Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
24 Jul 2023, 6:00 pmClosed
GE E/M Lucknow
Garrison Engineer E/M, 36 LBS Marg, Lucknow Cantt, Lucknow (U.P.) PIN 226002
REPAIR/MAINT/REPLACEMENT OF EXTERNAL LT SUPPLY, LT PANEL BOARD, LT SWITCH GEAR AND ALLIED WORKS AT VARIOUS SUB STATION AND MISC LT INFRASTRUCTURE OF CH CC, CMDC, ECHS, SHO, BASE HOSP, SOI IN THE AREA OF AGE E/M (HOSP) UNDER GE E/M LUCKNOW
2023_MES_605452_1
GE/EM/LKO/HOSP/T-23 OF 2023-2024
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Lucknow
As per NIT
8 documents required · 8 mandatory
₹500
GE E/M Lucknow
₹90,000
Yes
11 Sept 2023
24 Jun 2023
26 Jul 2023
24 Jun 2023
24 Jul 2023
11 Jul 2023
Amount
Supplying and laying or fixing in replacement, jointing and testing LT under ground electric power cable crossed linked polyethylene ( XLPE) insulated, galvanised steel strip or wire armoured, ISI-7098 Marked, with aluminium conductor multi stranded , heavy duty 1100 Volts grade of size 10 sqmm cross sectional area, 2 core, laid in trenches/ laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc. with and including MS Clamps, nuts , bolts, washers complete all as specified and directed. Note :- Excavation, earth work, sand cushioning, protection bricks/ tiles/ block and pipe shall be measured and paid separately under appropriate items.
All as per item No 01 above but of size 10 Sqmm 4 core
All as per item No 01 above but of size 16 Sqmm 4 core
All as per item No 01 above but of size 25 Sqmm 3.5 core
All as per item No 01 above but of size 50 Sqmm 3.5 core
All as per item No 01 above but of size 95 Sqmm 3.5 core
All as per item No 01 above but of size 150 Sqmm 3.5 core
All as per item No 01 above but of size 185 Sqmm 3.5 core
All as per item No 01 above but of size 240 Sqmm 3.5 core
S&F in replacement of GI Pipes galvanized, “light grade ”, laid in trench complete including fittings 80 mm dia protection for LT Cable, complete all as specified and directed.
S&F in replacement of GI Pipes galvanized, “light grade ”, laid in trench complete including fittings 50 mm dia protection for LT Cable, complete all as specified and directed.
S&F in replacement of GI Pipes galvanized, “light grade ”, laid in trench complete including fittings 40 mm dia protection for LT Cable, complete all as specified and directed.
M&L for PCC 1:2:4 type B0 12.5 mm graded agregrate as in foundation in coping in foundation of pole including necessary form work complete all as specified and directed.
M&L in replacement for fabrication and fixing canopy headed junction box suitable for LT Pole made out 3.15 mm MS sheet of size 30x25x15 cm with cover ,04 nos aluminium bus bar of size 25x3 mm for phase and neutral 01 nos 06 Amps MCB SP mounting channel for control street light cable gland aluminium lug MS FIixing clamp -02 nos with nut bolt washer painting with two coat of synthectic enamel paint over a coat of red oxide primer on external and internal surface complete all as specified and directed.
Excavating in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying of cables, pipes etc. and getting out including trimming the sides and forming bottom surfaces to required levels in soft/loose soil complete all as specified and directed.
Returning, filling in, including spreading, levelling, and well ramming in layer not exceeding 25 cm thick in soft/loose soil complete all as specified and directed.
Removing excavated material ( soils) not exceeding 50m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed.
Material and labour for river sand, washed and screened dry for cushioning to under ground cable in trenches below and around under ground cable including spreading and levelling complete all as specified and directed. Note :- Punned thickness shall only be considered for payment
M&L for fly ash bricks of size 230 mm x 110 mm x 70 mm as per IS 12894 -2002, laid flat with width equal to length of brick, laid dry over electric cable for protection complete all as specified and directed.
Supply, fixing, connecting and testing in replacement energy efficient LED blolard light of 18 Watt including foundation work with pCC as required complete all as specified and directed.
Supply, fixing, connecting and testing in replacement energy efficient LED Garden landscape view LANTERN WITH SYMMETRIC LIGHT DISTRIBITION AND LIMITED UPWARD LIGHT COMPONENT light of 18 Watt complete all as specified and directed.
Supply fixing testing in replacement and commissioning of LT panel board suitable size CPRI approved OF size – 1.5 x 1.0 x 0.50 mtr out door type factory made pedestal type outer fabricated out of 3.15 mm CRCA sheet and inner sheet of MS black sheet 2 mm thick and slopy roof and spray painting two coat inside and outside with synthetick enamle paint of approved shade over a coat of red oxide primer locking arrangement comprise 50 mm size brass pad lock with duplicate keys two earthly terminal suitable cable gland for all incoming and outgoing cable grouting of feeder piller box 40 cm above ground level by providing 90 cm long angle iron of size 50x50x6 mm welded on all the for corner embeded in PCC 1:2:4 using 20 mm stone agregrate up to 50 cm deep including connection all exisiting cable with MCCB terminal complete all as specified and directed at the site requirment complete including the following component:- (1) incoming (i) MCCB 4P 250 Amps , 25 Ka -01 Nos. Contd/---
Supply fixing testing in replacement and commissioning of LT panel board suitable size CPRI approved OF size – 1.5 x 1.0 x 0.50 mtr out door type factory made pedestal type outer fabricated out of 3.15 mm CRCA sheet and inner sheet of MS black sheet 2 mm thick and slopy roof and spray painting two coat inside and outside with synthetick enamle paint of approved shade over a coat of red oxide primer locking arrangement comprise 50 mm size brass pad lock with duplicate keys two earthly terminal suitable cable gland for all incoming and outgoing cable grouting of feeder piller box 40 cm above ground level by providing 90 cm long angle iron of size 50x50x6 mm welded on all the for corner embeded in PCC 1:2:4 using 20 mm stone agregrate up to 50 cm deep including connection all exisiting cable with MCCB terminal complete all as specified and directed at the site requirment complete including the following component:- (1) incoming (i) MCCB 4P 400 Amps , 25 Ka -01 Nos. Contd/---
Supply fixing testing in replacement and commissioning of LT panel board suitable size CPRI approved OF size – 1.5 x 1.0 x 0.50 mtr out door type factory made pedestal type outer fabricated out of 3.15 mm CRCA sheet and inner sheet of MS black sheet 2 mm thick and slopy roof and spray painting two coat inside and outside with synthetick enamle paint of approved shade over a coat of red oxide primer locking arrangement comprise 50 mm size brass pad lock with duplicate keys two earthly terminal suitable cable gland for all incoming and outgoing cable grouting of feeder piller box 40 cm above ground level by providing 90 cm long angle iron of size 50x50x6 mm welded on all the for corner embeded in PCC 1:2:4 using 20 mm stone agregrate up to 50 cm deep including connection all exisiting cable with MCCB terminal complete all as specified and directed at the site requirment complete including the following component:- (1) incoming (i) MCCB 4P 630 Amps , 36 Ka -01 Nos. Contd/---
Supply fixing testing in replacement and taking out old/unsv BUS BAR panel and supply and fixing LT bus bar panel OF size – 1 x 1.0 x 0.50 mtr out door type factory made pedastal type outer fabricated out of 3.15 mm CRCA sheet and inner sheet of MS black sheet and slopy roof and spray painting two coat insiade and outside with synthetick enamle paint of approved shade over a coat of red oxide primer locking arrangement comprise 50 mm size godredge brass pad lock with duplicate keys two earthly terminal suitable cable gland for all incoming and outgoing cable grouting of feeder piller box 40 cm above ground level by providing 90 cm long angle iron of size 50x50x6 mm welded on all the for corner embeded in PCC 1:2:4 using 20 mm stone agregrate up to 50 cm deep including connection all exisiting cable with with M CCB terminal complete all as specified and directed at the site requirment complete including the following component:- contd/---
Material & Labour for preparation of old painted surface of steel tubular pole 9 meter long above coping, applying two coat of aluminium paint, and making of strip of 20 cm width (BLACK and white in alternate band) upto 1400 mm height with one synthetic enamel paint, rewriting pole No by painter with enamel paint, and painting the existing MS clamp with one coat of aluminum paint complete all as specified and directed.
Material and labour for rewritting of Pole Nos on existing pole with stencil out with white colour in BLACK background of 80 mm hight around the radius of pole complete all as specified and directed.
M&L for preparation of old painted surface and applying one coat synthetic enamel paint with Spray painting on LT pannel of any type complete all as specified and directed.
M&L in repair MCCBs four pole 16 KA, fixed type incl taking out unserviceable MCCB's and connecting,of capacity 100 AMPS, complete all as specified and directed.
M&L in repair MCCBs four pole 16 KA, fixed type incl taking out unserviceable MCCB's and connecting,of capacity 125 AMPS, complete all as specified and directed.
M&L in repair MCCBs four pole 16 KA, fixed type incl taking out unserviceable MCCB's and connecting,of capacity 160 AMPS, complete all as specified and directed.
M&L in repair MCCBs four pole 36 KA, fixed type incl taking out unserviceable MCCB's and connecting,of capacity 200 AMPS, complete all as specified and directed.
M&L in repair MCCBs four pole 36 KA, fixed type incl taking out unserviceable MCCB's and connecting,of capacity 250 AMPS, complete all as specified and directed.
M&L in repair MCCBs four pole 36 KA, fixed type incl taking out unserviceable MCCB's and connecting,of capacity 400 AMPS, complete all as specified and directed.
M&L in repair Power contactor 4 pole Type Mcx 32 , Fr size 2 rating AC 1 rating 160 A, 50HZ including dismantling the unserviceable contactor, complete all as specified and directed.
M&L in repair Power contactor 4 pole Type Mcx 23 , Fr size 1 rating AC 1 rating 40A, 50HZ including dismantling the unserviceable contactor, complete all as specified and directed.
Supply & fixing in replacement MCCB Four Pole 630 Amp, 36 kA, 415 volts complete all as specified and directed.
S & F in replacement Off load change over switch, 200 Amps, 415 volts, 4 pole in sheet metal enclosure conforming to IS:13947 (Part-3); IEC:60947-3 with locking facility including all connecting/ jointing materials and dismantling of existing change over switch, complete all as specified and directed.
S & F in replacement On load change over switch, 63 Amps, 415 volts, 4 pole side handle type in sheet metal enclosure conforming to IS:13947 (Part-3); IEC:60947-3 with locking facility including all connecting/ jointing materials and dismantling of existing change over switch, complete all as specified and directed.
S & F in replacement on load change over switch (Front handle operate) 400 Amps, 415 volts 4 pole in sheet metal enclosure with interlock door and pad lock facility including dismantling of existing change over switch, complete all as specified and directed.
S & F in replacement street light panel single phase up to 6 kw load with Astronomical digital timer and MCB of capacity 32Amp TP/ MCB SPN 40 Amps fixed on wall/pole with clamps,nut bolts complete all as specified and directed.
Restreching only existing LT OH lines consisting 4 Lines of ACSR and 1 line of GI wire of any size and tightening with aluminium binding wire complete all as specified and directed. Note :- (i) Linear length centre to centre of the poles shall only be measured. 4 Lines of ACSR and 1 line of GI wire will be measured as 01 RM for payment. (ii) Cleaning / pruning of tree branches falling around the conductor shall also deemed to be included in the quoted rates
Supply and fix in repair flat twin core, 1.5 sqmm nominal cross sectional area multistranded aluminium conductor cable, 1100 Volts grade heavy duty cable PVC insulated and PVC sheathed complete all as specified and directed.
Supply and fix in repair flat twin core, 2.5 sqmm nominal cross sectional area multistranded aluminium conductor cable, 1100 Volts grade heavy duty cable PVC insulated and PVC sheathed complete all as specified and directed.
Supply and fix in repair flat twin core, 6.0 sqmm nominal cross sectional area multistranded aluminium conductor cable, 1100 Volts grade heavy duty cable PVC insulated and PVC sheathed complete all as specified and directed.
S&F Straight through joints (Heat Shrink Kits) for LT underground cable indoor/ outdoor type complete for Armoured, PVC sheathed Aluminium conductor cables including excavating earth work, identifying the fault, making proper joint of cable after rectification & returning soil back to earth, for the 3.5 core cable 25 to 50 Sq mm sizes, complete all as specified and directed.
All as per item No 46 above but 3.5 core cable 70 to 150 Sq mm
All as per item No 46 above but 185 sqmm to 300 sqmm 3.5 core
Supplying, transporting, erecting and fixing Steel tubular swaged poles type 410 SP-31 ( 9.0 metres long) complete with cast iron base plate, finial, taper plug, bolts, nuts and screws as specified, including necessary excavation and earth work , PCC 1:4:8 type D2 in foundations below pole, PCC 1:3:6 type C2 around poles and PCC 1:3:6 type C1 as in plinth block , disposal of surplus soil to a distance not exceeding 50 m and depositing where directed, painting steel tubular poles exposed surafces with Aluminium paint two coats over one coat of red oxide primer and providing 300 mm wide bands (3 bands/ straps with synthetic enamel paint and 2 bands with Black bituminous paint ) from plinth block and numbering of poles , painting embedded portion of poles with one coat of bituminous paint including taking down old pole complete all as specified and directed. Note -Old pole will be deposited in MES store yard.
M&L Earthing complete with galvanised mild steel earth plate electrode 600x600x6.0mm thick, burried directly in ground to a depth not less than 2.25 metres deep below ground level with top edge of earth plate not less than 1.5 metre below normal ground level surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all around the plate, using GI strip 32 x 6 mm as earth strip electrode bolted or rivetted to earth plate at one end and connected to equipments at another end, GI earth strip encased in and including 40 mm dia GI 'light grade' pipe from upper end of earth plate upto equipments,20 dia bore GI pipe 'light grade' as water pipe from earth chamber to upper edge of earth plate, Test point , GI funnel with wire mesh fixed on water pipe and PCC 1:2:4 type B-1 (using 20mm graded stone aggregate) as in pit chamber and RCC pit cover 50mm thick precast RCC 1:2:4 type B-1, duly reinforced with MS TMT bars 8mm dia @ 100 c/c both ways with 10mm dia MS round bar as in lifting handles, excavation, earth work including laying the GI pipe concealed in floor/wall all as described in electric plate of SSR Part I complete all as specified and directed and testing on completion. Note :- If the desired earth resistance is not found, earthing shall be redone by the contractor at no extra cost to the department.
Supply, installation, testing and commissioning of Polycrystaline Photovoltaic Module of 315Wp each.The PV modules used must qualify to the latest edition of IEC PV module qualification test or equivalent BIS standards. Crystalline Silicon Solar Cell Modules IEC 61215. In addition, the modules must conform to IEC 61730 Part-1 - requirements for construction & Part-2 requirements for testing, for safety qualification or equivalent IS. I-V curve of module at STC should be provided by bidder.The total solar PV array capacity should not be less than allocated capacity (kWp).The module frame shall be made of corrosion resistant materials silver anodized aluminium alloy.The bidder shall carefully design & accommodate requisite numbers of the modules to achieve the rated power. The module junction box should not be less than IP67 protection.The manufacturer should warrant the Solar Module(s) to be free from the defects and/or failures specified below for a period not less than ten(10) years from the date of sale to the original customer. including taking down old module and depositing in storeyard of EIC. Make of Solar PV modules shall be : TATA / Havells / Panasonic.
S & F in repair cast Aluminum extra heavy pole designer leg and broader designer base finished with polyurethane paint (with proper treatment) daimeter of one leg is 88 mm outer dia for spigot entry 75 mm 03 nos T shaped bolts with nuts & washer provided for concrete foundation . Total length of the pole incl base and legs (base with plate X04 nos Legs) is 3100 mm 10 feet 2 inch ) complete all as specified and directed.
S & F in repair fully cast Aluminum finished with polyurethane paint (with proper treatment) hexagonal junction box with maximum projection breath of 575 mm suitable for two number post top lanterns for 02 meter and 2.5 pole complete all as specified and directed.
S & F in repair fully cast Aluminum finished with polyurethane paint (with proper treatment) with acryclic window cover. Total lenght 933 mm (36.75 inch) & max breath 323 mm (12.75 inch) including B22 brass holder provided with aluminum cover and spigot entry 78/90 mm ans suitable for 30to 50 watt LED bulb complete all as specified and directed.
S & F in repair fully cast Aluminum finished with polyurethane paint (with proper treatment) squire junction with maximum projection breath of 625 mm suitable for two number post top lanterns for 2.5 meter and 3.0 Pole complete all as specified and directed.
M & L for tracing out LT Cable fault of any size any Location in the area of the AGE E/M hospital by cable fault fault locater Machine and mark location , Excavation for Joints and refilling removal complete all as specified and directed. Note - Joint Will be measure and paid respective Item.
Supply and fixing (in Rep) Integral dome type white coloure plastic boty of size 300 mm suitable for fixing on 80 mm pipe post top lanterns including suitable for 1x25 W CFL including making connections complete all as specified and directed.
Supply, installing, testing and commissioning in replacement factory made , tested , CPRI approved powder coated LT Panel board ,cubical compartmentalized , out door type double door , plate form mounted, suitable for 415 volts, 3 phase, 4 wire, 50 Hz AC supply system having bus bar chamber with insulated aluminium bus bars four pole installed on porcelain/SMC insulator. The panel shall be dust and vermin proof IP-54 class protection and outer shell made of of 3.15 mm CRCA MS sheet, inner shell made of 2.0 mm thick CRCA MS sheet , 50x50x6mm thick MS angle iron frame work, the cubical have bottom channel of size 75x40mm duly coated with zink metal coating,front and rear opening type, with apron for cable entry closing locking arrangement including internal wiring with PVC insulated solid, copper conductor FRLS cable, IS-694 marked, 1100 volts grade of appropriate size ( but not less than 2.5 Sqmm) and comprising of the following :- Contd/---
Item No 58.00 contd/--- (a) Incoming :- Air Circuit Breaker (ACB) draw-out type with microprocessor based protection release having inbuilt overload, short circuit, instantaneous and earth fault (LSIG) protection as standard features including separate LEDs on front of the release for identification of individual faults. The protection release should be with LCD display for viewing and recording last 10 fault trip history along with monitoring of current parameters of breaker. The ACB should have a breaking capacity of 50kA for Ics=Icu=Icw for 1 sec at voltage of 415 volt. Designed operational voltage should be 690 V. The rated insulation voltage (Ui) should be 1000 volts and the Rated Impulse Voltage should be 12kV with fully rated adjustable neutral. The ACB should have inbuilt over temperature protection. The ACB should be provided with 2 nos. of Programmable Changeover Contacts for overload pre-alarm and Over- temperature alarm Approved (i) ACB 4 pole, 800 Amp, 50 KA, 415 Volt AC Horizontal draw out type ,manual front operated with Micro processor based LCD protection release for adjustable over current, short circuit and earth fault protection-01 No Contd/----
Item No 58.00 contd/--- (ii) Digital VAF+PF meter -01No (iii) CTs ratio 800/5 A ,class 1, ISI marked -01 sets of three (iv) Indicating lamp- 01 set of three (v) Four Pole , Aluminium bus bar 1200 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators. (b) Outgoing :- Moulded Case Circuit Breaker shall be 3 pole 415Volts, 3 phase, 50 Hz AC with Thermal Magnetic based protection release & required Breaking capacity with adjustable protection and conforming to IEC 60947/IS 13947/Pt.II/1993 (Latest version). The MCCB should have Ics=100% Icu for short circuit breaking capacity of required KA rms at 415 Volt 50 Hz AC with designed operational voltage 550V. MCCB should have no derating up to 50 degree. The MCCBs shall have spreader links, ROH and phase barriers as standard feature of manufacturer. Approved Make : Siemens 3VL, Legrand DRX, ABB Tmax, Schneider NSX Contd/---
Item No 58.00 contd/--- (i) MCCB 4 pole , 250 Amps,50 Hz,415 Volts, 25 KA thermal magnetic release - 04 Nos (ii) MCCB 4 pole , 200 Amps,50 Hz,415 Volts, 25 KA thermal magnetic release - 02 Nos (iii) MCCB 4 pole , 160 Amps,50 Hz,415 Volts, 25 KA thermal magnetic release - 02 Nos (c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts platform shall be such that it is of a height 45 cm above the nearest road level. Contd/---
Item No 58.00 contd/--- Note :- (i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The MCCB /ACB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer.
Supplying, fabrication and fixing in replacement LT panel door made of CRCA MS sheet having thickness 3.15 mm powder coated finish over one coat of red oxide including all fixing acessories i.e. suitable size of hinges, nuts, bolts, washers, siliding bolt ,cutting and welding works etc complete all as specified and directed. Note;_ Net finished area of door will be measured for payment.
m/s allied enterprises
M/s Vatsh Raj and co
FUTURE Inc.
Ajanta Motor Store
Ajanta Associates
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .