Supplying, installing, testing and commissioning of Heavy grade GI. PIPES confirming to IS-1239 part - I with butt welded specials confirming to IS-1239 part - II, such as Tees, elbows, check nuts, unions, flanges, nipplesetc. Including cutting, Welding, fixing in / on walls - 80mm dia
Supplying, installing, testing and commissioning of Heavy grade GI. PIPES confirming to IS-1239 part - I with butt welded specials confirming to IS-1239 part - II, such as Tees, elbows, check nuts, unions, flanges, nipplesetc. Including cutting, Welding, fixing in / on walls - 65mm dia
Supplying, installing, testing and commissioning of Heavy grade GI. PIPES confirming to IS-1239 part - I with butt welded specials confirming to IS-1239 part - II, such as Tees, elbows, check nuts, unions, flanges, nipplesetc. Including cutting, Welding, fixing in / on walls - 50mm dia
Supplying, installing, testing and commissioning of Heavy grade GI. PIPES confirming to IS-1239 part - I with butt welded specials confirming to IS-1239 part - II, such as Tees, elbows, check nuts, unions, flanges, nipplesetc. Including cutting, Welding, fixing in / on walls - 40mm dia
Supplying, installing, testing and commissioning of Heavy grade GI. PIPES confirming to IS-1239 part - I with butt welded specials confirming to IS-1239 part - II, such as Tees, elbows, check nuts, unions, flanges, nipplesetc. Including cutting, Welding, fixing in / on walls - 32mm dia
Supplying, installing, testing and commissioning of Heavy grade GI. PIPES confirming to IS-1239 part - I with butt welded specials confirming to IS-1239 part - II, such as Tees, elbows, check nuts, unions, flanges, nipplesetc. Including cutting, Welding, fixing in / on walls - 25mm dia
Supplying, Installing, testing and commissioning CI Motorised BUTTERFLY VALVES ( PN 16) slim seal standared lever operated type confirming to BS - 5155 with required flanges,nuts, bolts etc. complete. 80MM Dia
Supplying, Installing, testing and commissioning CI Motorised BUTTERFLY VALVES ( PN 16) slim seal standared lever operated type confirming to BS - 5155 with required flanges,nuts, bolts etc. complete. 50MM Dia
Supplying, Installing, testing and commissioning CI Motorised BUTTERFLY VALVES ( PN 16) slim seal standared lever operated type confirming to BS - 5155 with required flanges,nuts, bolts etc. complete. 40MM Dia
Foam Water Sprinkler
Mechanical Foam Tank 2000 Ltr (Civil work Clint Scope)
Supply of Mechanical Foam
Supply and Installation of optical (photo electric) Smoke detector with base, Junction box and other accessories as required
Supply and Installation of Addressable type Hooter with base
Supply and Installation of Manual call point (break glass type) with back box
Supply and Installation of Relay Module
Supply and Installation of 2 core x 1.5 mm2, unarmoured, FRLS outer Sheathed PVC insulated copper conductor Cable to connect all fire alarm devices into FACP
System Programming testing and commissioning charge (1st floor)
Supply and Installation of 2 core x 1.5 mm2, unarmoured, FRLS outer Sheathed PVC insulated copper conductor Cable to connect all fire alarm devices into FACP (PA Systems)
Supply and Installation of 6w Celing Mounding Speaker (PA Systems)
Supply and Installation of Booster Amplifier including necessory control wires, jacks etc. complete.
Installation of Smoke Detector (External)
Supply and Installation of Addressable type Hooter with base (External)
Installation of Old Hooter (External)
Supply and Installation of Manual call point (break glass type) with back box (External)
Installation of Old MCP (External)
Supply and Installation of 2 core x 1.5 mm2, unarmoured, FRLS outer Sheathed PVC insulated copper conductor Cable to connect all fire alarm devices into FACP (External)
System Programming testing and commissioning charge (External)
Supplying and laying of PVC conduit long with accessories in recess including cutting the wall and making good the same in case of recessed conduit as required. Size - 20 mm (External)
MS Cylinder 4 Kg DLP Assembly with Automatic Valve 4 Kg MS Cylinder, DLP Assembly with Automatic valve,FK-5-1- 12 UL Listed Clean Agent, mounting bracket, Spring Top connector , Pressure Switch , End of Line Adaptor.
Heat Sensing Tube RED HR Grade Heat Sensing tube Red HR Grade, Single Layer Special Modified Polyamide Material, Tube ID 4MM OD 6MM, Operating Pressure 15-18 Bar, Maximum Pressure 30 Bar at maximum Temperature of +65 Degree C, Burst Temperature 125 Degree C, Service Life 3-4 Years, Long Term Application, Max Bend in Installation 140mm, Max space between tubes 250mm
Master Control Unit for monitoring the health of the system,Fire status dual RED LED,having dual tone buzzer to indicate fire status, Construction of Panel-(20 SWG) C.R Sheet,Finishing Red,Cable Entry Bottom Top Entry 19 mm knock out, Dimension (105X190X80)mm,Current Consumption 25 Watts,Type of Tone Dual Tone,90-100 dB at 1 Meter Distance,Output 1 Set of Potential Free NO NC COM Only, Contact Rating 1A/120V AC & 2A/24V DC,Indication Green LED (ON) Red Dual Tone Flashing Type
Supplying, installing, testing and commissioning of Heavy grade GI. PIPES 100mm Dia (GROUND FLOOR)
Supplying, Installing, testing and commissioning CI Motorized BUTTERFLY VALVES 100mm dia (GROUND FLOOR)
Supplying, Installing, testing and commissioning CI Motorized BUTTERFLY VALVES 40mm dia (GROUND FLOOR)
Supplying, Installing, testing and commissioning CI Motorized BUTTERFLY VALVES 50mm dia (GROUND FLOOR)
Existing Pipe and Valves dismandling and refabrication work (GROUND FLOOR)
Supply and Installation of optical (photo electric) Smoke detector with base, Junction box and other accessories as required (GROUND FLOOR)
Supply and Installation of Addressable type Hooter with base (GROUND FLOOR)
Supply and Installation of Manual call point (break glass type) with back box (GROUND FLOOR)
Supply and Installation of 2 core x 1.5 mm2, unarmoured, FRLS outer Sheathed PVC insulated copper conductor Cable to connect all fire alarm devices into FACP (GROUND FLOOR)
System Programming testing and commissioning charge (GROUND FLOOR)
Supply and Installation of Relay module (GROUND FLOOR)
Supply of Addressable 4 LOOP Panel (GROUND FLOOR)
Supplying and laying of PVC conduit long with accessories in recess includin cutting the wall and making good the same in case of recessed conduit as required. Size - 20 mm (GROUND FLOOR)
Supply and Installation testing and commissioning of pressure gauge
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].