Tender Value
₹3.7 Cr
EMD Value
₹4.4 L
Closing Date
15 Aug 2022, 6:00 pmClosed
CE (AF) WAC PALAM
HQ CE (AF) WAC PALAM
PROVN OF SEWAGE TREATMENT PLANT AT AF STN BHISIANA
2021_MES_487916_2
CEWAC/BHI/T-21/2021-22
Open Tender
Civil Works
Lump-sum
485 days
GE (AF) BHISIANA
AS PER NIT AND TENDER DOCUMENT
8 documents required · 8 mandatory
₹2,000
GE (AF) BHISIANA
₹4.4 L
Yes
29 Mar 2023
27 Jul 2022
22 Aug 2022
27 Jul 2022
15 Aug 2022
3 Aug 2022
Amount
SCHEDULE `A' PART - I (Building Works) is not prepriced by MES and prepriced rates indicates 0.0 under column 6 signified this fact only.
Construction of 1.0 MLD MBBR STP complete all as specified and shown on drawings.
NOTE: Schedule ‘A’ Part II to X under Ser No. 2.01 to 2.10 are Prepriced by MES.
Lump sum price worked out by the Contractor for “EXCAVATION AND EARTH WORK” as listed in Schedule ‘A’ Part II
Lump sum price worked out by the Contractor for “INTERNAL ELECTRIFICATION"” as listed in Schedule ‘A’ Part III
Lump sum price worked out by the Contractor for “INTERNAL WATER SUPPLY"” as listed in Schedule ‘A’ Part IV
Lump sum price worked out by the Contractor for “ROAD, PATH AND CULVERT” as listed in Schedule ‘A’ Part V
Lump sum price worked out by the Contractor for “FENCING AND GATES ” as listed in Schedule ‘A’ Part VI
Lump sum price worked out by the Contractor for “EXTERNAL ELECTRIFICATION ” as listed in Schedule ‘A’ Part VII
Lump sum price worked out by the Contractor for “SEWAGE DISPOSAL ” as listed in Schedule ‘A’ Part VIII
SCHEDULE `A' PART - XII MISC ITEMS (B/R & E/M) is not prepriced by MES and prepriced rates indicate 0.00 under column 5 signifie this fact only.
Supply, install, testing and commissioning of Raw Sewage pumps with suitable capcity motor of designed capacity & head for pumping sewage from Equalisation Tank to Anoxic. chamber (tanK) Pump shall be non clog, vertical submersible with chrome steel impeller and cutter, non-clog to pass 40 mm size with guide rail and lifting chain, cables etc. all as specified in particular specification alongwith necessary SS 304 , NRV , butterfly valve etc as shown in drawing. Each pump having: i) Flow: 41.7 m3/hr ii) Head: 12m iv) MOC: Cast Iron v) Type : Submersible Sewage Pump
Supply, install, testing and commissioning of Manual Fine Bar Screens as per design /suitable to 1 MLD STP. The screen shall be with 6 mm Opening in SS 304 material as per approved shop drawing complete in all respect including all accessories whether specified or not for the successful commissioning of the plant. Having specifications as below: i) Clear spacing of bars 6mm ii) Thickness of bars 5mm iii) No of bars: 24 Nos iv) Width of screen provided : 300mm v) Width of side frame provided : 50mm vi) Width of screen channel : 400mm vii) Angle of inclination 60o viii)Blind plate height : 100mm ix) Liquid depth of screen channel provided : 500mm x) Lenght of screen channel provided (As per CPHEEO Manual) 2700mm xi) Freeboard provided : 300mm
Supply, install, testing and commissioning of Air Grid of Coarse Bubble, Lateral & Header type in SS 304 (FRP Coated 3mm thick)construction for Equalisation Tank , sludge collection sump and MBBR reactors. Non-clog type air dispersion system capable 3-5 cfm of air or as required with oxygen transfer efficiency of 5 - 6% per/meter water depth, fine bubble membrane diffusers complete in all respect with fittings, valve .support, clamps and accessories complete all as shown in drawings. Air grid when being fed by air blower of 1050 cum/ hr capacity should supply min following qty of air MBBR tank: 409cum/hr/tank Eq Tank: 172.50cum/hr Sludgre Handling Tank:22.95cum/hr
Supply, install, testing and commissioning of twin lobe, roots type Air Blowers with motor of designed capacity and head (1050 Cum / hr. of free air at 0.65 kg/cm2, or as required ) driven through V belt or directly coupled through flexible coupling to a TEFC motor of suitable HP -3 phase supply, 415V, 50 cycles and complete in respect along with necassary connection to air grid , air flow meters, silencers, pressure release valves, butterfly valve NRVs, etc as shown in drawing Air Blowers : MOC : Cast Iron Type : Oil Free positive displacement screw type Capacity m3/hr @ 6000 mm WC : 1050 Air quality : Class "O" [100% oil-free air] Drive : Direct Noise Level : < 77+/-3 dB(A) Note: Cost quoted to be inclusive of foundation and overhead canopy and fixing of equipment to the foundation by means of base plate, grouting bolt etc.Foundation shall be of PCC 1:3:6 at least 450 mm below ground and 450 mm above ground width of foundation shall be sufficient to give 100 mm clearance on both side of equipment.
Supply, install, testing and commissioning of floating media for MBBR reactors in PP construction wagon wheel design having density less than water. Having specification as below: Media Type : Cylindrical/circular shaped media -Wagon wheel design having external fins, surface area - 400 m2/m3, non toxic Material of Construction : Virgin PP, hazy transparent white Specific Gravity : 0.90-0.92 GMS/CM3 Structure : Cylindrical with external fins Voidage : >95% Minimum Media Quantity : 65.48 cum with gross media surface of 400 sqm/cum. Media surface considerace effective media surface to be 87.5% of Gross media surface should be 22916.67 sq m
Supply, install, testing and commissioning of Tube settler internal of Square Tube type lamella PVC plate in secondary clarifier. Having specification as below: Tube Modules : Square tube PVC Tube Module qty : 35 m3 Media straight height/media height at 60 degrees: 1150mm/1000mm MOC of Media : UV stabilized Virgin PVC Base Shape of Media : Hexagonal (Chevron) Shape Cross Section Area : Horizontal-120mm, Vertical-48mm Tube fitting : Tongue and Groove Thickness : 1.0mm (+0.1mm) Plan settling area ; 12-14 m2/m3 Weight : 64 kg/m3 Color : Black
Supply, install, testing and commissioning of Centrifugal non clog type Sludge recirculation Pump with motor for delivery from MBBR tank 1 and MBB R tank 2 to anoxic chamber. Pump capacity 12.5 cum @ 8.0m head or as required, complete in all respect along with valves and fitment s as shown in drawings. Having specification as below: Energy efficient IE2 motor 3 phase induc tion 440Volts, 2900 RPM, 50 Hz, IP 55 protection Capacity (Each) ; 12.5 m3/hr Head ; 8.0 m MOC : Cast Iron Type : Self-priming Centrifugal monobloc Note: Cost quoted to be inclusive of foundation and overhead canopy and fixing of equipment to the foundation by means of base plate, grouting bolt etc.Foundation shall be of PCC 1:3:6 at least 150 mm below ground and 300 mm above ground width of foundation shall be sufficient to give 100 mm clearance on both side of equipment. OHP shall be by means powder coated 0.50 mm galvalume profile sheets supported over by frame made of 50x50x5 mm MS angle ( painted with 2 coat of synthetic enamel paint over one coat of red oxide primer). OHP should be at least 1.8 mtr above foundation floor level. Earthwork cost to be included in quoted rate.
Supply, install, testing and commissioning of Hypo dosing system consisting of metering type dosing pump in PP construction and LDPE/HDPE of designed 0-6 LPH pump doser and tank capacity 200 liter or as required complete with metering, piping and valve accessories. Having specification as below: Disinfectant : Free Chlorine Chlorine Dosage : 4-5 mg/ltr Process of Dosing : Electronic metering dosing pump No of dosing pumps : 02 Nos Capacity : 0-6 LPH Each Hypo Solution Tank : 1 No Hypo Solution Tank Capacity : 200 Ltr Hypo Solution Tank MOC : PVC Note: Cost quoted to be inclusive of foundation and overhead canopy and fixing of equipment to the foundation by means of base plate, grouting bolt etc.Foundation shall be of PCC 1:3:6 at least 150 mm below ground and 300 mm above ground width of foundation shall be sufficient to give 100 mm clearance on both side of equipment. OHP shall be by means powder coated 0.50 mm galvalume profile sheets supported over by frame made of 50x50x5 mm MS angle ( painted with 2 coat of synthetic enamel paint over one coat of red oxide primer). OHP should be at least 1.8 mtr above foundation floor level. Earthwork cost to be included in quoted rate.
Supply, install, testing and commissioning of Filter Feed pumps Horizontal centrifugal non clog water transfer pumps Cl body motor, pressure gauge with isolation cock, Isolation valve, NRV on delivery line. Isolation valve, stainer (with by-pass) at suction. Mechanical seal, suitable vibration elimination pads of approved design, drain pipe with valve (25 dia) for the pump. The pump shall be suitable for 415±10% volts 3 phase AC supply along with necessary pipe fittings, valves, NRV, butterfly valves as shown in drawuings. Having specification as below: Capacity :12.08 LPS each Head @26m Note: Cost quoted to be inclusive of foundation and overhead canopy and fixing of equipment to the foundation by means of base plate, grouting bolt etc.Foundation shall be of PCC 1:3:6 at least 200 mm below ground and 300 mm above ground width of foundation shall be sufficient to give 100 mm clearance on both side of equipment. OHP shall be by means powder coated 0.50 mm galvalume profile sheets supported over by frame made of 50x50x5 mm MS angle ( painted with 2 coat of synthetic enamel paint over one coat of red oxide primer). OHP should be at least 1.8 mtr above foundation floor level.cost of Earthwork for fdn to be deemed inclusive in quoted rate.
Supply, install, testing and commissioning of vertical MSEP Dual Media filter with adequate dirt holding capacity (suitable for 3.5 Kg/Sqcm working pressure). As per manufacturer's specifications complete with initial charge filter media . The filter shall also be provided with set of internals for raw water inlet and bottom collecting system. Complete with frontal piping & Valves. Having specifications as below: Diameter of Filter : 2000mm Height : 1600mm MOC: 8mm shell/10mm dish, mild steel bituminous painted inside Filter Media: 300mm Anthracite & 500mm Sand, under bed supporting media 500mm Back wash flow: 63m3/hr for 10 mintue Back wash time: 10 mintuesx2 per day Design flow ; 43.48 m3/hr No of filter ; 1.0 No Each filter design flow : 43.48 m3/hr Design flow 43.48 m3/hr = 0.72 m3/min Filtration Rate 14.00 m3/m2/hr
Supply, install, testing and commissioning of vertical MSEP Activated Carbon Filter with adequate dirt holding capacity (suitable for 3.5 Kg/Sqcm working pressure). As per manufacturer's specifications complete with intitial charge filter media . The filter shall also be provided with set of internals for raw water inlet and bottom collecting system. Complete with frontal piping & Valves. Having specifications as below: Diameter of Filter : 2200mm Height : 1800mm MOC: 8mm shell/10mm dish, mild steel bituminous painted inside Filter Media: Granular Activated carbon, 900mm carbon depth and 600 mm under bed supporting media Design flow : 43.48 m3/hr No of filter : 1.0 No Each filter design flow : 43.48 m3/hr Design flow 43.48 m3/hr = 0.72 m3/min Filtration Rate: 12.00 m3/m2/hr Dia of filter required 2.15m Provided 2.2m
Supply, install, testing and commissioning of Electromagnetic flow metre at Inlet and Outlet of STP of suitable Dia, complete all as specified.
Supply, install, testing and commissioning of screw press feed pump, having specifications as below: Minimum flow: 4.0 m3/hr Minimum head : 10m MOC : Cast Iron Type: Centrifugal monobloc self priming Note: Cost quoted to be inclusive of foundation and overhead canopy and fixing of equipment to the foundation by means of base plate, grouting bolt etc.Foundation shall be of PCC 1:3:6 at least 200 mm below ground and 300 mm above ground width of foundation shall be sufficient to give 100 mm clearance on both side of equipment. OHP shall be by means powder coated 0.50 mm galvalume profile sheets supported over by frame made of 50x50x5 mm MS angle ( painted with 2 coat of synthetic enamel paint over one coat of red oxide primer). OHP should be at least 1.8 mtr above foundation floor level.cost of Earthwork for fdn to be deemed inclusive in quoted rate.
Supply, install, testing and commissioning of screw press for dewatering of sludge having capacity 3.0m3/hr at sludge concentration of 1% & solid at outlet 20-22%, complete all as specified.
Supply, install, testing and commissioning of DWPE dosing system consisting of metering type dosing pump in PP construction and LDPE/HDPE of designed 150 LPH pump doser and tank capacity 2000 liter or as required complete with metering, piping and valve accessories, complete all as specified. Note: Cost quoted to be inclusive of foundation and overhead canopy and fixing of equipment to the foundation by means of base plate, grouting bolt etc.Foundation shall be of PCC 1:3:6 at least 200 mm below ground and 300 mm above ground width of foundation shall be sufficient to give 100 mm clearance on both side of equipment. OHP shall be by means powder coated 0.50 mm galvalume profile sheets supported over by frame made of 50x50x5 mm MS angle ( painted with 2 coat of synthetic enamel paint over one coat of red oxide primer). OHP should be at least 1.8 mtr above foundation floor level.cost of Earthwork for fdn to be deemed inclusive in quoted rate.
Supply, install, testing and commissioning of chlorine analizer having Resolution : 0.01 mg/l, Accuracy : < 2% of full scale, Response time :T90 in 60 Sec, Temperature operting: -5 to +70oC, Sensor Electrode Material : Shaft ; Glass, Elextrode-Gold, Reference electrode -Ag/Tepox gel, Diaphragn-Ceramics, Gasket-EPDM, Sensor Automatic cleaning : ASR-Automatic Sensor cleaning System, Transmitter type: Microprocessor based programmable, Display : backlit LCD graphic 128x64 pixels, Analog output : 3 x 4 to 20mA, max 400 ohm all galvanically isolated, Enlosure MOC & protection class: Die cast aluminium & IP66/NEMA4X.
Supply, installation, testing and commissioning of rated capacity automatic power factor correction (APFC) panel oudoor type factory made of 40 KVAR capacity ready to use design confriming to relevant IS rated for short circuit rating of 25 KA, front openable and lockable by keys having lowers and air vent, gasket and totally vermin proof and suitable for 415/440 V 3 phase 50 Hz, AC and housed in elegant enclosure fabricated from minmum 3.15 mm thick CRCA sheet and min 1.6 mm thick for partitions anti corrosive coating to achieve power factor from 0.95 to 0.99 are finally powder coated in texture seimens grey RAR 7032 & as direced by Engineer-in-Charge comprising of and including following including suitable size and lenght of conductorcable from main panel to APFC panel for (a) 200 Amp capacity for phase and 100 amps for neutural copper bus bar duly insulatd with colour coated heat shrinkable sleeves and mounted on suitable DMC/epoxy insulator. (b) A Set of heavy duty capacity type MPP heavy duty, square box type, 440 volts, with output steps of 40 KVAR capcity capacitor bank in steps of 5/10/25 KVAR in any configuration to accommodate all possible set ups. (c) MCB's TP 'C' series, 415 volts, off sizes with required numbers and suitable ratings as per the capacity of capacitors.
(k) Auxiliary contractor with required quantity of 'NO & NC' (l) Auto/ Manual Switch-01 No (m) Fuse for line protection as per requirement and as approved . (n) Indicator lamp LED based with lap holder as per requirement and as approved. (o) Current transformer (CT) of ratio 200/5A, measuring class accuracy 0.50 to 1.0 for capacitor panel. (p) Incoming MCCB capacity 200 Amp, 4 Pole, 415 V, 50 c/s 25 KA fixed manual type - 1 No (r) Deturning reactor of suitable size shall be provided to maintain THD less than 7 percent.
S & F cable route marker made up of PCC block and properly painted as per approved colour (1:3:6) type. C-1 using 20mm graded stone aggregated. Size 900 mm x 300mm x 100 mm thick. (45 Cm buried in ground) with DANGER/11KV CABLE/MES or DANGER/LT CABLE/MES embossed on route marker including excavation and earth work complete all as specified. Earthwork Cost to be inclusive in quoted rate.
S&F Junction box made out 2 mm CRCA Sheet of size 200 x 160 x 100 mm duly painted and fixed with suitable MS Clamps of 3 mm thick nut bolts including - TPN copper Bus bar of suitable size, supports duly insulated and fixed for terminating single phase 2 x 6/10/16 Sq mm aluminium UG Cable including glands etc with 01 No, MCB SP, 10 KA 10 Amps complte all as specified and directed.
Supply and fixing LED street light 35 Watt 230 V, AC outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics with IP 65/66 protection complete all as specified.
M&L for three single core PVC insulated unsheathed stranded copper conductor cable drawn into steel pole of size 1.5 sq mm for connection of security/street light fitting from junction box complete all as specified and as directed
Transformer floor mounted capacity 100 KVA ,step down, outdoor type11/0.433 KV,50Hz, AC double wound core type copper wound ,oil immersed ,air naturally cooled with external cooling tubes, transformer delta connection on HV side and star connection on LV side in accordance with vector symbol DyN-11 ( vector group 4) and having tapping of ± 7.5% in equal step of 2.5 % changed by means of auto on load tap changing arrangement. The voltage regulation shall be as per IS including first fill of transformer oil as per IS-335 and including all fittings /accessories as specified in SSR Part -1 and IS -1180 the transformer should have cable box on LT side and brass bushing on HT side. The limit of temp rise after continuous full load run as specified in SSR part-I and IS -2026 shall be suitably adjusted to suit the maximum ambient temp prevailing at site all as specified
i) 01 No Cable box on LT side consisting of 03 Nos porcelain bushing with bushing brass rods and nuts washers and cable glands of suitable for reception of cable LT 1100 Volt grade XLPE insulated heavy duty including gland joint complete.(ii) HV bushing with arching horn on 11 KV side.(iii) Oil Conservator with filter type drain valve and oil level gauge.(iv) Dehydrating Breather with first filling of Dehydrating Agent .(v) Explosion Vent.(vi) THERMOMETER Pocket(vii) Two Earthing Terminal on tank body to facilitate fixing of 32x6mm GI strips.(viii) One No Thermometer Dial Type vapour pressure type having range 0-120 degree centigrade with maximum temperature indicator and re-setting device to maximum temperature including needle of temperature gauge : Max reading painted (ix) Rating plate with terminal marking plate. (x) Oil level gauge. (xi) Oil drain filter valve. (xii) Oil filling port on top cover with plug.(xiii) Air release valve/plug (xiv) 4 Nos plain solid cast steel detachable rollers.(xv) Shut off valve between conservator and bucholz relay. (xvi) First fill of transformer oil conforming to relevant IS and tested upto 60 KV dielectric strength.(xvii) Inspection cover.
(xviii) Lifting lugs and jack lifting pad support. (xix) Bi-directional plan / flanged rullers. (xx) Explosion vent with double diaphragm and sight glass. (xxi) Silica gel breather or with connecting pipe, first fill of dehydrating agent. (xxii) Hand hole of sufficient size to assess the interior of the tank.(xxiii) Cover lifting eves. (xxiv) Double float bucholz relay with trio and alarm contacts. (xxvi) Rail section and channel embedded in foundation of suitable size in and including PCC 1:3:6 type C-I plate form size 3.0x2.5x1.0 Mtr. Including ramp and necessary earth work and excavation as directed. (xxv) Oil temp indicator of approved range, including shutt of valve between conservator and main tank.(xxvi) Winding temp indicator of approved range ,including shutt of valve between Conservator and main tank. (xxvii) Drain valve with threaded adaptor. (xxviii) Filter valve with threaded adaptor. (xxix) Sample valve. (xxx) Extra bushing for neutral outside the LV side. Note: 1. The oil temperature and winding temperature gauges shall be housed on a MS box shall be 0.6Mx0.6Mx0.3M with hinged door and having glass 3 mm thick front side of the box and provision for entry of cables and compression glands. 2.Contractor shall arrange for factory visit for GE/EIC/or his Rep to check the above
Supply and install , testing and commissioning of diesel engine driven generating set with AMF PANEL Panel 100 KVA with water cooled engine for 64 KW power generation @ RPM 1500, brushless frame with silencer and Canopy for sound less mode (sound level not exceeding level specified by central pollution control board) and all engine accessories such as self starter, alternator/dynamo and 64 kW/ 100 KVA electric alternator, 415 volts, 3 phase, 4 wire,50 Hz, Voltage Regulation± 15, Insulation class H coupled to engine with suitable coupling and base frame on foundation as recommended by the manufacturer and consisting of other electrical l components, fuel tank of capacity of not less than for 12 hour run with level indicator installed on suitable steel frame with PCC foundation as per manufacturers instructions, Power Command genset Controller, fuel pipes, Dual spin on fuel filter, Dry type Air cleaner, Shutt off coil with safeties for LLOP/HWT , fuel pipes , bar metre, hour meter , oil temperature gauges, ammeter , ignition switch, radiator with cooling fan, maintenance free battery 24 V (2x12V) / 2x160 AH including suitable size of copper cable leads with terminals, all mountings, accessories and necessary foundation and AVM pads complete as per specified and directed.
(A) PRIME MOVER:- Suitable for driving 64 KW/100 KVA alternator water cooled battery start diesel Engine of suitable capacity confirming of ISO 3046 / BS 5514 BSS 649 and fuel tank suitable for 12 hrs running capacity mounted on MS frame pedestal supported with anti-vibration mounting rated for continuous running capable of taking 10% over load for one hr in any 12 hrs operation complete with (B) ALTERNATOR : 64 KW/100 KVA at 0.8 PF Brushless self excited, self regulated 3 phase 50 Hz 415 V 1500 RPM 4 wire screen protected drip proof free from simulation problems continuous rating confirming to BS 5000 complete with automatic voltage regulator 0/P voltage regulated between +/- 1% or set voltage (C) AUTOMATIC MAINS FAILURE PANEL: AMF panel for 64 KW/100 KVA DG Set fabricated out of sheet steel factory made suitable for floor mounting hinged from panel for easy accessibility with suitable rated bus bar internal wiring and with provision for connecting incoming/outgoing leads with the following accessories :- a) HRC fuse (06 Nos) of proper rating for Both in coming and MCCB of rated capacity 4 pole - (02 Nos-) for incoming
Note: (i) any fittings/fixtures which are necessary for proper functioning of the DG set shall also be deemed include in the unit rate quoted and shall be provided by the contractor without any extra cost to the Deptt. ii) Necessary foundation for installation of DG set shall be provided as per manufacturers recommendations and cost deemed to be inclusive in the rate quoted for this item. iii) All testing equipments are to be arranged by the contractor and testing shall be carried out by the contractor in presence of Engr-in-Charge and testing result duly signed by the Engr-in-charge and the contractor shall be kept in Record. iv) Rate quoted by the contractor including the rate of first filling of lubricating oil, Coolent and duct with wooden cover from DG set to AMF Panel. AMF panel must be outside the canopy. (v) Drawings/cataloged for DG Set and AMF panel got approved by the GE before ordering to the manufacturer
Supply, install, test and commission LT panel board outdoor type CPRI approved, 3 phase, 4 wire, 415 volts with 400 Amps Aluminium bus bar, prewired complete with suitable size multistanderd copper cable , and suitable CTs, indicator lamps, outdoor cubical type, IP 54, dust and vermin proof fabricated out of CRCA sheet not less than 3.15 mm thick fixed on angle iron frame of size 50x50x6mm duly powder coated, front openable double door hinged with locking arrangements complete with and comprising the following including necessary PCC platform. Note: Cost quoted to be inclusive of foundation and fixing of equipment to the foundation by means of base plate, grouting bolt etc.Foundation shall be of PCC 1:3:6 at least 200 mm below ground and 300 mm above ground width of foundation shall be sufficient to give 100 mm clearance on both side of equipment. cost of Earthwork for fdn to be deemed inclusive in quoted rate. Design of MPCP to be approved by GE before placement of order by contractor.
Note: All starter shuld have seprate enclosure and fitted in seprate compartment in panel, Alll starte should have seprate Dry run protectio, Single phase preventer, Relay , Timer and steel enclosure Note No-2 All the cable entries should be through proper metalic glandsm only Note No-3 Every starters has seprate endivdudals compartment Note: Cost quoted to be inclusive of foundation and fixing of equipment to the foundation by means of base plate, grouting bolt etc.Foundation shall be of PCC 1:3:6 at least 200 mm below ground and 300 mm above ground width of foundation shall be sufficient to give 100 mm clearance on both side of equipment. cost of Earthwork for fdn to be deemed inclusive in quoted rate. Design of MPCP to be approved by GE before placement of order by contractor.
M&L for PCC/brick work platform work for transformer of size 2 mtr x 2 mtr x 1.5 mtr in CM 1:4 as manufactrurer instructions complete all as specified and as directed . Note:- Earthwork cost to be included in Quoted rate.
Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4mm dia galvanised iron or steel wire complete all as specified and as directed
M&L for brick masonary valve pit (type A) of size .9 x .9 x .9 m (internal of chember) depth of chember to be reckoned from the top of PCC in foundation to top the MS cover as 1.25 mtr and including MS sheet cover fabricated from 3mm thick MS sheet and frame of angle irn 40mm x 40mm x 6mm with fixing arrangement, hinges and locking arrangement and painting two coat of synethetic enamel paint over a coat of red oxide primer on MS cover and frame, incuding necessary excavation and earth work in any type of soil, returning, filling in approved soil, disposal of surplus soil to a distance not exc 50 mtr, 150 mm thick PCC (1:4:8) type D-2 using 40 mm graded stone aggregate as in foundation, brick work in cement motor (1:6,) 15mm thick plastering in cement mortoar (1:4) (both internally and externally) 100mm thick PCC (1:2:4) type B1 using 20 mm graded stone aggregate as in flooring complete all as specified. Cost of earthwork deemed to be included in rate quoted.
M&L for brick masonary valve pit (type B) of size 1.2 x 1.2 x 1.2 m (internal of chember) depth of chember to be reckoned from the top of PCC in foundation to top the MS cover as 1.25 mtr and including MS sheet cover fabricated from 3mm thick MS sheet and frame of angle irn 40mm x 40mm x 6mm with fixing arrangement, hinges and locking arrangement and painting two coat of synethetic enamel paint over a coat of red oxide primer on MS cover and frame, incuding necessary excavation and earth work in any type of soil, returning, filling in approved soil, disposal of surplus soil to a distance not exc 50 mtr, 150 mm thick PCC (1:4:8) type D-2 using 40 mm graded stone aggregate as in foundation, brick work in cement motor (1:6,) 15mm thick plastering in cement mortoar (1:4) (both internally and externally) 100mm thick PCC (1:2:4) type B1 using 20 mm graded stone aggregate as in flooring complete all as specified. Cost of earthwork deemed to be included in rate quoted.
Supply and lay pipe ductile Iron , SIS including specials, Class "K-7" ,100 mm (4") dia including all joints and fittings such as elbows, bends Ts etc. The pipe length for treated water distribution complete all as specified and as directed
Supply and lay pipe ductile Iron , SIS including specials, Class "K-7" ,150 mm (6") dia including all joints and fittings such as elbows, bends Ts etc. The pipe length for treated water distribution complete all as specified and as directed
Supply and fix CI body sluice valve PN 1.6 conforming to IS of size 150 dia complete with jointing material such as rubber gasket, bolts, nuts, etc suitable for size 150 mm complete all as specified and as directed.
Supply and fix CI body sluice valve PN 1.0 conforming to IS of size 100 dia complete with jointing material such as rubber gasket, bolts, nuts, etc suitable for size 100 mm complete all as specified and as directed.
Monoblock pump set suitable for 415 V, 3 phase system having capacity 15 HP. Note: Cost quoted to be inclusive of foundation and overhead canopy and fixing of equipment to the foundation by means of base plate, grouting bolt etc.Foundation shall be of PCC 1:3:6 at least 200 mm below ground and 300 mm above ground width of foundation shall be sufficient to give 100 mm clearance on both side of equipment. OHP shall be by means powder coated 0.50 mm galvalume profile sheets supported over by frame made of 50x50x5 mm MS angle ( painted with 2 coat of synthetic enamel paint over one coat of red oxide primer). OHP should be at least 1.8 mtr above foundation floor level.cost of Earthwork for fdn to be deemed inclusive in quoted rate.
Suppy and fix GI concertina coil 610 mm dia having 50 turns and approximate weight 8.50 Kg(+5%) and coild be streched to cover a distance of 5-7 running meter complete all as specified and as directed .
Supply and install submersible pump set (non clog ) with chrome steel impeller and cutter non clog to pass 40 mm size particles , having capacity up to 2500 LPM foa an head of 10 mter and 10 HP motor capacity all as speciifed and as directed complete all as specified and as directed , Note: The cost shall be included steel wire rope with lifting pully suitbale for hanging for submersible pump in to the sewage sump as required at site (Sump Depth 10 mtr)
Supply and fix garden irrigation green hose pipe polyetylene (PE-AL-PE) composit pressure pipe including all crimp type internal sealing Plastic- metal comosite fittings ( such as elbow , tees, reducer etc.80 mm bore including suitable metal clamps with nut and bolts required to fix in outlet submersible (Sewage Pump & Onward Connection to Outlet pipe Feeding raw sewage to STP)
Supply and lay cable 3.5core 4 sqmm cable PVC insulated and unsheathed sumersible flat type with stranded copper conductor all as specified and as directed.(for supply to Submersible pump near Existing panel Near SP-2)
Supply and fix CI body Sluice valve PN 1.6 conforming to IS of size 250 dia complete with nuts,bolts,rubber gaskets etc including ,ISI marked ,including jointing material such as rubber gasket,bolts,nuts,etc suitable for size 250 mm all as specified and as directed by Eng-in-Charge
Supply and fix CI body Sluice valve PN 1.6 conforming to IS of size 200 mm dia complete with nuts,bolts,rubber gaskets etc including ,ISI marked ,including jointing material such as rubber gasket,bolts,nuts,etc suitable for size 200 mm complete all as specified and as directed by Eng-in-Charge.
Supply and fix nrv (non return valve of size 200 mm bore flanged and drilled ends complete,ISI marked ,including jointing material such as rubber gasket,bolts,nuts,etc suitable for size 200 mm all as specified and as directed by Eng-in-Charge.
Supplying and laying 65 mm bores of tubes 'medium grade' galvanised including all joints and fittings such as elbows, bends Ts etc and fixed, laid in tranches complete all as specified and as directed.
Supply and fix Cast Iron Air Valves PN 1.6 with single air Outlets, conforming to IS 14845 of size 100 mm dia bore and fixing up in Cast Iron Water supply mains of size 100 mm dia. complete all as specified and as directed
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure.
Supply an fix water garden Hydrant post of size of 25 mm dai of GI pipe and (Height of the hydrant post 0.8 mtr from ground ) in 100 MM DI pipe The cost shall be included for fixing of hydrant post including welding work for fixing of GI pipe in to the DI pipe in 100 mm and all such as fittings such as ends, sockets, elbows, unions,tees, reducing tees, adopters,socketrs, plugs, hose clips etc. of size 25 mm bore necessary nuts bolts , welding works and rubber etc complete all as specified and as directed
Supply an fix water garden Hydrant post of size of 25 mm dai of GI pipe and (Height of the hydrant post 0.8 mtr from ground ) in 65 MM GI pipe The cost shall be included for fixing of hydrant post including welding work for fixing of GI pipe in to the GI pipe in 65 mm and all such as fittings such as ends, sockets, elbows, unions,tees, reducing tees, adopters,socketrs, plugs, hose clips etc. of size 25 mm bore necessary nuts bolts , welding works and rubber etc complete all as specified and as directed
Supply an fix water garden Hydrant post of size of 25 mm dai of GI pipe and (Height of the hydrant post 0.8 mtr from ground ) in 50 MM GI pipe The cost shall be included for fixing of hydrant post including welding work for fixing of GI pipe in to the GI pipe in 50 mm and all such as fittings such as ends, sockets, elbows, unions,tees, reducing tees, adopters,socketrs, plugs, hose clips etc. of size 25 mm bore necessary nuts bolts , welding works and rubber etc, all as specified and directed
Supply an fix water garden Hydrant post of size of 25 mm dai of GI pipe and (Height of the hydrant post 0.8 mtr from ground ) in 25 MM GI pipe The cost shall be included for fixing of hydrant post including welding work for fixing of GI pipe in to the GI pipe in 25 mm and all such as fittings such as ends, sockets, elbows, unions,tees, reducing tees, adopters,socketrs, plugs, hose clips etc. of size 25 mm bore necessary nuts bolts , welding works and rubber etc complete all as specified and as directed
Supply and fix MS ERW flanged pipe nominal dia 200 mm as per IS 3589 (1981) thickness 5.0 mm , including special joints complete for delivery and side including necessary nuts bolts and rubber etc, complete with one coat of red oxide and two coat of blacj paint on ms pipe all as specified and as directed. (Header) Note: - The cost shall beinclusive for making header for connection of varios sizes of DI/GI pipe line for delivery including welding , bending work .(Header) complete all as specified and as directed
Supply and fix MS ERW pipe nominal dia 100 mm as per IS 3589 (1981) thickness 5.0 mm , including special joints complete for delivery and side including necessary nuts bolts and rubber etc, complete with one coat of red oxide and two coat of blacj paint on ms pipe all as specified and as directed. (Suction pipe) complete all as specified and as directed
Supply and fix nrv (non return valve of size 100 mm bore flanged and drilled ends complete,ISI marked ,including jointing material such as rubber gasket,bolts,nuts,etc suitable for size 100 mm complete all as specified and as directed
Supply and fix nrv (non return valve of size 150 mm bore flanged and drilled ends complete,ISI marked ,including jointing material such as rubber gasket,bolts,nuts,etc suitable for size 150 mm complete all as specified and as directed
Supply and fix CI body foot valve conforming to IS of size 100 dia complete with nuts,bolts,rubber gaskets etc including ,testing all as specified.complete all as specified and as directed
Labour for Disconnecting the existing 150mm x150 X100 mm DI pipe ,suction and delivery end of any type from the distribution line and inserting T 150x150mm and supply and fixing with new pipes of various material and sizes of pipe given in schedule complete all as specified and as directed
Supply and lay cable 1.5 sqmm cable 2 core PVC insulated and unsheathed sumersible flat type with stranded copper conductor complete all as specified and as directed
Supply, install , testing commissioning of anoxic mixer with agitator alonwith made of SS 304 shaft height of shaft 3.5 suitable motor minimum 1.49 kw , 2 HP , with flange alongwith necessary suspension arrangement made of structrual mild steel and grouting with RCC tank ( The suspension arrangement to be integrally casted wiht the RCC structure) Note: Piping network for connecting all pumps to STP units, fresh water supply to pipies to STP units and drainage pipes from STP units is included in the various items quoted above . Pipe network diagram and schedule is to be submitted by contractor as per Pirticular specifications and to be approved by GE/CWE/Accepting Officer before execution complete all as specified and as directed . Cost of pipes and connections is deemed inclusive in various rates quoted in.
Shree Construction Co.
Hydrotech Paryavaran India Pvt. Ltd.
OBEROI CONSTRUCTION CORPORATION
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .