Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹42.3 LAccepted-AOC 11 82 GROUND FLOOR BLOCK 11 KALYANPURI EAST DELHI DELHI 110091 | EAST DELHI | DELHI | 110091 | ₹42.3 L Quoted ₹42.4 L | L1 | Accepted-AOC ACCEPTANCE |
| 2 | L2₹42.6 L+₹16,205 (0.38%)Rejected-Finance | ₹42.6 L+₹16,205 (0.38%) | L2 | Rejected-Finance HIGHER BIDDER |
| 3 | L3₹47.6 L+₹5.2 L (12.2%)Rejected-Finance | ₹47.6 L+₹5.2 L (12.2%) | L3 | Rejected-Finance HIGHER BIDDER |
Tender Value
₹38 L
EMD Value
₹76,000
Closing Date
1 Nov 2023, 6:00 pmClosed
COL BHUPINDER SINGH CWE NAVY VASCO
CWE NAVY VASCO VASCO DA GAMA GOA 403802
SPECIAL REPAIRS FOR REPLACEMENT OF OLD DETERIORATED HT 4 POLE STRUCTURE TO RMU SYSTEM INFRONT OF 33 KV MRS HANSA OF SOUTH SIDE UNDER GE NW VASCO
2023_MES_621572_1
85700/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
CWE NAVY VASCO
AS PER TENDER DOC
9 documents required · 9 mandatory
₹500
GE (NW) VASCO
₹76,000
Yes
5 Jan 2024
4 Oct 2023
3 Nov 2023
4 Oct 2023
1 Nov 2023
18 Oct 2023
Amount
Supply, install ,testing and commissioning SF6 insulated compact Outdoor type R.M.U. rated voltage 11 KV,rated current 630 A, short circuit breaking current 16 KA and making capacity 40 KA ,fully arc proof metal enclosed, free standing, floor mounting, flush fronted type consists of manually operated non draw out type SF6 module-2 Nos load break switches (Incomers) and 8 No. Vaccum circuit breaker (outgoing) with integrated relays and related CTs as specified below, cable switch module and an interlocking mechanism with the earthing switch all as specified and directed. Degree of protection shall be per manufacturer specifications.
(a) Fixed type voltage indicators and electronic short circuit indicators for simple fault indication (b) Resin cast CT with ratio 50-100/1A with 2.5VA burden class 0.5 for metering and class 5 P10 for protection-Set of three (c) Resin cast potential transformers with ratio 11KV/1.732/110V/1.732, 50VA class0.5 with HT fuses . MeatringPT shall be fixed type provided (d) Self powered microprocessor controlled numeric relay comprising of three over current , one earth fault protection relay with high set for both phase & earth and with fault memory, universal auxliary supply (e) Trip circuit supervision relay (f) Master trip relay
Supply & Lay , testing and commissioning XLPE cable , PVC insulated, screened PVC bedded galvanised steel strip or wire armoured electric power cable, heavy duty with aluminium conductor 11000 Volts grade (earthed), 3 core 95 sqmm laid in trenches/floor/duct/fixed on poles/through GI tubing in different locations / areas complete
Supply & Lay , testing and commissioning XLPE cable , PVC insulated, screened PVC bedded galvanised steel strip or wire armoured electric power cable, heavy duty with aluminium conductor 11000 Volts grade (earthed), 3 core 120 sqmm laid in trenches/floor/duct/fixed on poles/through GI tubing in different locations / areas complete
S & F cable jointing kit for 11KV grade cable for Indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 120 sqmm.
S & F cable jointing kit for 11KV grade cable for Indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 95 sqmm.
Excavation in trenches 1.5 Mtr wide and not exc 1.5 Mtr deep in hard/dense soil getting out and levelling of bottom surface to required level for laying UG cable / errection of poles all as specified.
Excavation in trenches 1.5 Mtr wide and not exc 1.5 Mtr deep in soft/disintegrated rock getting out and levelling of bottom surface to required level all as specified.
Excavation in trenches by cutting of road crossing/PCC hard standing, under boundary wall for laying of pipe/cable including making good the existing surface with same finish to match the original finish complete all as specified and directed by Engr-in-charge.
Returning filling in, including spreading, leveling, watering and well ramming in layers not exc 25cm thick.
Removing excavated material of soils from site to a distance not exc 50mtr away and depositing where directed not exc 1.5mtr from the starting point.
Supplying & Laying in trenches Clear Sand for cushioning under ground cable 8 cm below and 15 cm above complete in level all as specified. (punned thickness of sand will be measured and paid)
Supply and lay un-reinforced precast concrete cable covers, class EHV , type- I with peak, size 300mm x 180mm x 40mm, all as specified and directed.
S & F in trench/on wall in repairs GI tubing light grade for road crossing and cable protection of sizes 80 mm dia
M & L Earthing complete with copper earth plate electrode of size 60cm x 60cm x 3.15 mm thick, buried directly in ground vertically earth pit not less than 2.25 mtr deep below the ground level with top to edge of the plate n. less than 1.5 mtr below ground level connected to copper strip 32 x 6 mm as earthing lead by means of blots, nuts, check nut and washer of galvanized steel, including necessary earth work and excavation in any strata and PCC 1:3:6 type C2 chamber and RCC cover and light grade GI pipe 40 mm dia pipe of required length for protection of GI wire and water funnel and wire mesh with GI pipe medium grade 32 mm dia etc complete all as per electrical plate No 3 of SSR part - I and all directed including connections and testing on completion.
ASHIRWAD ELECTRICALS
S and G Constructions
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .