Executive Engineer MHD, Srinagar
office of Executive Engineer MHD, Srinagar
Shifting of Boiler from LD Hospital to Govt. Super Specialty Hospital for Heating purposes during winter months , installation and functioning thereof
2024_PWDJK_264294_1
MHDS/TS /2024-25/117/e-tendering, Dated 12 -11-2024
Open Tender
Machineries/ Mechanical Engg Items
Item Wise
3 days
super specilaity hospital srinagar
as detailed in the NIT
3 documents required · 3 mandatory
₹200
Executive Engineer MHD SGR
₹7,740
20 Nov 2024
12 Nov 2024
18 Nov 2024
12 Nov 2024
18 Nov 2024
12 Nov 2024
Amount
Shifting of 06 Lac Kcal/hr capacity Hot Water Generator along with allied piping system and accessories to Govt. Superspeciality Hospital Srinagar. The job comprises of removal of soil and brick debris and laying of removed debris in paving pathway leading to stationed boiler site by means of excavator/crawler loader. The job includes lifting of all the dis-assembled components of the plant viz. NRV's, Supply/return pipe headers, piping/ connection systems,feed and circulation pump, electrical control panels, cabling etc manually as well as by employing pick and carry crane for loading and transporting of the same by means of suitable mechanical transport to the designated location from Govt.LD Hospital . The job further includes pick and carry unloading of the components, followed by suitable placement of the HWG at designated location.
Site preparation within the plant which includes removal of stacked old part of prevously executed mechanical works and other materials and storing them a a designated location. Any debris collected is to be dumped out side the municipal limits. All tools/tackles, transportation etc to be arranged by the contractor.
Creation of staff chamber frames in existing plant room by way of Providing and fixing powder coated aluminium work (minimum thickness of powder coating 50 micron) consisting of tee/ angle sections, of approved make conforming to IS: 733 in frames of false ceiling including aluminium angle cleats with necessary C.P. brass/ stainless steel sunk screws, aluminium perimeter angles fixed to wall with stainless steel rawl plugs @ 450 mm centre to centre and fixing the frame work to G.I. level adjusting hangers 6 mm dia. with necessary cadmium plated machine screws all complete as per approved architectural drawings and direction of the Engineer-in-charge (leveladjusting hangers, ceiling cleats and expansion hold fasteners.
Providing and fixing glazing in aluminum door, window, ventilator shutters and partitions etc. to the chamber aluminium framework with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer in-charge. (Cost of aluminum snap beading shall be paid in basic item.) With float glass panes of 5.0 mm thickness (weight not less than 12.50 kg / sqm)
Providing and laying of 25 mm dia PVC conduit alongwith all bends and other 2 fixtures
Providing and fitting of 100 mm Deep Junction for lighting
Providing and fixing of Lighting points inclusive of copper wire 1 sqmm,ON/OFF switch 5Amp along with require capacity of MCB to be fitted distribution box, all electric fittings, protective devices and accessories, 12Watt LED light of reputed make
Providing and fixing of three pin socket inclusive of copper wire 1 sqmm, ON/OFF sitch 5Amp all electric fittings, protective devices and accessories, of reputed make
Providing and fixing of Heating points inclusive of copper wire 2.5 sqmm, ON/OFF switch 16 Amp along with require capacity of MCB to be fitted in distribution box, all electric fittings, protective devices and accessories.
Providing and fixing of 100W High mast flood lights for plant room illumination, shall inclusive of copper wire 1.5 sqmm /OFF 16A Single pole MCCB switch along with enclosures
Providing and fixing of metallic distribution box (8-way) along with the cost of 32A capacity DP and other necessary fittings as shall be required at the site
Electrification of HWG control panel to main panel by way of connecting A wire alongwith replacement of faulty 4 pole 63A MCCB (2 Nos) in main control panel, Providing & fixing of DOL starter having following specifications: Phase 3-phase, Thermal Over Load Protector: Yes, Power Supply 20-32 A Power Rating: 14.9 KW, Motor Power 20 hp in place of damaged starter. The job further includes electrification of burner panel to HWG panel alongwith replacement of faulty contactors and overload relays with current rating 9-13A (2 Nos.)
Opening of Thermax Make AMW06 Hot Water Generator. Dismounting of the burner gun assembly, removing the front plate coil from it by employing chain pulley block. The job involves thoroughly removing soot and carbon deposits from shell and coil by using wire brush, scrapers and blower etc. The inside of the coil shall be cleaned by circulating through it a solution of de-scaling compound, sulphamic acid powder of Thermax Make (approx . 25 Kg) and water continuously for 24 hr with the help of pump while maintaining a PH of 1-2. The solution is to be circulated from tank/barrel/trays. All consumable items viz. Brushes, detergent, diesel/kerosene oil, dhoti cloth etc. required shall be provided by the executing agency. The HWG shall then be reassembled, tested and commissioned after overhauling. The job includes replacement of all seals, gaskets, asbestos rope, asbestos felt, asbestos sheet, defective nuts, bolts etc. as required .The tools and tackles required for the job and any other consumables shall be provided by the contractor.
Replacement of Refractory of Thermax Make AMW06 Hot water Generator. The job includes complete removal of old/damaged refractory and thorough cleaning of refractory surfaces/bases. Angle Iron hooks/holdfasts shall be firmly welded to the refractory base wherever necessary and collar of the top plate shall be repaired if required. Refractory shall be laid in "fire Crete Super' brand castible cement.
Front Plate Refractory
Back plate refractory
Servicing of 15 HP circulation water pump/s by way of removing/dismantling of the pump assembly followed by checking of impeller, diffuser rings, bushes bearing, and mechanical water seal for complete water leakage seal. All faulty components viz. impeller, diffuser rings, bushes bearing, and mechanical water seal should be replaced by the firm. The pump/s should be reassembled and sealed back with packings for mounting into the central heating circuitry followed by testing and commissioning
Servicing of 5 HP feed water pump/s by way of removing/dismantling of the pump assembly followed by checking of impeller, diffuser rings, bushes bearing, and mechanical water seal for complete water leakage seal. All faulty components viz. impeller, diffuser rings, bushes bearing, and mechanical water seal should be replaced by the firm. faulty components should be replaced by the firm. The pump/s should be reassembled and sealed back with packings for mounting into the central heating circuitry followed by testing and commissioning.
Replacement of damaged inlet/oulet EDPM fuel pipe hoses PN 16 rated in all four HWGs (03 hoses in each) of the hot water system including dismantling of the damaged inlet/outlet pipe connections of the radiators and then providing/fitting of new 304 Grade Stainless Steel cladded EDPM pipe with washer and nuts other necessary fittings including Ball valves, elbows, Tees, Unions, Adapters, etc. to make the fuel lines leak proof and fully functional. The job also includes testing of the system for its satisfactory performance.
Supply, installation, testing and commissioning of:
M S Piping:
P/F of new supply and return header for 06 Lac Lcal/hr HWG from and to main supply and return header with overhead laying with MS Structural steel hangers and MS ISMC supports where ever required with Mild Steel class ‘C’ ERW pipes of following diameters with fittings like tees, elbows, bends, junctions, unions, flanges etc. clamps structural supports, wooden pedestals as per site requirements including application of anticorrosive paint of approved shade over a coat of steel primer/ red oxide.
P/F of new flue gas header for 06 Lac Lcal/hr HWG to main erected flue gas chimney with angular laying with MS Structural steel hangers and MS ISMC supports where ever required through punctured brill wall with Mild Steel class ‘C’ ERW pipes of following diameters with fittings like tees, elbows, bends, junctions, unions, flanges etc. clamps structural supports, wooden pedestals as per site requirements including application of anticorrosive paint of approved shade over a coat of steel primer/ red oxide.The job further includes sealing of punctured wall with concrete and brick mortor.
P/F of new fuel header for 06 Lac Lcal/hr HWG from main fuel line with angular laying with MS Structural steel hangers and supports where ever required with Mild Steel class ‘C’ ERW pipes of following diameters with fittings like tees, elbows, bends, junctions, unions, flanges etc. clamps structural supports, wooden pedestals as per site requirements including application of anticorrosive paint of approved shade over a coat of steel primer/ red oxide.
Insulation for Indoor: Discard and replacement
Elastomeric nitrile foam.
FARUKH SONS ENTERPRISE (BID ID -2237763)
FAVOURITE ELECTRICALS (BID ID -2236814)
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .