Const. of Sports Stadium at Sewah Distt. Panipat (Pdg. Fire Alarm System only).
2024_HRY_368164_1
202429E5C9C9 6019 4C20 9DA2 9180BED875B6665BAR
Open Tender
Electrical Works
Works
60 days
SEWAH
2 documents required · 2 mandatory
₹1,000
₹41,740
Yes
14 Jun 2024
13 Mar 2024
26 Mar 2024
14 Mar 2024
22 Mar 2024
14 Mar 2024
Amount
SITC of Clean Agent Gas HFC 236fa Based Fire Suppression System Direct System 2Kg Capacity with 10 Mtr HST (Heat Sensing Tube) with Open Cabinet with natural airflow,System operating pressure 15 bar at 20°C ,System operating temperature range : -20°C to plus 60°C,The sensing tube must be made of a special modified Polyamide (PA) in Black color with an outer diameter of 6mm, Complete system should be tested and Certified to Standard LPS 1666:Issue 1.0 by LPCB for following type of enclosures - Enclosed airflow,Open with Natural airflow, Open with Forced Airflow along with test report without Monitoring Panel Kit Make: Eaton/ Safex/ Cease Fire
SITC of Watermist and CAF(Compressed Air Foam) Low Pressure Trolley Mounted Fire Extinguisher 50 ltr capacity,Two Units of MS Body 6 ltr Compress air cylinder,Nozzle with Jet and Spray Modes, Working Pressure - not more than 11 bar,Gun - weight without hose - Should be 1.5 kg. ± 10%,Jet mode Lancing Distance - 15 meters ( variance of upto -5% and plus no limit),Jet - Minimum Discharge duration-Continuous and at full throttle and Spray - Minimum Discharge duration should be more than 100 seconds,Product Certification from any NABL accredited Lab (tested in Indian condition) / National Test House as per DIN EN1866-1:2007 Test report shall be enclosed along with the offer,Fire Rating Certificates with standard AFFF 6% foam: For Class A should be Minimum 55A and Class B should be Minimum IIB,The product should be PED certified to PED 2014/68/EU, ANNEXIII(MODULE H),The supplier/OEM should have a licence from PESO for refilling and storage of high pressure gas cylinders Make: Eaton/ Safex/ Cease Fire
SITC of Microprocessor based 1 Loop fault tolerant, networkable type Fire Alarm / Detection Control Panel (having Nos. Each Loop length capacity should be 2000 meters of required loops to suit minimum 20% extra over the nos. of fire detectors. The panel shall be able to give location of all fire / fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON/OFF respective control module whenever any alarm is triggered. Signal with address and analog output, external/inbuilt printer to log all fire or fault events complete in all respects. The Panel Shall be sheet Steel powder coated, sealed to IP30. The panel shall have a built-in power supply, battery charger maintenance free battery capable of running for a minimum 24 hours operation in normal conditions and 30 minutes in fire conditions complete as required. The panel should also have IP30 or better protection. And conforming to BS5839 standards and Duly Approved by EN 54/UL865 9th edition/VDS as per specifications complete in all respect up to the entire satisfaction of Engineer in charge of work. Make: Eaton/ Bosch/ Siemens
SITC of addressable multi sensor smoke detector including mounting base with RED LED should blink in normal conditions and LED should be continues in fire conditions complete as required with inbuilt Isolators as per NFPA 72 style 7 wiring requirements for maintaining operational availability of all elements in the loop in the eventof a short circuit and to meet style 7 requirements: Compensation feature and Automatic addressing. Detector should monitor Electromagnetic interference and report to the panel-current and average values. Detector should have IP30 or better protection rating. Shall be UL/EN/VDS certification. Detectors should have Inbuilt Isolators. Make: Eaton, Bosch, Siemens)
Supply erection testing and commissioning of addressable Heat detector with fixed and rate of raise 60 degree feature and minimum 70 degree including mounting base with RED LED should blink in normal conditions and LED should be continues in fire conditions. etc complete as required. Each Detector should inbuilt Isolators as per NFPA 72 style 7 wiring requirements for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements. High resistance to electro magnetic Detector should monitor Electromagnetic interference and report to the panel current and average values. Detector should have IP30 or better protection rating. Shall be UL/EN/VDS certification. (Detectors should have Inbuilt Isolators). (Make: Eaton, Morley, Bosch,Siemens)
Supply, installation, testing and commissioning of intelligent Analog Addressable type Manual Call Point with RED LED should blink in normal conditions and LED should be continues in fire conditions. having Surface or flush mounting option fully compliant to EN 54 having auto addressing with back box for mounting as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required to complete thejob in all respect up to the entire satisfaction of Engineer in Charge of work. Make : (Make: Eaton, Bosch, Siemens)
Supply, installation, testing and commissioning of Addressable Control Relay Module should have soft addressing features, isolator should be inbuilt with flexible network structures with a maximum switching current of 1A @30V DC.I should have inbuilt isolator. Shall be EN54/UL/VDS Certification Make: (Make: Eaton, Bosch,Siemens)
SITC of Addressable Monitor Module for monitoring of a line with EOL resistor/ Potential free contact/voltage monitoring, it should have soft addressing features, isolator should be inbuilt shall be EN54/UL/VDS approved. (In case of 2 monitoring features in one module (points) each point shall be consider separately for payment). Make: (Make: Eaton, Bosch,Siemens)
Supply erection testing and commissioning 2Core 1.5 sq. mm, FRLS Armoured, two core copper conductor cable including required accessories for erection Polycab /Havells/RR Kabel
AVNET Solutions
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .