Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹24.7 LAccepted-AOC | 1 | Accepted-AOC Being lowest | |
| 2 | 2₹33.5 L+₹2.0 L (6.26%)Rejected-Finance 9 NAROTTAM KUNJ MADHU NAGAR AGRA CANTT 282001 | AGRA | UTTAR PRADESH | 282001 | 2 | Rejected-Finance Not being lowest |
| Sl No | Description | Qty | Unit | M/s SCHOLASTIC ENTERPRISES L2 | M/S VIDIT ENTERPRISES L1 |
|---|---|---|---|---|---|
| 1.00 | Dehydration and Filtration of existing transformer oil in transformers (33 KV system step down to 33/11 KV) by centrifuging machine on site at different locations without disturbing the power supply system. The machine continuously run round the clock till obtaining the dielectric strength of oil 60 KV minimum 2.5 mm gap and carrying out IR test of primary and secondary of transformer including commissioning and testing of transformers after topping up with new transformer oil complete all as specified and directed.
Note:- New Transformer oil for topping up shall be measured in relevant items of BOQ. | 7,500 | Per Litre | 4 ₹30,000 Lowest | 10 ₹75,000 |
| 2.00 | Supply & filling up of transformer oil conforming to IS -335 of 1993 as in topping up / replacement up to desired level of transformer oil capacity complete all as specified and as directed.
Note: Dielectric strength of oil should not be less than 50 KV/cm . | 1,400 | Per Litre | 130 ₹1,82,000 Lowest | 145 ₹2,03,000 |
| 3.00 | Disconnecting all eletrical connections from transformer and dismantling the components of transformer for easy loading transportation unloading the unserviceable transfomer 2 MVA TO 3.15 MVA, 33/11 KV copper wound from 33 KV MRS to workshop and back including installation, testing and commissioning after repairs including painting of complete transfomer and its mounting structure complete all as specified and as directed. Labour only for opening the top cover of transformer and carrying out the following work/repairs by specialist/reputed transformer manufacturer or repairing firm:-
(a) Removing of transformer oil from transformer into separate barrels.
(b) Taking out the core assembly with HV & LV windings of the transformer.
(c) Cleaning the transformer from inside of tank as per manufacturer's guidleines and painting with one coat of zinc paint as per manufacturer's norms.
(d) Ovening in vapour phase drying oven at factory workshop for 72 hrs.
(f) Filling of transformer oil after centrifuging of complete transformer oil.
(g) Reassembling of winding over the core of the transformer.
(h) Replacement of bushings, spindle, oil level indicator, winding temperature gauge, oil temperature gauge, drain valve, breather etc shall be measured and paid separately. | 1 | Each Job | 50,000 ₹50,000 Lowest | 70,000 ₹70,000 |
| 3.01Item No.3 (Contd...) (j) Refixing of transformer top cover with new gasket, nut-bolts etc complete. (k) Testing and repair of radiator complete against any type of leakage and carry out soldering/brazing if required to stop the leakage. (l) Checking of Buchholz relay and proper connection to breaker and testing complete. (m) Supply/fixing of insulating /material packing. Note:- (i) Transformer oil, HV and LV windings shall be measured and paid separately. (ii) Routine test, high voltage test, buchholtz relay tripping test and all other mandatory tests as per IS shall be carried out at factory premises. (iii) The quoted rate are inclusive of all minor spare parts that are required to make function electrically to transformer and not mentioned in Sch 'A' BOQ. (iv) The repair work shall have guarantee of 12 months. | |||||
| 4.00 | M & L for rewinding HT coil of 33/ 11 KV Transformer any capacity using proper size DPC copper wire and insulation material , heating coils in heat chamber after rewinding including taking out carefully burnt unserviceable copper winding of coils complete all as specified and directed. | 792 | KG | 1,320 ₹10,45,440 | 1,150 ₹9,10,800 Lowest |
| 5.00 | M & L for rewinding LT coil of 33/ 11 KV Transformer any capacity using proper size DPC copper wire and insulation material , heating coils in heat chamber after rewinding including taking out carefully burnt unserviceable copper winding of coils complete all as specified and directed. | 540 | KG | 1,320 ₹7,12,800 | 1,150 ₹6,21,000 Lowest |
| 6.00 | Re-insulation of LT/HT coil of transformer of any capacity using proper size paper insulation material to form DPC Copper wire and insulation material suitable for HT 33/11 KV transformer complete all as specified and directed.
Note : Item shall be measured only where re-insulation of copper wire is required. | 80 | KG | 500 ₹40,000 | 350 ₹28,000 Lowest |
| 7.00 | Supply & fixing in repair breather assembly with silica gel as per existing size, shape and specification complete for capacity 2 MVA TO 3.15 MVA, 33/11 KV transformer complete all as spd and directed. | 1 | Each | 3,000 ₹3,000 | 2,000 ₹2,000 Lowest |
| 8.00 | Supply & fixing in replacement silica gel for 33/11 KV transformer complete all as specified and directed. | 8 | Kg | 300 ₹2,400 Lowest | 300 ₹2,400 Lowest |
| 9.00 | Supply & fixing in repair brass stud on HT side as per existing size, shape and specification for capacity 2 to 3.15 MVA, 33/11 KV transformers complete all as specified and directed. | 3 | Each | 800 ₹2,400 Lowest | 1,500 ₹4,500 |
Tender Value
₹29.9 L
EMD Value
₹59,800
Closing Date
15 Sept 2025, 6:00 pmClosed
HQ CWE Agra
112, Taj Road, Agra Cantt
REPAIR AND MAINT OF 33 KV TRANSFORMER, VCBs ACSR CONDUCTOR, LIGHTING ARRESTER, BATTERY BANK AT COD AND GWALIOR ROAD POWER HOUSE UNDER GE (EAST) AGRA
2025_MES_725992_1
84383/E8
Open Tender
Miscellaneous Works
Item Rate
180 days
Agra
MES contractors enlisted for Class D and above and category b(iii) for unenlisted contractors meeting the enlistment criteria corresponding to value class and category of work
8 documents required · 8 mandatory
₹500
GE East Agra
₹59,800
30 Oct 2025
13 Aug 2025
22 Sept 2025
13 Aug 2025
15 Sept 2025
27 Aug 2025
13 Aug 2025 - 20 Aug 2025
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .