| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.4 LAccepted-AOC PLOT NO 32 FF SHIVAJI ENCLAVE NEW DELHI 110027 | NEW DELHI | NEW DELHI | DELHI | 110027 | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹4.4 L+₹800 (0.18%)Rejected-Finance A 47D RAM DUTT ENCLAVE UTTAM NAGAR NEW DELHI 110059 | WEST | DELHI | 110059 | L2 | Rejected-Finance Not being lowest | |
| 3 | L3₹5.1 L+₹70,250 (16.0%)Rejected-Finance 3788 SHAH GANJ GB ROAD NEW DELHI 110006 | NORTH | DELHI | 110006 | L3 | Rejected-Finance Not being lowest |
Tender Value
₹6 L
EMD Value
₹12,000
Closing Date
23 Dec 2020, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE (AF) Gurgaon
HQ CWE (AF) Gurgaon, Old Palam Road, Delhi Cantt-110010
REPAIR/ MAINT OF HT CABLES, ELECTRIC EQUIPMENTS, HT POLES WITH ALLIED WORKS SERVICES OF ELECTRIC SUPPLY AT AF STN DADRI UNDER GE (AF) FARIDABAD
2020_MES_398212_1
CA NO CWE/GGN/F-26/2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
Dadri
As per NIT
9 documents required · 9 mandatory
₹500
GE (AF) Faridabad
₹12,000
Yes
17 Feb 2021
25 Nov 2020
25 Dec 2020
25 Nov 2020
23 Dec 2020
9 Dec 2020
60 days
Amount
M&L in repair cable end jointing kit for 11 KV (Earthed) grade cable for indoor termination joint heat shrinkble type joint complete with jointing material and accessories suitable for HT UG XLPE armoured aluminium conductor cable of size 95 sqmm 3 core 11KV complete all as specified and testing after jointing.
Supply & fix cable end jointing kit for 11 KV (Earthed) grade cable for outdoor type termination heat shrinkable joint complete with jointing material and accessoies suitable for HT UG XLPE armoured aluminium conductor cable complete with jointing material and accessories suitable for 3 core X 95 SQ MM core complete all as specified and testing after jointing.
M&L in repair out door type cable straight through joint heat shrinkble type suitable for HT UG XLPE armoured aluminium conductor cable complete with jointing material and accessories suitable for cable of size 95 sqmm 3core 11KV all as specified and testing after jointing.
Supplying installing, testing and commissioning of air break, gang operated, triple pole switch, outdoor, vertical mounting type of capacity 200 amps, ISI marked, mechanically operated on insulators and frame work with operating mechanism worked from ground level, with locking arrangements including 65 mm pad locks with two keys, complete with fuse mounts, fuse carriers and HT fuse elements having 11000 amp rating suitable for HT 11 KV, 50 Hz Ac Supply incl necessary electric connections complete all as specified and directed.
Dismantling & taking down old, deteriorated, lightening, arrestor and supply and fixing litghtening arrestor expulsion type complete with all fittings transmission class discharge capacity 65 Kilo Amp suitable for 11000 Volts duly carrying out insulation test complete all as specified and directed.
Dismantling of cross arms / bracing supports / clamps / back plates or any other structural steel sections including removing nuts bolts washers etc complete all as specified and directed.
M & L for cross arms, bracing supports, clamps back plates angles fabricated from the structural steel section including bolts, nuts, washers, welding, bending, drilling holes for bolts, bent to any required shape of size as indicated or directed, inclusive of one primer coat and two coats of aluminium paint after preparation of surfaces complete all as specified and directed.
S&F XLPE insulated aluminium conductor single core cable insulated for jumper suitable for HT 11000 volts overhead lines of size 95 Sqmm including making binding with GOD switches/insulators/ conductors and connection with GOD switches (length of jumper shall be 4 mtr but not more than 5 mtr long) complete all as specified and directed.
All as per Srl item No 08 above of size 95 Sqmm (but length of jumper shall be 1.5 mtr but not more than 2 mtr long) complete all as specified and directed.
Painting of steel surface of HT/LT PCC poles/Steel tubular pole over 10cm width or girth or less in girth or in small article such as brackets 'D' clamps etc with one coat of aluminium paint after prepration of surfaces complete all as specified and directed.
M & L for dehydration /filtration of transformer oil in existing pole mounted/floor mounted transformer ,Voltage stabilizer, HT OCB, ,HT VL switches with the help of dehydration/filtration machine to achieve the dielectric strength of transformer oil not less than 50 KV all as directed by EIC Note:- (i) Dehydration/filtration machine will be arranged by the contractor and he will make his own arrangement and to carry the machine at various sub stations including vehicle and towing arrangement. The rate shall be inclusive as above. (ii) Filtered oil should be with stand for one minute on voltage applied 50 KV at 4mm gap (iii) Test result will be recorded before and after filtration of oil.
M& L for topping up new transformer oil low viscousity confirming to IS:335 (latest revision) having dielectric strength not less than 55 KV, to transformers at various sub stations as directed by Engineer-in-Charge. Note :- (i) New insulating transformer oil shall be obtained in sealed steel container 200 Ltr cap duly ISI marked on drum and produced to Engineer-in-Charge for approval before use. (ii) Transformer oil shall be obtained from reputed Make: Gujrat Petrochem/ SAVITA/SHAKTI/IPO Petro Ltd/Power Link.
Taking down carefully transformer any capacity, any make, any type from pole / plinth by dismantaling, dis-connecting HT & LT sides, earthings of transformer, supporting angles/crossarms, Shifting / transporting transformer carefully from the site to the workshop and refixing at site after repair with all electrical connection to the entire satisfaction of engineer -in- charge.
M&L for opening of top cover by unsrewing nut, bolts & washer etc and taking out core assy from tank by disconnecting from tap changer HT & LT side bushing studs to outside by dismantling the channel and disconnecting star delta connection incl testing complete as specified and directed.
M&L for removing the lamination in proper manner carefully for taking out serviceable / un serviceable HT/LT coils from the limbs incl testing complete as specified and directed.
M&L for Rewinding of HT coils with copper wire DPC/ super enameled high quality matching with existing guage and impedance incl requisite paper/material in each layer of winding incl testing complete as specified and directed. Note : the rate quoted shall be inclusive of cost of all type of insulating material and heating/ varnishing etc.
All as per Srl item No 16 above but LT coils with copper strips incl testing complete etc all as specified and directed. Note : the rate quoted shall be inclusive of cost of all type of insulating material and heating/ varnishing etc.
M&L for inserting of HT/LT coils on limbs rewinded here-in-before/ old after cleaning of lanimation in proper way after insulating the limbs with requisite insulating materials on limbs in between limbs/ coils including testing complete etc all as specified and directed by E-in-Charge.
M&L for rearrange the top lamination over coils in proper manner incl fixing of top channel soldering in between coils as necessary and brazing of star delta connection with tap chnager incl testing complete etc all as specified and directed by E-in-Charge.
M&L for Baking the core assy in the oven duly varnishing the coil to improve IR value and to eliminate moisture incl testing complete etc all as specified and directed by E-in-Charge.
M&L for inserting core assy after baking in the tank (before inserting tank to be cleared by removing all deposit sludge etc incl drying) and making connection with HT/LT bushing studs and closing the tank top cover by fixing nut, bolts and washers (Top cover gasket will be measured and paid seperately) including testing complete etc all as specified and directed by E-in-Charge.
S&F in renewal of transformer bushing LT side incl brass set stem conical bush/ gasket, tightning ny using spring and star washer for indoor/ outdoor transformer by for the following capacity incl testing complete etc all as specified and directed : Note : The rate quoted is deemed to be included the cost of necessary labour charges for draining out transformer oil, opening of top cover by un screwing nut, bolts, washers and suitable size pad type bus bar aluminium and nut bolt washer etc.
(a) upto 160 KVA
(b) upto 200 KVA
M&L for Repairs to the leaks of transformer from tap switch/ fins/ any parts of body, by replacing gasket / seal or Repairs to the leaks of transformer body / fins by welding/ brazing etc complete all as specified and directed.
M&L for replacement of drain valve brass of suitable any size 25mm bore ISI marked.
Supply and fill up in replacement of defective silica gel in breather assy
Supply and fixing Breather assembly complete suitable for power distribution transformer of capacity up to 200 KVA including taking out old unserviceable breather complete all as specified and directed by E-in-Charge.
Supply and replacement temperature gauge 0-100 degree Celsius range dial type complete all as spd and directed.
Surface cleaning/ site clearance n exc 15 cm in depth in Sub stations area, trenches,sub station rooms two pole/ foure structure surroundings to make a over all presentable condition all as directed by Eng-in-charge.
Supply and loose filling stone Aggregate of gauge 40 to 80 mm grade in Two pole/ 4 pole electrical sub stn area complete all as specified and directed by Engr-in-charge.
Supply and fixing HT PVC Insulating floor Mat 2.50 mm thick class B anti skid without metalic derivative suitable for 11 KV Sub stn bldg incl all fixing adhesives etc complete all as specified and directed by Engr-in-charge.
Net Contract Sum will be after deducting Sch of Credit of Rs 95220.00
AKHIL ENTERPRISES
M/S Anand Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .