HQ CWE JAMMU
HQ CWE JAMMU PIN 900172 c/o 56 APO
PROVN OF 250 KVA TRANSFORMER AT DAMANA UNDER GE JAMMU
2021_MES_469828_1
CWE/JP-38/2021-22
Open Tender
Support/Maintenance Service
Item Rate
180 days
HQ CWE JAMMU
Class E Cat b(ii)
9 documents required · 9 mandatory
₹500
Yes
Yes
24 Nov 2021
21 Aug 2021
11 Oct 2021
21 Aug 2021
4 Oct 2021
20 Sept 2021
Amount
Supply,installation,testing and commissioning transformer step down outdoor type copper wound , oil cooled IP-43 plinth mounted powder coated capacity 250 KVA CL-I with latest feature complete with standard fitted HT 11 KV 3 Phase LT 433 V 3 phase 4 wire,50 C/S oil immersed naturally cooled externally cooling tube delta connection on primary HT 11 KV side and star connection on secondary LT 433 V with tapping at +/- 2.5% to +/- 5% & +/- 7.5% on HV side and to be charged by means of hand operated off load/lap changing gear including first filling of new transformer oil of dielectric strength not less than 60 KV with all fiiting and accessories such as LT box at LT side,silica gel,brather,oil level indicator, conservator tank with oil level indicator,drain out valve(oil tank), exhaust vent,air release valve,temp gauge and cast iron wheel etc complete level-2 as per IS-1180(Part-1):2014,complete all as specified and directed.
XLPE insulated, screened, PVC bedded,galvanised steel strip or wire armoured, electric power cables (heavyduty) withaluminium conductor, 11000 volts, grade cross sectional area 95 sq. mm 3core complete all as specified and directed.
Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm to 120 sqmm complete all as specified and directed.
Construction of Plateform for installation of transformer with and including Earth work, Brick work, PCC, RCC, Plastering, chain link fencing, gate etc all as shown in Drawing No CWE/TD-230/2021 Sheet 1/1 dated 23 Jun 2021, complete all as specified and directed.
XLPE cable insulated screened PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 11 KV grade with stranded aluminium coductor of size 300 Sqmm 3.5 core and including suitable size of lugs all as directed by Engr-in-Charge.
Earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below ground level connected to galvanized iron strip 32 x 6 mm size by mean of nut/bolt and washer of galvanized iron or steel as shown in electrical plate No 5 including 40 mm bore GI tubing for protection of earth strip upto test point of SSR part I including necessary excavation and earth work GI pipe 20mm bore light grade for watering and GI 15mm bore light grade pipe for protection of GI earth wire etc, PCC chamber with RCC cover in cement concrete 1:2:4 Type B1(20mm graded stone aggregate), funnel, wire mesh, charcoal dust, salt layers each layer thickness should be 15 cm (layer start from below the electrode plate to above plate) etc, connected to LT panel board as indicated including testing complete all as specified and as directed.
Earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below ground level connected to galvanized iron wire 4 mm dia by mean of nut/bolt and washer of galvanized iron or steel as shown in electrical plate No 5 including 20 mm bore GI tubing for protection of earth wire upto test point of SSR part I including necessary excavation and earth work GI pipe 20mm bore light grade for watering and GI 15mm bore light grade pipe for protection of GI earth wire etc, PCC chamber with RCC cover in cement concrete 1:2:4 Type B1(20mm graded stone aggregate), funnel, wire mesh, charcoal dust, salt layers each layer thickness should be 15 cm (layer start from below the electrode plate to above plate) etc, connected to LT panel board as indicated including testing, complete all as specified and as directed.
Replacement of lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp suitable for 11 KV all as specified and directed.
Replacement of switch air break gang operated triple pole mechanically operated from ground level, mounted on insulators and steel frame (12 insulator type) outdoor type suitable for vertical installation single break provided with locking arrangement consisting of MS channel, HT post top insulator with drop out fuses operating rod 25mm bore GI pipe medium grade confirming to relevant IS, current rating 200 Amp and voltage 11 KV including jumpering, lead of wire/cable as directed at site including taking down old/ unserviceable switch, complete all as specified and as directed.
Supply , fixing , connecting commissioning and testing of Automatic and manual operation power factor improvement panel of capacity 100 KVAR for 250 KVA Trasformer including interconnection with LT panel with appropriate size of electric cable for transformer (Outdoor/Indoor) type panel factory made, weather proof , dust and vermin proof (IP54/IP 42) suitable for 1100 V/440 V grade 3 phase 50 HZ AC supply floor mounted , fabricated out of 14 SWG MS sheet and having four Nos angle iron legs made out of 40 x 40 x 6mm, 60 cm long angle iron below frame with front door and Side/Back opening having locking arrangement prewired with copper conductor PVC insulated flexible wire size 1.5 sq mm / extension strips and connected with suitable size thimbles , lugs duly painted with Light grey epoxy powder coating after suitable chemical treatment , legs duly embedded in ground in PCC 1:3:6 type C-1 (using 20 mm graded crushed stone aggregate) of suitable size including locking arrangement suitable for mounting , with required sheet metal enclosures, thimbles and including following items :-
Incommer MCCB 250 Amp , Three Pole, Thermal Magnetic release with adjustable O/L , Adj S/C Setting Class II Front Face, 36KA rupturing capacity, Ics=100%Icu, Isolation with Positive Break Indication with Double Break Contacts, Standard Extended Rotary Handle, Seperator, Phase Barrier.
Metering Section- Digital Ammeter (0-300) Amps, digital Volt Meter (0-500) Volts, RYB Indicating Lamps ,1 Set Control fuses, CTs. 3
Insulated Busbar of Aluminium of 300A Capacity for 3 phase, fixed on Insulators, Busbar Should be PVC Sleeved with red. Yellow. Blue Colour, Busbar Support should be of smc/dmc - 1 set.
Multi 12 Step 440V, 5A (144 x 144) microprocessor based power factor controller provided in the common module for target power factor setting, automatic adjustment of dead bank ratio, digital power factor display.
Ventilating fans of reuiredd size to dissipate the heat liberated by capacitor unites complete with automatic switching on/off of fans depending upon the temperature of the pane; 230vac 1500rpm, 160cu.m/h flying leads
Automatic Power Factor controller steps Relay Micro proccessor based for switchting ON and OFF of capacitors to Display of voltage, current,Active power ,apparent Power display of COS Ø ,THD voltage, THD current,alarm indication for defective step,low power factor and axcess temperature.The relay having volt free c/o contact,automatic detection and uses of optimum capacitor capable of 4 Quadrant operation and any phase offset requirement.Switching programm :LIFO combi Filter ,manual mode built in under and over voltage release with auto reset large voltage input band of 90V to 440 volt ,45 to 65 HZ,current measuring 10MA-5A suitable for CT x/1A andx/5A commissing without additional setting and programming.Three decimal power reading .Phasing out of fault capacitor bank Automatically.
All accessories prewired with suitable size copper Wire with stand high temperature, housed in cubical panel made out of 14 swg thick MS sheet factory made duly powder coated front and rear door open able with locking arrangement complete with foundation as required or recommended by manufacturer.
Anti climbing device spike type febricated out of MS bars (Round, square and flat) including nut, bolts, washer and welding in two halves made to shape to suit the cross section of the pole, complete all as specified and as directed.
Danger notice plate of 1.6 mm thick mild steel sheet vitreous enamelled white, with letter, figures and conventional skull and bones in signal red and fixed with M.S clamps, bolts and nuts of approved size for HT, 25 x 20 cm size, complete all as specified and directed.
GI tubing light grade of 80mm bore incl all accessories for cables protection/Mechanical protection, laid under plinth/floors/path culverts with complete accessories such as bends/sockets/reducers/saddles incl necessary threading/drilling works all as specified and directed of sizes (MS work will be measured under respective item in schedule)
Supply, installation, testing and commissioning LT panel powder coated vermin and weather proof of suitable size for 3 Phase 415 volt , outdoor double door type made out 3.15 mm thick CRCA sheet with angle iron frame of size 50x50 x6 mm cubical type front and back door operated complete with aluminium bus bar 600 Amp 4 way fitted on DMC insulation with color coding and internal panel with suitable size copper cable FRLS powder coated , with IP 54 as per IS 13947 protection, fault rating 50 KA/1Sec, complete and including with following items:-
MCCB 4 Pole, current rating 400 Amp, with adjustable thermal magnetic setting 70%-100% breaking capacity 36KA at 415V,50Hz, - 01 No as incomer
MCCB 4 Pole, current rating 125 Amp, with adjustable thermal magnetic setting 70%-100% breaking capacity 25KA at 415V,50Hz, - 03 Nos as outgoing
MCB SPN 4 Pole, current rating 32 Amp, with adjustable thermal magnetic setting 70%-100% breaking capacity 25KA at 415V,50Hz, - 01 No as outgoing
LED indicating Lamp-01 Set
Amit Enterprises
M/S SHREE KRISHANA ENERPRISES
vishesh engineers
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .