Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.3 LAccepted-Finance GOPALPUR BANSI RANIGANJ DISTRICT PRATAPGARH | PRATAPGARH | UTTAR PRADESH | L1 | Accepted-Finance Rate quoted is lowest | |
| 2 | L2₹4.9 L+₹63,745 (14.9%)Accepted-Finance | L2 | Accepted-Finance Rate quoted is second lowest | |
| 3 | L3₹5.0 L+₹67,616.50 (15.8%)Accepted-Finance | L3 | Accepted-Finance Rate quoted is highest |
Tender Value
Refer Docs
EMD Value
₹7,000
Closing Date
9 Oct 2024, 4:00 pmClosed
SUPERINTENDING ENGINEER
SE ETC Sultanpur 400KV S/S Campus Payagipur Sultanpur
CONSTRUCTION OF 33KV ABPL SOLAR BAY-UNIT-II INCLUDING SUPPLY OF MATERIAL ALONG WITH OTHER ASSOCIATED WORKS AT 132KV S/S MUSAFIRKHANA UNDER ETD, SULTANPUR
2024_UPTCL_954902_1
T.No. 18/ETCS/2024-25
Open Tender
Electrical Works
Item Rate
60 days
Sultanpur
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
SE ETC SULTANPUR
₹7,000
Yes
23 Oct 2024
11 Sept 2024
10 Oct 2024
11 Sept 2024
9 Oct 2024
11 Sept 2024
Amount
Construction of 33KV ABPL Solar Bay unit-II including Supply alongwith other associated works at 132KV S/S Musafirkhana, Amethi with all Cost of Men; Materials; Misc. Consumables, T&Ps etc. Required for Satisfactory Completion of the Work as per Technical Specifications and Direcüon of the Supervising Engineer as per Site Requirement and Details below :
Supply of Materials
Supply of PG Clamp duly made of LM-6 Aluminium Alloy, suitable for ACSR Moose to Panther Conductors complete with 4No. 16x90mm size GI Bolts, Nuts, Spring & Plain washers as per Technical Sqecification & Sample.
Supply of PG Clamp duly made of LM-6 Aluminium Alloy, suitable for ACSR Panther to Panther Conductors complete with 3No. 16x75mm size GI Bolts, Nuts, Spring & Plain washers as per Technical Sqecification & Sample.
Supply of 33KV Isolator Bi-Metallic Terminal Connectors duly made of LM-6 Aluminium Alloy alongwith Bi-Metallic Sleeve Plate suitable for Twin ACSR Panther Conductor with 4No, 12mm size GI Bolts, Nuts, Spring & Plain washers as per Technical Sqecification & Sample.
Phase Plate in sets of red, blue and yellow
Name Plate Standard Size
Retro Reflective bay sign Board
150 Watt LED light complete fitting of philips/CGL/Havells make with 2 year statndard warantty card
50x6 mm MS Flat
25x6 mm MS Flat
36KV CT Junction Box
Flexible Copper bond 16mm dia 500mm length
Carriage of Materials
Sorting, Weighting and Loading of Galvanized Sub Station Structures on private Truck at EFU Naini, Allahabad
Safe Transportation of Galvanized Sub Station Structures by Private Truck Arranged by the Contractor from EFU Naini, Prayagraj to 132KV S/S Musafirkhana, Amethi (210 Km. approx.) including Toll charges.
Unloading, Sorting & Proper Stacking of Galvanized Sub Station Structures from Private Truck at store yard of 132KV S/S Musafirkhana.
Carriage of Misc. Items like CTs, PTs, CB, Isolators, Control Cables, Conductors, M.S. Earthing Strips etc. from Designated Primary Sub Station within 250 Km Distance (ETC-Sultanpur and ETC-Gonda) to 132KV S/S Musafirkhana, Amethi including its Loading and Un-Loading.
Erection of main and auxiliary structures
Erection of auxiliary structure required for installation of isolator, CTs, PTs, LAs, CVTs and other equipments. The job consists of shifting of all material i e. Structure part, nut&bolts, washers etc. from store to site of erection, erection to structure as per relevant drawing and practices using flat and spring washer with each bolt matching of holes, cutting, matching of members if required shall also be done by the contractor without any extra cost to complete the work satisfactorily completion of work shall be arranged by the contractor at his own cast.
Erection of following Equipments for construction of 1 No. each 33 K.V. Feeder Bays at 132 K.V. Sub Stations Musafirkhana as per instruction manual of various equipments & Technical Specifications including shifting of Equipments from Store to Erection site including all other associated works for completion of Erection work satisfactorily :
33 K.V. C.B. with Structure
33 K.V. C.T. (400-200/1 A )
33 K.V. C.T. Junction Box
33 KV PT (1phase)
33 KV PT Junction Box
33 K.V. Bus Isolator without Earth Blade
33 K.V. Line Isolator with Earth Blade
Erection of CRP Panel including shifting etc.
Erection of new 33KV Tripple Feeder Control and Relay Panel in Control Room of 132 KV S/S Musafirkhana, Amethi including grouting, earthing & termination of control panels, as per cable schedules including Providing & Fixing of Cable Glands of appropriate sizes and ferrules etc. with all other associated works as per technical specification.
Jumpering, Stringing, Destringing, Extension etc. of various Equipments/ Bus Sections
Jumpering of various equipments with Twin ACSR "Panther Conductor " in new 33 KV ABPL Solar Bay Unit-II after due cutting and bending of conductor and fixing & tightening etc of the Conductor/ Clamps/Connectors/Spacers etc.
Cutting, Straightening, Laying 700 mm below inside ground & above ground of 50 mm x 6 mm size & 25 mm x 5 mm size M.S. Flats to be provided by Department as per requirement at 132 K.V. Sub Stations Musafirkhana for Earthing of newly erected Aux. Structures, Equipments, C&R Panel & Cable Trenches including welding with main Earthmat and with the object to be earthed, excavation of Trenches, its back filling, Painting of Earthmat above ground level in Bus Green colour including all other associated works to complete the Earthing work satisfactorily, as per Technical Specifications :
Earthing of Aux. Structures & Equipments with 50 mm x 6 mm size M.S. Flat
Earthing of new Cable Trench Racks / Peak Mast with 25 mm x 6 mm size M.S. Flat
Earthing of control panels at 2 point each panels
Painting of Earthing strips above ground level with one coat of Red oxide and two coat of synthetic/ enamel paint and with black Bitumen paint below ground level as per etails below:
50x6 mm (in green color)
25x6 mm (in black color)
Laying of Following sizes of Control Cables in the Cable Trenches from Control & Relay Panels in Control Room to various Equipments, Junctions Boxes etc. in Switchyard as per Cable Schedule, its saddling with 25 x 3 mm size including Carriage of Cable Drums from Stores to work site & Shifting back to Stores the balance Cable including all other associated works to complete the job satisfactorily as per Technical Specifications :
Laying of 2 x 2.5 mm2 size Control Cable
Laying of 4 x 2.5 mm2 size Control Cable
Laying of 6 x 2.5 mm2 size Control Cable
Inter-connection & Termination of above laid Control Cables between new 33 K.V. Triple Feeder C&R Panel and erected equipments i.e. C.B., C.T., C.T. Junction Box, P.T., P.T. Junction Box including making necessary holes in Gland Plates or Boxes wherever required alongwith supply & fixing of Cable Glands of appropriate size & providing of Ferrules for each core of the Cables & its termination with crimping type Copper Lugs alongwith preparation of Inter-connection Drawing and Commissioning of the Panel / Feeders in co-ordination with T&C Wing including providing of 2 Sets of Hard Copies of as executed Inter-connection Drawing including all other associated works to complete the job satisfactorily as per Technical Specifications (1 Job each for each Bay).
Erection of SAMAST Energy Meter and Data communication work
Installation of new 3P4W, 0.2s accuracy class Interface Energy Meters (one Main and Check Meter)
Necessary interconnection from data transmission of already installed SAMAST compliant meters to Lan switch upto DCU/Gateway and all other H/W, S/W per No.
Installation of communication cable (CAT-6 alongwith necessary hardware wherever required in between Energy meter to Lan switch to SDH equipments upto DCU/Gateway and all other H/W, S/W per No.
Installation of OFC cable armoured (6P) in HDPE conduit pipe 32mm.
Installation & commissioning of Common Metering cubicles for Meters, DCU, switch for 2 IEM
Pilferproofing work for metering
Providing & Laying pilfer proof of following size B-Class Jindal/JTC/TATA or other standard make ISI approved G.I. pipes complete with assembly such as bend, tee, socket, clamps etc. including cost of threading, welding, earth work, cutting bricks, filling the trenches/brick etc required for completion of workas per site requirement with all material, labour, T&P complete. Laying control cable in the G.I. pipe ( from 33KV CT & PT to 33KV C&R Panel) completely covered up to termination point of both ends as per requirement, termination of above cable at both ends including cost of gland, ferrules etc. only control cable will be the provided by department.
Earthing of laid GI pipe welding with cable racks by spot welding at two points and painting of welded points to be done at spot with zinc paint.
Switchyard Lighting
Providing of Junction Box of.size 280 x 225 x 150 mm duly made of 16 SWG Sheet and Painted with Smoke Grey Colour Synthetic Enamel Paint and Fitted with 1 No. 6 Amp. SP MCB on Anodized M.S. Channel, 1 No. Bakelite Fuse Fitting with 6 Amp. NS 6 type HRC Fuse, 1 No. Copper Neutral Link, Bakelite Terminal Block of 4 Terminals, Cable Glands suitable for 2C / 4C x 2.5 Sq.mm size Incoming / Outgoing Control Cables etc., then Installation of Junction Box on G.I. Column Structures at designated Height with the help of suitable M.S. Clamps alongwith Earthing of the Junction Box with 12 SWG G.I. Wire including Cable Termination with Satisfactory Testing & Commissioning.
Providing & Fixing of G.I. Pole Bracket duly made of 40 mm dia. 1.2 Meter Long 'B' Class Pipe and Bent at one end by Quarter Circle in 1.0 Meter at an Angle of 30 degree for Fixing of 125 Watt LED Street Light Luminaries Fitting on G.I. Column Structure with the help of M.S.Clamps.
Laying of 2C x 2.5 Sq.mm. size Control Cables form Junction Box to LED Street Light Luminaries Fittings through Inside the M.S. Pole / GI Stricture including necessary Fixing of Cable on GI Structure.
M/S SHRI RAMRAJ TRADERS
M/s Janta Charan
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .