Tender Value
₹7.6 Cr
EMD Value
₹7.0 L
Closing Date
21 Nov 2025, 6:00 pmClosed
Chief Engineer(AF) Nagpur
HQ Chief Engineer(AF) Nagpur- 440007
PROVISION OF DEFICIENT MD ACCN UNDER GE AF GURGAON NO 1
2025_MES_732212_1
AF_GUR_801248
Open Tender
Civil Works
Lump-sum
540 days
GURGAON
For MES Enlisted Contractors- Class S Category a (i) For other Contractor meeting enlistment Criteria of MES for Class S Category a (i)
7 documents required · 7 mandatory
₹3,000
GE AF GURGAON NO. 1
₹7.0 L
Yes
HQ Chief Engineer(AF) Nagpur
6 Mar 2026
23 Sept 2025
28 Nov 2025
23 Sept 2025
21 Nov 2025
14 Nov 2025
23 Sept 2025 - 30 Sept 2025
1 Oct 2025
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
Blank
SCH 'A' PART XI (MISC B/R & E/M ITEMS) Note:- Excavation and earthwork to the extent required for execution of relevant item under this schedule unless otherwise specified shall be measured and paid under relevant items of Schedule 'A' Part-II.
INTERNAL WATER SUPPLY
Supply and fixing Health Faucet (ABS Body) mild steel chromium plated suitable for 15 mm dia fixing in pipe with 1.25 meter long flexible tube and ABS wall hook including making connection and fixed to 15mm bore complete all as specified and directed.
Supply and fixing angle valve of cast coper alloy chromium plated fancy type screwed down high pressure with crutch or butterfly handle screwed both ends for iron pipe or for unions and fixed 15 mm bore (concealed) complete all as specified and directed.
Supply and fixing 15mm dia Two Way Bib taps, fancy type,,cast copper alloy chromium plated with crutch or butterfly handle, screwed down for CPVC pipe or for brass ferrule and fixed complete all as specified and as directed.
Supply and fixing Brass CP Mixer for mixing hot & cold water screwed down for 15 mm dia CPVC Pipe and fixed all as specified and as directed.
INTERNAL ELECTRIFICATION
Supply and fixing LED Lamp 9 watt 220 volts AC of suitable size complete all as specified and as directed.
Supply and fixing LED lights fitting 1x 20 W, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed.
Supply and fixing LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and as directed.
Supply and Fixing LED light fitting 1x9W/1X10Wbulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size.complete all as specified and as directed.
Supply and fixing LED Building Security light fitting 25 watt complete all as specified and directed by Engr -in- charge.
Supply and fixing MCCB 63 Amps 4P 25 KA 415 Volt Make Indoasian Cat No 830020 including MCCB Enclosure for 63 Amp MCCB Make Indoasian Cat No 811985 fixed on wooden board of appropriate size for mounting of enclosure complete all as specified and as directed. NOTE:-Rate inclusive of Fixing of cable including lugging complete
Supply and Fixing ceiling fan 230V, 50 Hz AC, 1200mm sweep, min air delivery 210 CFM with service value 6.00 BEE, five star rated with brushless direct current motor (BLDC) complete with hanging arrangement by down rod alongwith steel wire rope for additional safety in ceiling fan with all allied accessories and connecting up with three core, 0.75 sqmm PVC insulated copper conductor cable complete all as specified and directed.
Supply and Fixing exhaust fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding of sweep 250mm (for Toilets) complete all as specified and as directed.
Supply and Fixing exhaust fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding of sweep 300m (for Kitchen) complete all as specified and as directed.
Supply and Fixing electric water heater, storage type steel body and heating element upto 2 KW capacity 25 litre, BEE 5 Star rated complete with all accessoriessuch as safety valve, thermostate, NRV, connection piece etc. complete all as specified and as directed.
Supply and fixing Smart RF/Cellular Single Phase AC Meter Tamper Proof, Static Meter of Class 1.0, 315 V, 50 Hz, 10 A-60 A conforming to IS-16444 and relevant IEC standards with inbuilt Radio Frequency communication facility with self healing mesh network with default and on demand display, billing data generation facility, anti-tamper features, Microprocessor and LED/LCD based circuitry including Polycarbonate Meter Box of minimum suitable size for 1 Phase meter with viewing glass, concealed hinge and earth bolt plugged complete all as specified and directed. Meter Should support sending the following data : 15/30 min instantaneous data for voltage, current, power factor, power, cumulative energy and frequency, monthly billing survey for Cumulative Energy and Max Demand to software Meter should have connect / disconnect functionality operable from mdm/billing software and prepaid features would be MDM / Billing end as per prevalent IS including taking down of existing meter and deposit to MES store yard for safe custody all as specified and as directed . Note:- Contractor has to ensure integration and maintainance of meters with the existing Advance Metering infrastructure (AMI) of smart meters of different makes without any additional infrastructure and cost implication.
EXTERNAL WATER SUPPLY
Supply, install, testing and commissioning of monoblock pump set with discharge 417 LPM, head not less than 36 m with delivery size of 80 mm bore, 415 Volts, 50 Hz, AC 3 Phase supply, electric driven, inclusive of air valve at delivery, pressure guage along with cabling by XLPE copper cables from starter to pump set with cable tray and PCC foundation complete all as specified and as directed.
EXTERNAL ELECTRIC SUPPLY
d) Four sleek circular LED light fitting in false ceiling . e) One Sleek circular PVC heavy duty fan in false ceiling. f) Aluminum chequered plate (3 mm thick) as flooring joint in chequered plate should not more than one and top covering with Granite flooring complete. g) Non stop button / independent operation with braille script. h) Over load warning indicator both audio and visual type with tripping system having relays etc (overload protecting / tripping system). j) Front landing door of stainless steel mirror finish operations with a minimum time of 10 seconds and up to a maximum time of 30 seconds. k) Car size shall be conformity with IS-3534-1976 and body to be stainless steel of 16 gauge mirror finish with stainless steel hand rail 38 mm hairline finish. l) Set of three in number limit switches at the bottom and top most position of lift hoist ways as specified in IS. m) Mirror of 4 mm thickness of suitable size as specified. n) Specification plate with complete details . o) Continuous earthing for machine and equipments, 2 Nos of GI plate earthing per lift as shown in electrode plate No 3 of SSR Part -I p) Steel wire rope of adequate size as per relevant IS and as per manufacturer specifications.
Supply and erect 2 pole structure on 11 mtr steel Tubular pole consisting with anti-climbing device, PCC foundation & cross arms etc. complete all as specified and as directed.
Supply & erect steel tubular swaged poles Type 410 SP-31 (9.0 metres long) complete with CI base plate and finial and single swan neck including foundation all as specified and as directed.
Supply and fixing LED street light fitting 35/36 W 230V AC outdoor type with high pressure die cast aluminium housing and heat resistant complete with impact and corrosion resistant including thermal management in multiple optices complete with IP 65/66 protection all as specified and as directed.
Total amount of Schedule 'A' Part XIII carried over to General Summary
Supply and Installation , testing and commisioning distribution Transformer step down, outdoor type, 11//0.433 KV with HT 3 phase and LT 3 phase 4 wire system copper wound with off load tap changing arrangement on HT side for a variation of secondary voltage +/- 7.5% insteps of 2.5% cotinuous rating of 100 KVA outdoor type confirming to (IS 1180, level-II) with and including the following: (a) Lifting lugs/ hooks for transformer and tank. (b) Earthing terminal rating and diagram plate. (c) Air release device. (d) Oil filling inlet pipe with plug. (e) Drain outlet pipe with brass gate valve with dummy plug. (f) Conservator with
FIRE FIGHTNING
Supply and fix Control Console of 12 zone console speaker complete all as specified and as directed.
Supply and fix 6 Watt wall mount CD Speaker with talk back complete all as specified and as directed.
Supply and fix 250 Watt wall mounted amplifier complete all as specified and as directed.
Supply and fix Microphone set complete all as specified and as directed.
Supply, installation, testing and commisioning & laying of 2 core twin twisted 48/0.2 ATC multi strand over all amoured speaker cable complete all as specified and as directed.
Supply and fix Fire Alarm sounders / Sirens electronic type horizontal single stage continuous normal operation for at least 50 minutes with sound level 65 DB to 120 DB measured at 1.5 meter with sound output variation of + 5 DB for 500 meter range complete all as specified and as directed.
Supply & installation of Light weight squeeze grip type CO2 type fire extinguishers of 4.5 kgs capacity with stand from branch new seamless dran controller of explosives approval fitted with wheel valve as per IS : 3224 with ISI mark with discharge hose and horn and supplied with initial charge as per IS :15683 with ISI mark complete all as specified and as directed.
Supply and fixing of dry powder ABC stored pressure squeeze grip type fire extinguishers, 6 kg cap, IS:15683:2006, filled with ABC mono ammonium phosphate base power-90 complete with discharge hose and wall mouting bracker, 2 mm mild steel EPDM rubber, pressure gauge which work effectively on all class of fires (ABC &E) with 5 years warranty incl transportation all taxes and all labour charges etc complete all as specified and as directed.
Supply and fixing fire extingusher mechanical foam type light weight stored pressure type of 9 Ltr Capacity IS 15683. incl transportation all taxes and all labour charges etc complete all as specified and as directed.
Supply, install and testing booster pumps for 440 Volts, 3 Phase, 50 Hz confirming to IS 12469-1988 with CI casing bronze impeller and stainless steel shaft mounted on heavy duty bearings suitable for 440 Volts, 3 Phase, 50 Hz, 36 m head, 900 LPM discharge with minimum pressure of 3.5 Kg/Sq.cm. complete all as specified and directed.
LT Panel made out of CRCA sheet 3.15 mm thick outdoor Pedestal type CPRI approved, totally enclosed with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for cables, danger notice plate, strickering of Switch gear about termination of switch gear, and the nuts/ bolts etc used are to be made of rust proof material incl as per IS: 8623 tinned aluminum bus bar with insulators suitable for three phase and four wire LT AC, 50 Hz 415 V 2000 A capacity complete with powder coating, necessary internal electric connection as required and provision of the following: (Main Panel ) Incoming: (a) MCCB 4 Pole, 415 V,36 kA (ICS=ICU=ICW for 1 Sec), with magnetic release of capacity 250 Amps, with adjustable type overload protection, short circuit protection - 01 No OUTGOING : a) MCCB 3 Pole, 415 V,16 kA (ICS=ICU=ICW for 1 Sec), with magnetic release of capacity 250 Amps, with adjustable type overload protection, short circuit protection - 01 No for APFC Panel b) MCCB 3 Pole, 415 V,16 kA (ICS=ICU=ICW for 1 Sec), with thermal release of capacity 63 Amps, with fixed type overload protection, short circuit protection - 01 No for DG Panel c) MCCB 3 Pole, 415 V,16 kA (ICS=ICU=ICW for 1 Sec), with thermal release of capacity 100 Amps, with fixed type overload protection, short circuit protection - 02 No for Building d) Intelligent Panel meter to measure voltage, current, frequency, power factor etc with all connected CTs of each breakers e) LED Indicating Lamps for each phase with colour code Red Yellow Blue for R, Y and B Phases for each breakers
DIESEL GENERATING SET
Silent engine generating set with accoustic enclosure as per CPCB norms 415 volts 30 KVA 3 phase 0.8 power factor 50 Hz, 1500 RPM self excited self regulated brushless AC generator including accoustic enclosure suitable for ambient condition and conforming to condition under IS 4722, BS 5514/ 2613 /5000 with and including the following:- (i) The capacity of Generator set shall be net after all due de-rating factors as per relevant ISI design. (ii) Rate quoted shall be deemed to be inclusive of cable and terminations form Generator to the AMF Panel, with necessary holes to wall including making good to disturbed surfaces so as to match with the existing finishes all as specified and directed. (iii) The quoted rate shall be deemed to be inclusive of first fill of oil and final successful acceptance test. (A) Alternator :- Standard design alternator rated at min 35 KVA net output at site after considering de-rating as per site conditions at 0.8 (lag) power factor AC, 3 - phase 4 - wire 415 volts 50 Hz, 1500 RPM, self excited self regulated screen protected drip proof IP 23 enclosure brushless design with winding in pole faces, insulating class 'H' and voltage regulation of +/- 1% at rated voltage from no load to full load. The alternator shall be conforming to BS 2613/5000 and shall be imposition to generate supply with f
q) Other standard fixtures and fitting like guide rails, sheaves, counter weights with guards, buffers, gear unit breaks, control panel, locks, governor, car operational panel, power, control and trailing cables complete. r) Full length display indicator panel. s) Main drives and control shall be of latest, high effective and low power consumption. t) Suitable phase reversal relay shall be provided on the controller to protect lift / equipment against phase reversal, phase failure and low voltage. u) Stainless steel front opening type landing door & car door with small opening for vision of size 200 mm x 800 mm with toughened glass not less than 8mm thick. v) Three-way Intercom connectivity i.e. Ground floor, security post, car cabin and machine room.
requency regulation with in +/- 1% tolerance. The alternator will be suitable for tropical climate and shall generally conform to BS - 2613/5000/ IS – 4722.
i) Insulation class - 'H‘ ii) Temparature rise Class - 'H‘ iii) Excitation : Self Excited iv) Regulation performance: The voltage is kept constant with +/- 1%, manual voltage adjustment within +/- 5% v) Frequency regulation +/- 1% (B) Diesel Engine: - Adequate capacity of Diesel engine as accosted by the accepting officer basing on manufacturers technical details water cooled to drive independently above alternator and after considering de-rating as per site conditions after generating and reducing power consumed by accessories directly coupled through flexible coupling multi cylinder multi stroke direct injection, cold starting 1500 RPM, as per relevant ISI/BS - 5514 with an overload capacity of 10% for half an hour in 12 hours continuous running complete with standard accessories all as specified and required for safe handling and operation salient features of accessories shall be as under :- i) Fly wheel with housing ii) Cooling system :- Moulded radiator with fan & belts iii) Cooling Water pump : - Centrifugal type belt driven iv) Exhaust System :- Exhaust System complete with exhaust piping of suitable dia with MS pipe light grade upto & outside and 1 meter away from the enclosure, covered with asbestos rope and aluminium foil of 28 SWG complete with in the enclosure for safe exhaust without transforming vibration to the wall of the enclosure.
x) Generator Monitoring Panel : - Comprising of all standard items as mentioned under this schedule or asper standard practice iginiton key switch and start / stop arrangement, indications for Engine parametes, hour run meter, RPM meter, Engine oil pressure indicator, water/coolent temparature indicator, Battary volt display. xi) Safety Controls : - Engine low lube oil pressure high water temparature and over speeding of engine xii) Coupling arrangement : - Flexible coupling, fly wheel to suit flexible coupling xiii) Accessories :- AVM Pads built in enclosure and for entire unit on platform. xiv) Base Frame : - Should be provided as OEM norms xv) MS pipe line to and from he fuel tank to the DG set. C) AMF Panel :- Factory made inbuilt type control cubical type made out of 2mm thick CRCA sheet dust and vermin proof totally enclosed with front opening of 415 volts 3 -phase 4 - wire AC 50 Hz, including powder coated, copper bus bar of one and half times the rated load of 35 KVA alternator complete with internal wiring with PVC insulated single core copper conductor multi stranded wire of 1100 volts grade of suitable capacity, fuses, name plates consisting of 4 pole MCCBs and Contactors of capacity as recommended by the manufacturer. Detachable cable gland plates, all controls, indicators and standardstandard microprocessor based LED/LCD display for indicating voltage, current, frequency, speed, kW, kWH, pf, temperature, Battery voltage, etc
g) Annuciation with indication lamps for : (i) Low lub oil pressure. (ii) High Water Temparature. (iii) Engine over speed. (iv) Battery low voltage Controls :- a) Load on Indication b) Load off indication c) Engine start push button d) Engine stop push button e) Fault accept / reset push button f) Battery charger (i) Transformer shall be dry type, double wound, with copper conductor and Class–B insulation with temperature rise limited to Class-A insulation. (ii) Isolating switch shall be heavy duty, load break type, operated by an external handle. (iii). Fuses shall be HRC type and arranged for easy replacement. Semiconducting devices fuses shall be fast-acting type. (iv). Indicating meters (voltmeter and ammeter) shall be 96mm x 96mm, flush type 90 degree scale with antiglare glass, + 1% accuracy with zero adjuster on the front of the meter. (v) The following indications/alarm annunciation shall be provided: a) Failure of input AC supply to the charger
ix) The noise level should be 75 dba at 1m under free field conditions. x) The acoustic enclosure parts shall be of powder coated after pre treatment process. The powder coating shade should be Gen set Green. The base frame should be painted with epoxy based black shade. E) The coated rate includes excavation, removing of soft soil and PCC, Cement Concrete foundation, filling and mass concrete type B2 (1:2:4) using 40 mm graded aggregate of size not less than 4.6 x 3.0 x 0.8 m for placing of DG Set complete all as specified and directed.
SEWAGE DISPOSAL
Supply, laying in trenches and jointing of 200 mm dia bore double wall corrugated polyethelene (HDPE) pipe of stiffness class designation SN8 including all necessary jointing material and fittings such as couplers, connectors,bends, elbows ,Tees and end caps etc complete all as specified and as directed.
Total amount of SCHEDULE 'A' PART XIII (MISC ITEMS) (B/R & E/M ITEMS) brought forwarded from Serial Page No. 75
Blank
Blank
Blank
GENERAL SUMMARY
Lumpsum price worked out by the contractor for “BUILDINGS & STRUCTURES” as listed in Schedule ‘A' Part I representing above / below the lumpsum price as inserted by MES for Schedule ‘A’ Part I on Srl Page No. 31
Lumpsum price worked out by the contractor for “EXCAVATION,EARTHWORK & SITE CLEARANCE (FOR SCHEDULES OTHER THAN SCHEDULE 'A' PART-I)” as listed in Schedule ‘A' Part II representing above / below the lumpsum price as inserted by MES for Schedule ‘A’ Part II on Srl Page No. 32
Lumpsum price worked out by the contractor for “DEMOLITION & DISMANTLING” as listed in Schedule ‘A' Part III representing above / below the lumpsum price as inserted by MES for Schedule ‘A’ Part III on Srl Page No. 33
Lumpsum price worked out by the contractor for “INTERNAL WATER SUPPLY” as listed in Schedule ‘A' Part IV representing above / below the lumpsum price as inserted by MES for Schedule ‘A’ Part IV on Srl Page No. 35
Lumpsum price worked out by the contractor for “INTERNAL ELECTRIFICATION ” as listed in Schedule ‘A' Part V representing above / below the lumpsum price as inserted by MES for Schedule ‘A’ Part V on Srl Page No. 40
Lumpsum price worked out by the contractor for “FIRE FIGHTING” as listed in Schedule ‘A' Part VI representing above / below the lumpsum price as inserted by MES for Schedule ‘A’ Part VI on Srl Page No. 42
Lumpsum price worked out by the contractor for “LIGHTENING PROTECTION” as listed in Schedule ‘A' Part VII representing a
bove / below the lumpsum price as inserted by MES for Schedule ‘A’ Part VII on Srl Page No. 44
Lumpsum price worked out by the contractor for “AREA DRAINAGE” as listed in Schedule ‘A' Part XII representing above / below the lumpsum price as inserted by MES for Schedule ‘A’ Part XII on Srl Page No. 58
Lumpsum price worked out by the contractor for “EXTERNAL WATER SUPPLY” as listed in Schedule ‘A' Part IX representing above / below the lumpsum price as inserted by MES for Schedule ‘A’ Part IX on Srl Page No. 50
Lumpsum price worked out by the contractor for “ROAD/ PATH/ CULVERT” as listed in Schedule ‘A' Part VIII representing above / below the lumpsum price as inserted by MES for Schedule ‘A’ Part VIII on Srl Page No. 47
Lumpsum price worked out by the contractor for “SEWAGE DISPOSAL ” as listed in Schedule ‘A' Part XI above/below the lumpsum price as inserted by MES for Schedule ‘A’ Part XI on Srl Page No. 56
Lumpsum price worked out by the contractor for “EXTERNAL ELECTRIFICATION” as listed in Schedule ‘A' Part X above/below the lumpsum price as inserted by MES for Schedule ‘A’ Part X on Srl Page No. 54
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 5.13 MB
801248TENDERDOCUMENT.pdf
Tender Documents • 2.28 MB
801248ARCH.pdf
Additional Documents • 6.87 MB
801248SRT.pdf
Additional Documents • 9.80 MB
BOQ_819810.xls
BOQ • 0.35 MB
801248TDDRAWINGS.pdf
Additional Documents • 5.32 MB
801248CORRIGENDUM02.pdf
PDF • 0.27 MB
801248CORRIGENDUM01.pdf
PDF • 0.22 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .