road/ under the track/ on pole/ in existing GI pipe/ Hume pipe etc. including excavation sand cushioning etc. shall be as per tech specification at Tech Spec-I attached or latest, IS & IE rule. Note: - All cable connection shall be made with proper size of crimping socket/ glands etc by the contractor at his own cost and labour. Road/ floor where cable is to be laid shall be made good as original by the firm at his own cost and labour to the satisfaction of Railway representative. The cable shall be fixed on wall/ pole with suitable size of GI clamps.Inspection by- Consignee. | Metre | 100.00 | 581.64 | 58,164 |
| 50 | Supply of PVC insulated flexible copper cable 4Cx2.5 sq.mm. complete as per relevant IS, IE rules. Inspection by- Consignee. | Metre | 100.00 | 88.65 | 8,865 |
| 51 | Supply of PVC insulated flexible copper cable 3Cx2.5 sq.mm. complete as per relevant IS, IE rules. Inspection by- Consignee. | Metre | 100.00 | 90.45 | 9,045 |
| 52 | "Supply, Installation, testing, commissioning, Loading, Unloading of the indoor unit. Unit shall be complete in all respect and suitable for 230 ± 5% volts and suitable for both heating and cooling option, include wired thermostat having a display showing temperature and control of temperature inside the room. Indoor unit shall include hanging arrangement of the unit with necessary supporting rod, nut & bolts, fastners and accessories for complete installation of Indoor unit as per site requirement. User shall be able to adjust the temperature as per their comfort level requirement. The units shall be compatible with BMS system in open protocol with MODBUS/BACnet. Supply, installation, testing & commissioning of 1 - Way Cassette Unit with Drain Pump 2.0 Tr.". Inspection by-RITES. | Numbers | 8.00 | 72,215.81 | 5,77,726.48 |
| 53 | Supply and installation of 1-phase 5 KVA, 120/96 Volt DC input UPS as per IS 16242/ IEC-62040 with Battery Bank of 12V, 10 Nos. tubular batteries having each capacity 150 AH for Emergency Supply. Inspection by-Consignee. | Numbers | 1.00 | 1,22,110.8 | 1,22,110.8 |
| 54 | Supply, fixing, testing and commissioning of 250 mm sweep fresh air fan complete to Explanatory Note. Inspection by-Consignee. | Numbers | 10.00 | 1,041.12 | 10,411.2 |
| 55 | Design, Manufacturing, Supply, Erection, testing and commissioning of LT switchgear panel board of 02 mm Tk. Dia pressed CRS steel sheet panel shall be treated for anti corrosion treatment and finished with smoke gray paint as per technical specification no. Sr.DEE/G/ALD/Panel-94/113 Comprising with as under:-........MCCB of 400 A, 36 kA Standard breaking capacity, 415 volt, 3 Phase 4 Pole current rating 400 Amp. | Numbers | 1.00 | 14,761.41 | 14,761.41 |
| 56 | MCCB of 125A, 36 kA Standard breaking capacity, 415 volt, 3 Phase 4 Pole currentrating 125 Amp. | Numbers | 2.00 | 6,423.54 | 12,847.08 |
| 57 | MCCB of 63A, 36 kA Standard breaking capacity, 415 volt, 3 Phase 4 Pole current rating 63 Amp. | Numbers | 4.00 | 3,114.3 | 12,457.2 |
| 58 | Supply of Indicator lamps with suitable holder. | Numbers | 24.00 | 78.87 | 1,892.88 |
| 59 | Supply, fixing, testing, connecting and commissioning of Outgoing/Feeder Panel Mounted Multi-function Mtrs. with Accuracy Class 1 as per IEC 62053-21 or Class 0.5, 0.5S as per IEC 62053-22.LED Mtrs. Cl 1 with RS485: Mtrs. should have following features built-in LED • Flush mounting 96 x 96 mm • True RMS measurement • Password protection provision for security • Site selectable for 3 Phase 4 wire, 3 Phase 3 wire, 1 Phase, CT Secondary 1A/5A, Universal Auxiliary Supply 80-300 VAC/DC, Input Voltage Measurement 50-500 VAC, 64 samples/ cycle The Mtrs. should be able to read/display following paraMtrs.s Instantaneous ParaMtrs.s (V1, V2, V3, V12, V23, V31, Avg (VLN, VLL), A1, A2, A3, Aavg, F, PF-1, PF-2, PF-3, PF (Avg) W1, W2, W3, W (total) VA1, VA2, VA3, VA (total) Cumulative ParaMtrs.s (Import Wh, Import Vah, Import load hours, Reset (old) Cumulative paraMtrs.s (Import Wh, Import load hours, Communication (RS485 Modus RTU).complete with all accessories. | Numbers | 7.00 | 2,500.87 | 17,506.09 |
| 60 | Fabrication works and insulated Aluminum bus bars of 800A capacity for phases & 800A capacity for neutral Bus bar shall be suitably insulated with heat shrinkable sleeves/ epoxy coating/insulating tap to withstand the test voltage of 2.5 KV Copper strip for connection outgoing as well as incoming with suitable size be provided. Item no. 55 to 60 Inspection by- Consignee. | Numbers | 1.00 | 44,706.74 | 44,706.74 |
| 61 | Supply, fixing, testing and commissioning of wall mounted LT distribution board made up of steel sheet, phosphatised powder painted complete with neutral link,earth point, Din rail and prewired confirming to IS:13032 & 8623:1991 withfollowing items to be fixed in distribution board, confirming to IS:8828 :1996 orlatest, IE rules and site requirement. 4P, MCCB 125 Amps. 10 kA 'C' series= 01 No.(Incoming) DP RCCB (25, 40 Amps., three nos. each) 10 kA 'C' series = 06 Nos.(Outgoing). Inspection by- Consignee. | Numbers | 1.00 | 25,425.66 | 25,425.66 |
| 62 | Supply, fixing, testing and commissioning of wall mounted LT distribution board made up of steel sheet, phosphatised powder painted complete with neutral link,earth point, Din rail and prewired confirming to IS:13032 & 8623:1991 with following items to be fixed in distribution board, confirming to IS:8828 :1996 orlatest, IE rules and site requirement. 4P, MCCB 125 Amps. 10 kA 'C' series= 01 No.(Incoming) DP RCCB (40 & 63 Amps., two nos. each) 10 kA 'C' series = 04 Nos.(Outgoing). Inspection by- Consignee. | Numbers | 1.00 | 20,340.53 | 20,340.53 |
| Schedule total | ₹38,14,344.59 | ||||
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .