Loading…
Loading…
Tender Value
₹1.7 Cr
EMD Value
₹2.4 L
Closing Date
27 Feb 2026, 1:00 pmClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
Above/Below/Par
TECHNICAL
15 conditions · 4 needing a document upload
Clause Regarding GST: (a) All the Bidders/tenderers should ensure that they are GST Compliant and their quoted tax Structure are as per GST LAW.(b) Tenderer Should Furnish their GSTIN numbers representing the States in Which they are registered GST, along with address of Registered Office.(c)The Contract is under GST Act and rules as applicable time to time.
Financial Eligibility Criteria: The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. Annual Contractual Turnover Data for the Previous 3/4 Years should be submitted as per Annexure-IX.(Annexure- VIB of Tender Documents)
43 conditions · 11 needing a document upload
Check List: The tenderer(s) would fill up the check list, as per Annexure-XXIII to ensure that they are submitting the complete tender offer.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Augmentation of 33KV Rly feeder from 132/33 KV Dibrugrah GSS to DBRT power house , augmentation of 11KV network in Bogibeel area at TSK Division.
LV-T-14-TSK-933
LV-T-14-TSK-933
Open
Works - General
12 Months
Tinsukia, Assam
₹0
₹2.4 L
27 Feb 2026
5 Feb 2026
100 items across 2 schedules
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 1,46,82,484 | ||
| — | 5200.00 | — | — | ||
| Supply, drawing, strengthening and stringing of ACSR conductor 6/1/4.09 mm (Racoon) on HT overhead lines, including laying of conductor on ground, lifting and placing on poles, tensioning with approved tension clamps, binding on insulators, and providing jumpers asrequired. The work also includes supply and fixing of all associated fittings and accessories such as tension clamps, nuts, bolts and hardware, ensuring standard sagging in each and every span. The work shall be carried out complete in all respects as per relevant specifications, safety norms and directions of the Supervisor-in-Charge. | — | — | — | 3,25,572 | |
| — | 60.00 | — | — | ||
| Supply, excavation, erection, testing and commissioning of 12-metre long GI tubular pole of type SP-64, having base diameter 219.1 mm, middle diameter 193.7 mm and top diameter 165.1 mm, with minimum thickness of 4.85 mm at base and middle and 4.50 mm at top, and approximate weight of 292 kg. The work includes supply of all foundation materials and erection of the pole in cement concrete foundation of mix 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate of 40 mm nominal size), including excavation of pit, centering and shuttering, proper alignment, concreting, curing, refilling and disposal of surplus earth, complete in all respects as per site conditions and directions of the Supervisor-in-Charge. | — | — | — | 32,81,580 | |
| — | 40.00 | — | — | ||
| Supply, fitting and fixing of GI channel of size 100 x 50 x 6 mm, 2500 mm long, on tubular pole for pole structure, including provision of necessary MS/GI clamps of size 50 x 6 mm. The work includes drilling of required holes on pole/channel, supply and fixing of all associated accessories such as nuts, bolts, washers and hardware, proper alignment and secure fastening. The item is complete in all respects as per approved drawings, site conditions and directions of the Engineer-in-Charge. | — | — | — | 45,680 | |
| — | 50.00 | — | — | ||
| Supply, fitting and fixing of GI channel of size 100 x 50 x 6 mm, 1500 mm long, on tubular pole for pole structure, including provision of necessary MS/GI clamps of size 50 x 6 mm. The work includes drilling of required holes on pole/channel, supply and fixing of all associated accessories such as nuts, bolts, washers and hardware, proper alignment and secure fastening. The item is complete in all respects as per approved drawings, site conditions and directions of the Engineer-in-Charge. | — | — | — | 34,250 | |
| — | 50.00 | — | — | ||
| Supply, fitting and fixing of GI channel of size 100 x 50 x 6 mm, 300 mm long, on tubular pole for pole structure, including provision of necessary MS/GI clamps of size 50 x 6 mm. The work includes drilling of required holes on pole/channel, supply and fixing of all associated accessories such as nuts, bolts, washers and hardware, proper alignment and secure fastening. The item is complete in all respects as per approved drawings, site conditions and directions of the Engineer-in-Charge. | — | — | — | 6,850 | |
| — | 20.00 | — | — | ||
| Supply, fitting and fixing of GI angle of size 50 x 50 x 6 mm, 3500 mm long, including cutting, drilling of holes, and supply and fixing of all necessary clamps, brackets, nuts, bolts, washers and accessories. The item is complete in all respects for proper mounting on pole/structure as per approved drawings, site conditions and directions of the Engineer-in-Charge. | — | — | — | 22,620 | |
| — | 30.00 | — | — | ||
| Supply, fitting and fixing of GI angle of size 50 x 50 x 6 mm, 3000 mm long, including cutting, drilling of holes, and supply and fixing of all necessary clamps, brackets, nuts, bolts, washers and accessories. The item is complete in all respects for proper mounting on pole/structure as per approved drawings, site conditions and directions of the Engineer-in-Charge. | — | — | — | 29,070 | |
| — | 50.00 | — | — | ||
| Supply, fitting and fixing of GI angle of size 50 x 50 x 6 mm, 2000 mm long, including cutting, drilling of holes, and supply and fixing of all necessary clamps, brackets, nuts, bolts, washers and accessories. The item is complete in all respects for proper mounting on pole/structure as per approved drawings, site conditions and directions of the Engineer-in-Charge. | — | — | — | 32,300 | |
| — | 120.00 | — | — | ||
| Supply, fitting and fixing of 33 kV polymeric type pin/post insulator (10 kN / 12.5 kN) complete with hot-dip galvanized pin/post, nuts, bolts, washers and all accessories, made of FRP core with silicone rubber housing, suitable for outdoor overhead line application, including proper mounting, alignment and binding of conductor, complete in all respects as per IS 16603, IS 731, IEC 61109 and IEC 60383 and as per directions of the Engineer-in-Charge. | — | — | — | 99,000 | |
| — | 60.00 | — | — | ||
| Supply and erection of a set of three 33 kV polymeric disc insulators (70 kN), ball and socket type, for strain/suspension application on overhead lines, complete with hot-dip galvanized steel fittings including yoke plates, U-bolts, arcing horns, strain/suspension clamps, bolts, nuts, washers, cotter pins and all associated hardware.The insulators should be of high-quality polymer with FRP core and silicone rubber housing, resistant to UV, tracking, erosion and pollution, with electro-mechanical failing load of 70 kN and adequate creepage distance for 33 kV system.The work includes proper assembly of the string, correct tensioning, alignment, conductor clamping and safety locking of fittings, complete in all respects as per IS 16603, IEC 61109, IEC 60383, IEC 60120, approved drawings and directions of the Engineer-in-Charge. | — | — | — | 1,69,500 | |
| — | 4.00 | — | — | ||
| Supply and erection of single piece, gapless (non-linear metal oxide) type Lightning Arrester suitable for 3-wire, 33 kV overhead lines, with rated voltage 30 kV (rms), nominal discharge current 10 kA (station class), complete with hot-dip galvanized mounting/clamping arrangement, G.I. bolts, nuts, washers and all accessories.The arrester shall be polymer housed, weatherproof, UV and pollution resistant, suitable for outdoor installation.The work includes proper mounting on structure, earthing connection, alignment and testing, complete in all respects as per IS 3070 (Part 3), IEC 60099-4 and as per directions of the Engineer-in-Charge. | — | — | — | 69,076 | |
| — | 10.00 | — | — | ||
| Supply and erection of hot-dip galvanized stay set for 33 kV overhead lines complete with 19/20 mm dia x 1.8 m long stay rod, anchor plate of size 450 x 450 x 7.5 mm thick, thimble, stay clamps, turnbuckle (20 mm x 600 mm), 7/4.00 mm dia G.I. stay wire and 33 kV strain insulator, embedded in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate, 40 mm nominal size) foundation including excavation, backfilling and compaction, complete in all respects as per IS 2062, IS 5621, IS 2141, IS 2486, IS 731, IS 456, IEC 60383, approved drawings and directions of the Engineer-in-Charge. | — | — | — | 54,660 | |
| — | 200.00 | — | — | ||
| Supply, laying, connection , testing and commissioning of 33 KV HT , Single Core ,120 SQ. mm compact circular aluminium conductor, conductor screen with extruded semi conducting compound, , XLPE insulated , insulation screening with extruded semi conducting compound in combination with copper tape ( 0.3KA for 1 sec) , cores laid up, innersheath of PVC tape , galvanised steel flat strip armoured , and overall pvc sheathed cable conforming to is 7098 / (part-ii) 1985 with the latest amendments. For cable laying Excavation of earth depth 0.90 Mtrs. into breadth 0.508 Mtrs. below the ground level and a layer of course sand of 7.5 CM thickness shall be spread over the ground before laying the cable and the cable shall be covered with a layer of course sand of 7.5 CM thickness. The bottom of cable trench shall be leveled and got rid of any sharp material. Above the Layer of Course Sand 3 inch Size Brick is to be provided for protection of cable. Cable route markers to be provided at an interval not less than 50 Mtrs. All conditions to be fulfilled as per DRG No : PCEE/ELG/DRG/2024/2 Dtd 04.10.2024. | — | — | — | 4,79,600 | |
| — | 6.00 | — | — | ||
| Supply, fitting, and fixing of heat-shrinkable outdoor type cable termination kit for 33kV single-core 120sq.mm cable, complete with insulation, sealing, earthing, installed and tested as per IS 13573 / IEC 60502-4 standards. | — | — | — | 48,900 | |
| — | 10.00 | — | — | ||
| Erection of earth by 50 mm dia 3 Mtrs. long (3.6 mm thickness) GI pipe and 32x6 mm GI strip-5 Mtrs,GI nuts, bolts including masonry materials for earthing pit, salt, charcoal etc. and construction of earth pit covered with RCC cover slab 12.7 mm thickness and watering pipe per Drawing No PCEE/ELG/DRG/2024/1 Dtd 30.09.2024 | — | — | — | 52,680 | |
| — | 2.00 | — | — | ||
| Supply, installation, testing and commissioning of 11 kV, 3-phase, 50 C/S, outdoor type, porcelain clad Vacuum Circuit Breaker (VCB) of rated continuous current 1250 A and short circuit breaking capacity 25 kA, complete with spring/motor charged operating mechanism, manual and electrical trip/close, two independent trip coils such that on failure of one the other shall operate, suitable for control voltage as per site requirement, anti-pumping relay, closing coil, control wiring, auxiliary contacts, electrical and mechanical interlocks, ON/OFF position indicators, mechanical operation counter, mounting structure, base frame, hardware, earthing connections, and all associated accessories and auxiliaries, conforming to IEC 62271-100 / relevant IS standards and as per attached/approved technical data sheet, erected, tested and commissioned complete in all respects as directed by the Engineer-in-Charge. | — | — | — | 6,11,606 | |
| — | 2.00 | — | — | ||
| Supply, installation, testing and commissioning of 11 kV Control & Relay Panel for Vacuum Circuit Breaker (VCB), indoor, floor mounted, metal clad, dust, moisture and vermin proof, complete with numerical protection relays comprising Over Current Relay (50/51), Earth Fault Relay (50N/51N), Master Trip Relay, trip circuit supervision relay, lockout relay (86), auxiliary relays for transformer oil and winding temp alarm and trip along with Buchlz relay protection, DC supply distribution with MCBs/fuses, meter as required for measuring parameter such as V,I,KVA,KVAR,KW and Current etc.,control switches, selector switches, indication lamps, hooters, annunciation windows, panel illumination lamp, space heater with thermostat, mimic diagram, name plates, terminal blocks, ferruled wiring, cable glands, earthing, module mounting structures, communication port (RS-485/Ethernet) for SCADA/RTU interface, suitable for control voltage as per site requirement, conforming to relevant IS/IEC standards IS:3427,IS:8623,IEC:62271-200,any other IS Standard applicable and as approved technical data sheet by railway authority, erected, tested and commissioned complete in all respects as directed by the Engineer-in-Charge. | — | — | — | 9,79,400 | |
| — | 2.00 | — | — | ||
| Supply, installation, testing and commissioning of 11 kV, outdoor, tank type, oil cooled, single phase wound primary Current Transformer set (comprising of 3 units for 3-phase system), with CTR 200-100/5-5-5 A, Core-1: 0.5 class, 30 VA, Core-2: 5P10 class, 15 VA, Core-3: PS class with Vk 150 V and knee point 75 V, short time thermal current 25 kA for 1 second, BIL 70 kV (1 min power frequency) / 170 kVp impulse, complete with porcelain bushings, oil filled tank, secondary terminal box with shorting links, mounting structure, clamps, hardware, earthing connections and all standard accessories, conforming to IS 2705 / IEC 61869 and as per approved technical data sheet, erected, tested and commissioned complete in all respects as directed by the Engineer-in-Charge. | — | — | — | 2,40,908.8 | |
| — | 2.00 | — | — | ||
| Supply, installation, testing and commissioning of 11 kV Potential Transformer (PT) set (comprising of 3 single phase units for 3-phase system), outdoor type, of ratio 11,000 V / 110 V, accuracy class 0.5 / 3P, burden 50 VA, insulation level 28 kV (1 min power frequency) with 75 kVp impulse withstand, oil immersed / resin cast, complete with primary & secondary fuses, terminal box, secondary MCBs, mounting structure, clamps, hardware, earthing connections and all accessories, conforming to IS 3156 / IEC 61869 and as per specification , erected, tested and commissioned complete in all respects as directed by the Engineer-in-Charge. | — | — | — | 2,35,811.2 | |
| — | 600.00 | — | — | ||
| Supply, laying, testing and commissioning of copper control cable, multicore round, 10 core x 2.5 sq.mm, 650/1100 V grade, XLPE insulated, cores laid up, PVC inner sheathed, armoured, extruded PVC outer sheathed (Type ST2), conforming to IS 7098 (Part-1):1988 or latest, complete with laying in trenches / trays / conduits, dressing, termination with suitable copper lugs, glands, ferrules, testing and all labour, tools and plants, complete in all respects as directed by the Engineer-in-Charge. | — | — | — | 4,96,200 | |
| — | 400.00 | — | — | ||
| Supply, laying, testing and commissioning of copper control cable, multicore round, 4 core x 2.5 sq.mm, 650/1100 V grade, XLPE insulated, cores laid up, PVC inner sheathed, armoured, extruded PVC outer sheathed (Type ST2), conforming to IS 7098 (Part-1):1988 or latest, complete with laying in trenches / trays / conduits, dressing, termination with suitable copper lugs, glands, ferrules, testing and all labour, tools and plants, complete in all respects as directed by the Engineer-in-Charge. | — | — | — | 1,38,000 | |
| — | 4.00 | — | — | ||
| Supply, fitting, fixing of 33 KV, 400 Amps, 25KA Air Break vertical mounting Gang operating switch. The Gang Operating Switch Shall conform to the following standards: (i)IS- 9920(PartI to V) (ii) IS 2544/1973 (iii)IS 2633.The Insulators should be 22 KV / 24 KV class (for 33 KV AB Switches) Post Insulators complete with pedestal cap duly cemented to be used in the AB Switch Set conforming to IS-2544/1973. The operating mechanism shall be suitable for manual operation from the ground level and shall be so designed that all the three phases shall open or close simultaneously. The Switches shall be robust in construction, easy in operation and shall be protected against over travel or straining that might adversely affect any of its parts. The required base M.S. Channel, phase coupling rod, operating rod with intermediate guide braided with flexible electrolytic copper, tail piece of required current carrying capacity and operating mechanism with ON' & OFF' positions shall be provided. The operating rod shall be medium gauge of 32mm diameter nominal bore G.I. pipe single piece 6 meters. The phase coupling rod for gang operation shall medium gauge 25mm dia nominal bore G.I. Pipe. Rotating post insulators shall be provided with suitable bearing mounted on a base channel with 6 mm thick thrust collar and 6mm split pin made out of stainless steel. The operating down rod shall be coupled to the spindle (minimum dia - 32mm) for gang operation through another suitable bearing by two numbers 10mm dia through stainless steel bolts with double nuts. The post insulators should be fixed with the base channel using Galvanized Nuts and Bolts. Suitable arcing horns shall be provided for breaking the charging current horn shall be made of 10 mm dia G.I. Rod with spring assisted operation. The required Test certificates of the Gang operated switch should be provided. | — | — | — | 1,16,468 | |
| — | 2.00 | — | — | ||
| Supply, fitting, fixing of 33 KV Drop out fuse, 400 Amps, 3 pole with 4 Nos 22/24KV post insulator per phase . The Drop Out fuse unit shall conform to the following standards: (i) IS- 5792- 1973 (For high voltage expulsion fuses & similar fuses) (ii)IS-2544-1973 ( for porcelain post insulators) (iii) IS-9385-1979 or its latest amendments if any. (iv) IS-2633-1979 ( For Galvanization of ferrous parts ). The Drop out Fuses shall have adjustable arcing horns made of solid copper rod having 8.23 mm dia. The horns shall be fitted with screwing devices with flynuts for fixing and tightening the fuse wire. It shall have robust terminal connector 5s of size 80mm x50 mm x 8 mm made of copper casting ( 95% minimum copper composition) duly silver plated with two numbers of 12mm dia brass bolts and double nuts with flat brass washers. The connector should be capable of connecting crimp able conductor up to 232 Sq.mm. size (ACSR/ AAAC) with bimetallic solder less sockets .The Drop Out Fuse Set shall suitable for horizontal mounting on sub-station structures. . All metal (ferrous) parts shall be galvanized and polished. Only post insulator (original cemented and not pin insulators shall be used for the Drop Out Fuse Set. | — | — | — | 30,178 | |
| — | 45.00 | — | — | ||
| Dismantling of existing old MS tubular poles, including lowering, removal from foundation, stacking at site/store as directed, and disposal of debris, complete in all respects as per directions of the Engineer-in-Charge. | — | — | — | 1,19,790 | |
| — | 2.00 | — | — | ||
| Supply, installation, testing and commissioning of 3 pole, double break, turn & twist, horizontal outdoor type isolator for 33 kV system, rated voltage 33/36 kV, continuous current 800 A, short time withstand current as per IEC 62271-102, complete with manual gear-operated operating mechanism for smooth and easy gang operation, interconnecting operating shaft, base frame, MS fabricated mounting structure, PCC foundation, solid core porcelain/polymer insulators, electrolytic copper/silver plated contacts, arcing horns, terminal pads with tinned copper connectors, nuts, bolts, washers, earthing connections and all accessories, conforming to IEC 62271-102 and relevant IS standards, as per specification, erected, tested and commissioned complete in all respects as directed by the Engineer-in-Charge. | — | — | — | 1,64,167.4 | |
| — | 2.00 | — | — | ||
| Supply, installation, testing and commissioning of 1 MVA, 3-phase, 50 Hz, outdoor type, oil immersed power transformer of ratio 33/11 kV, copper wound, BIS Energy Efficiency Level- II, vector group Dyn11, connection HV/LV: Delta/Star, with transposition of winding conductors to minimize circulating current and losses, current density not exceeding 2.4 A/sq.mm under all operating conditions, with impedance (Z%) as per IS 2026 and system requirement, with 5 Nos. off- circuit tap positions (±2.5%, ±5%), complete with first filling of transformer oil as per IS 335, welded leak-proof tank with radiators, conservator tank, Buchholz relay, OTI & WTI with marshalling box, arcing horns, silica gel breather, air release plug, drain cum sampling valve, pressure relief device, HV & LV porcelain bushings, name & diagram plate, lifting lugs, earthing terminals (2 Nos.), jacking pads and all standard accessories, conforming to IS 2026 (latest) and all relevant IS standards, as per approved technical data sheet, erected, tested and commissioned complete in all respects as directed by the Engineer-in-Charge. | — | — | — | 45,43,000 | |
| — | 1.00 | — | — | ||
| Supply, installation, testing and commissioning of 33 kV, 3-phase, 50 C/S, outdoor type, porcelain clad Vacuum Circuit Breaker (VCB) of rated continuous current 1250 A and short circuit breaking capacity 25 kA, complete with spring/motor charged operating mechanism, manual and electrical trip/close, two independent trip coils such that on failure of one the other shall operate, suitable for control voltage as per site requirement, anti-pumping relay, closing coil, control wiring, auxiliary contacts, electrical and mechanical interlocks, ON/OFF position indicators, mechanical operation counter, mounting structure, base frame, hardware, earthing connections, and all associated accessories and auxiliaries, conforming to IEC 62271-100 / relevant IS standards and as per attached/approved technical data sheet, erected, tested and commissioned complete in all respects as directed by the Engineer-in-Charge. | — | — | — | 4,23,803 | |
| — | 1.00 | — | — | ||
| Supply, installation, testing and commissioning of 33 kV, outdoor, tank type, oil cooled, single phase wound primary Current Transformer set (comprising of 3 units for 3-phase system), with CTR 200-100/5-5-5 A, Core-1: 0.5 class, 30 VA, Core-2: 5P10 class, 15 VA, Core-3: PS class with Vk 150 V and knee point 75 V, short time thermal current 25 kA for 1 second, BIL 70 kV (1 min power frequency) / 170 kVp impulse, complete with porcelain bushings, oil filled tank, secondary terminal box with shorting links, mounting structure, clamps, hardware, earthing connections and all standard accessories, conforming to IS 2705 / IEC 61869 and as per approved technical data sheet, erected, tested and commissioned complete in all respects as directed by the Engineer-in-Charge. | — | — | — | 1,67,890.4 | |
| — | 1.00 | — | — | ||
| Supply, installation, testing and commissioning of 33 kV Control & Relay Panel for Vacuum Circuit Breaker (VCB), indoor, floor mounted, metal clad, dust, moisture and vermin proof, complete with numerical protection relays comprising Over Current Relay (50/51), Earth Fault Relay (50N/51N), Master Trip Relay, trip circuit supervision relay, lockout relay (86), auxiliary relays for transformer oil and winding temp alarm and trip along with Buchlz relay protection, DC supply distribution with MCBs/fuses, meter as required for measuring parameter such as V,I,KVA,KVAR,KW and Current etc.,control switches, selector switches, indication lamps, hooters, annunciation windows, panel illumination lamp, space heater with thermostat, mimic diagram, name plates, terminal blocks, ferruled wiring, cable glands, earthing, module mounting structures, communication port (RS-485/Ethernet) for SCADA/RTU interface, suitable for control voltage as per site requirement, conforming to relevant IS/IEC standards IS:3427,IS:8623,IEC:62271-200,any other IS Standard applicable and as per approved technical data sheet, erected, tested and commissioned complete in all respects as directed by the Engineer-in-Charge. | — | — | — | 4,89,700 | |
| — | 120.00 | — | — | ||
| Providing and laying Cement Concrete (CC) work for substation yard including equipment foundations, cable trenches, operating platform and slab casting, for a total concrete quantity of 120 Cum, using nominal mix 1:1.5:3 (1 part cement : 1.5 parts coarse sand Zone-III derived from natural sources : 3 parts graded stone aggregate 20 mm nominal size derived from natural sources), complete with all materials, batching, mixing, formwork, vibration, finishing, curing, cutting of grooves/expansion joints, disposal of surplus earth, and all labour, tools and plants, conforming to IS 456 and relevant IS standards, for an area of approximately 20 m x 20 m (dimensions to be finalized as per site requirement and directions of the Engineer-in-Charge), noting that the area and thickness/depth are not fixed and shall vary as per actual site requirement, complete in all respects. | — | — | — | 11,27,383.2 | |
| — | 2342.00 | — | — | ||
| Supply, drawing, straining and binding of GI guard wire on pole/structure by GI bearer wire of 8 SWG and GI cross wire of 10 SWG, complete in all respects, wherein one route length shall consist of 2 metres of 8 SWG GI bearer wire and 1 metre of 10 SWG GI cross wire, as per standard practice and directions of the Engineer-in-Charge. | — | — | — | 46,840 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
TenderDocument933.pdf
AnexxuresSectionVIINew.pdf
TransformerParameter1MVA.pdf
VCBTechnicalParameter.pdf
FRPFencingTechnicalSpec.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .