Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.4 LAccepted-AOC 29 MODEL TOWN BEHIND GURUDWARA PATHANKOT | PATHANKOT | PATHANKOT | PUNJAB | 145001 | ₹27.4 L Quoted ₹31.2 L | L1 | Accepted-AOC Since L1 bidder |
| 2 | L2₹36.3 L+₹5.1 L (16.3%)Rejected-Finance | ₹36.3 L+₹5.1 L (16.3%) | L2 | Rejected-Finance Since not L1 bidder |
| 3 | L3₹36.4 L+₹5.3 L (16.8%)Rejected-Finance SCHEME NO 07 BLOCK NO 22 FLAT NO 03 NEW GURDASPUR DISTT GURDASPUR PB 143521 | GURDASPUR | PUNJAB | 143521 | ₹36.4 L+₹5.3 L (16.8%) | L3 | Rejected-Finance Since not L1 bidder |
| 4 | L4₹41.2 L+₹10.0 L (32.2%)Rejected-Finance 195 MAHESH NAGAR AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | ₹41.2 L+₹10.0 L (32.2%) | L4 | Rejected-Finance Since not L1 bidder |
| 5 | L5₹50.3 L+₹19.1 L (61.1%)Rejected-Finance 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | ₹50.3 L+₹19.1 L (61.1%) | L5 | Rejected-Finance Since not L1 bidder |
Tender Value
₹60 L
EMD Value
₹1.1 L
Closing Date
17 Sept 2024, 6:00 pmClosed
CWE Amritsar
HQ CWE Amritsar
REPAIRS/REPLACEMENT AND MAINTENANCE OF VCB POWER TRANSFORMER, SWITCHGEAR, ISOLATOR AND CIRCUIT BREAKER UNDER GE GURDASPUR
2024_MES_663539_1
CWE/ASR-12/2024-25
Open Tender
Civil Works
Item Rate
270 days
GE Gurdaspur
As per tender documents
8 documents required · 8 mandatory
₹1,000
GE Gurdaspur
₹1.1 L
Yes
13 Nov 2024
3 Jul 2024
24 Sept 2024
3 Jul 2024
17 Sept 2024
3 Aug 2024
Amount
Taking down the fault transformer from existing site from pole and Sub Stn with the help of man power & chain pully block or by crane etc including disconnecting all electrical and mechanical connections for rectification of minor fault in site, i.e connection of tapchanger, connection of LT and HT winding with bush, changing of bush etc of capacity 25 KVA to 750 KVA Transformer (including 750 KVA). Note : (i) Minor fault of the transformer should be rectified at site within 2 days time frame on receipt of telephonically call/msg/whatsapp Msg or letter. Failing which 1500/- per day will be levied to the contractor as penalty complete, all as specified and directed.
M&L for shifting of the stand by transformer of capacity 63 KVA to 500 KVA from one sub stn to another with the help of crane, or manpower and disconnecting the fault transformer and connecting the stand by transformer for smooth provide the electric supply all as specified and directed by Engineer-in-charge. Note : (i) The transformer shall be shifted to faulty area under GE Gurdaspur by 6 Hrs of time frame after intimated by Tele phonically/Whatsapp Msg or letter. Falling which Rs 1000/- per hrs will be levied to the contractor as penalty. (ii) All the T&P and connecting material will be included in the quoted rate.
Taking down the unserviceable transformer from existing site from pole and Sub Stn with the help of man power & chain pully block or by crane etc including disconnecting all electrical and mechanical connections from the site and carrying to workshop for repair and replacement of old burnt unserviceable items as well as winding etc including transporting of capacity 25 KVA to 100 KVA Transformer (including 100 KVA) Note : (i) Unserviceable transformer should be taken down from site and carried to workshop within 2 days time frame on receipt of telephonically call/msg /Whatsapp Msg or letter. Failing which 1500/- per day will be levied to the contractor as penalty. (ii) The cost for Transportation provide by contractor for carrying the Unserviceable transformer from site to workshop & vice versa is deemed to be inclusive in the quoted rates and nothing extra shall be paid to Contractor.
All as per srl item No 3 above but 125 KVA to 250 KVA (including 250 KVA) complete, all as specified and directed.
All as per srl item No.3 above but 315 KVA to 400 KVA (including 400 KVA) complete, all as specified and directed.
All as per srl item No.3 above but 500 KVA to 750 KVA complete, all as specified and directed.
Opening Dismantling the transformer of capacity 25 KVA to 100 KVA (including 100 KVA capacity of transformers ) by lifting the top cover taking out the HT/LT core and draining out the transformer oil in clean barral including cleaning the transformer chamber (body) inside and out side thoroughly with emery paper and cloth then checking the winding and other worn-out parts such as HT/LT coils silicon stamping and other connected items as Tap-changer, breather assembly, replacement of HT and LT coil winding with DPC enamelled copper/Aluminimu wire/ strip of adequate size gauge and number of turn complete and connected to existing serviceable strip by jointing with soldring and re insulated of cotton tape over strip including using insulating material like varnish to limb coil fire proof type and sleeves etc by drying and baking of Insulating material in heating chamber in adequate temprature Reassenbling the transformer LT/HT connection with help of soldering.Testing of transformer after reassembly complete on No load at workshop and on load at site including painting to the transformer with super enamel paint complete, all as specified and directed. Note :- (i) HT/LT coils winding wire/strip, transformer oil , and other connecting items shall be measured & paid seperately. (ii) Unserviceable transformer should be rewinding in workshop within 09 days time frame on reaching at the transformer in workshop failing which Rs 2000/- per day will be levied to the contractor as penalty. (iii) HT/LT side bush, insulator and other connected items shall be measured & paid seperately. (iv) The cost for Transportation provide by contractor for carrying the transformer from site to workshop & vice versa is deemed to be inclusive in the quoted rates and nothing extra shall be paid to Contractor.
All as per srl item No.7 here in before but 125 KVA to 250 KVA complete, all as specified and directed.
All as per srl item No 7 here in before but 300 KVA to 400 KVA complete, all as specified and directed.
All as per srl item No.7 here in before but 500 KVA to 750 KVA complete, all as specified and directed..
Supply and fixing HT/LT coil winding with super enamelled copper wire/ strip of existing size & guage for winding the transformer HT/LT coils incl insulating material complete, all as specified and directed.
Supply and fixing HT/LT coil winding with DPC or enameled aluminium strip /wire of existing size & guage for winding the transformer coil HT/LT coils complete, all as specified and directed.
M&L for reconditioning of LT limb i.e replacement of cotton cloth, insulation paper etc complete, all as specified and directed.
Supply and fixing in replacement of HV bush with rod as per existing material & size and nut suitable for indoor/outdoor type transformer 25 KVA To 100 KVA complete, all as specified and directed.
All as per srl item No.14 here in before but 125 KVA to 250 KVA complete, all as specified and directed.
All as per srl item No.14 here in before but 300 KVA to 400 KVA complete, all as specified and directed.
All as per srl item No 14 here in before but 500 KVA to 750 KVA complete, all as specified and directed.
Supply and fix in replacement of LV bush and Insulator complete with rod as per existing material & size and nut suitable for indoor/outdoor type transformer 25 KVA To 100 KVA complete, all as specified and directed.
All as per srl item No.18 here in before but 125 KVA to 250 KVA complete, all as specified and directed.
All as per srl item No.18 here in before but 300 KVA to 400 KVA complete, all as specified and directed.
All as per srl item No.18 here in before but 500 KVA to 750 KVA complete, all as specified and directed.
Supply and fix in repair of tap changer for adjusting the voltage with brass parts as per sample of existing for indoor/ outdoor type transformer 25 KVA To 100 KVA complete, all as specified and directed.
All as per srl item No 22 here in before but 125 KVA to 250 KVA complete, all as specified and directed.
All as per srl item No 22 here in before but 300 KVA to 400 KVA complete, all as specified and directed.
All as per srl item No 22 here in before but 500 KVA to 750 KVA complete, all as specified and directed.
Supply and fix in replacement of silica gel in breather assembly different capacity of transformer all as directed by Engineer in charge complete, all as specified and directed.
Supply and fixing breather assemblty of capacity 500gm complete, all as specified and directed.
All as per Item ser No 27 above but capacity 1 Kg complete, all as specified and directed.
Supply and fixing of the temperature gauge of the different type and capacity of tranformercomplete, all as specified and directed.
Material & labour for painting to transformer rating 8 MVA power transformer out door type installed at 66 KV Sub Stn including mounting channels and connected accessories with two coats of super enamelled paint of approved colour spray painting machine including preparation of the surface complete, all as specified and directed.
All as per item ser No 30 but transformer capacity 5 MVA complete, all as specified and directed.
All as per item ser No 30 but transformer capacity 25 KVA to 100 KVA complete, all as specified and directed.
All as per item ser No 30 but transformer capacity 125 KVA to 315 KVA complete, all as specified and directed.
All as per item ser No 30 but transformer capacity 400 KVA to 750 KVA complete, all as specified and directed.
Material & labour for painting to panels & feeder pillar box, any sizes, installed at 66 KV Sub Stn with two coats of super enameled paint of approved colour with spray painting machine including preparation of the surface complete, all as specified and directed.
Supply and fixing in repair of protection cover for LT and HT side of the outdoor type transformer of any capacity, the protection cover should be made out of 3 mm dia CRCA sheet in rectangular, triangular or square shape and fixing the same cover by means of nuts, bolts, etc including applying one coat of red oxide and two coat of super enamel paint over the exposed surface of the box complete, all as specified and directed by Engineer in charge
Dehydration and filteration of transformer oil at site by using dehydrating and filteration machine to be carried out till time, dielectric strength reached to min 40 KV complete all as specified and directed. Note : The transformer dehydration machine shall be arrange/brought by contractor at site for which no extra amount be paid to the contractor complete, all as specified and directed.
Material and labour for toping up of the transformer with new with Xmer Oil having dielectric strength not less than 40 KV. Make - Power link /Savita/Transol complete, all as specified and directed.
Supply and fixing of 66/11KV HT side bushes of 8 MVA transformer complete, all as specified and directed.
Supply and fixing of 66/11KV HT side bushes of 5 MVA transformer complete, all as specified and directed.
Supply and fixing of 66/11KV LT side bushes of 8 MVA transformer complete, all as specified and directed.
Supply and fixing of 66/11KV LT side bushes of 5 MVA transformer complete, all as specified and directed.
Supply and fixing oil temperature indicator for 8 MVA power Transformer as per sample complete, all as specified and directed.
All as per item No 43 but for 5 MVA power Transformer as per sample complete, all as specified and directed.
Supply and fixing winding temperature indicator for 8 MVA power Transformer as per sample complete, all as specified and directed.
All as per item No 45 but for 5 MVA power Transformer as per sample complete, all as specified and directed.
Supply and fixing in repair of Buchholz relay for 8 MVA power transformer as per sample complete, all as specified and directed.
Supply and fixing in repair of Buchholz relay for 5 MVA power transformer as per sample complete, all as specified and directed.
M&L for Opening Dismantling the transformer of capacity 25 KVA to 750 KVA for repairing of transformer oil leakage from the top cover and HT/LT bushes, by lifting the top cover and draining out the transformer oil in barrel including cleaning the transformer chamber (body) inside and out side throughly with emery paper and cloth than checked the winding and other parts for smooth functioning and replacement of top cover and LT and HT bush gasket and reassenbling the transformer LT/HT connection with help of soldering..Testing of transformer after reassembly complete on No load and full load at site incl painting to the transformer with super enammed paint complete, all as specified and directed. Note :- The job includes the cost of gasket set, LT / HT bushes, nuts, bolts, washers etc required for the complete job. Only transformer oil will be measured and paid separately.
M&L for Opening Dismantling the power transformer of capacity 5MVA and 8 MVA for repairing of transformer oil leakage from the top cover and HT/LT bushes, by draining out the transformer oil in barrel including cleaning the transformer body outside throughly with cloth then checking the leakage of LT and HT bush gasket and reassmbling the transformer LT/HT connection with help of soldering. Testing of transformer after reassembly complete on No load and full load at site all as specified. Note :- The job includes the cost of gasket set, LT / HT bushes, nuts, bolts, washers etc required for the complete job.
Comprehensive maintenance of 66/11KV sub station equipment including replacement of unserviceable parts of following equipments all as specified and directed and testing by Punjab State Power Corporation Limited (PSPCL) authorised personal:- (a) Transformer 66/11 KV 8 MVA - 01 No (b) Transformer 66/11KV 5 MVA - 01 No (c) 66 KV SF-6 based Breakers 02 Nos (d) VCBs/C&R Panel /Battery Charge - 12 Nos and any other relevant HT equipment.
Notes:- (a) Checking of 11 KV functioning of all the tripping system / relay displayed on the control relay panel - such as differential O/C, earth fault, metering circuits and all othe protection from transformer - oil temp, trip, OLTC trip, winding temp gauge trip, bucholz relay, inter trip etc calibration of all the relays complete for time observed with respect to time set primary injection of all the CTs (Periodicity of testing half yearly). Deposite the charges levied / charged by the PSPCL authority for calibration / checking the protection system of 66 KV system all as directed. (b) Greasing / oiling of all the moving parts (c) Operation / working of charging motor and limit switch (d) Any part / spares found defective during testing shall be repaired / replaced for which payment shall be made separately against respective items of Sch 'A' (e) Test sheet shall be prepared as specified and made part of RARs & final Bill. (f) The equipments shall be tested twice, 1st test will be carried out within two months or as directed by Enngr -in-Charge from the date of commencement of contract and second test after six months from the 1st test. Payment shall be released on receipt of results/reports from PSPCL
M & L for comprehensive maintenance of VCBs installed at 66 KV MRS and different Sub stn i.e disconnecting of HT connections & DC connection from existing busbar and other parts carefully incl taking down the VCB trolly complete & disconnect the male/female contacts & clean the busbar with carbon tetra chloride liquid throughly busbar spout, trolly spout applying a one coat of 11 KV insulation quoting as per sample on busbar, spouts & other connected parts including, rewiring , greasing the movable parts with electrical greasing and repair or replacement the worn out parts by spare parts and reassembling the same re-connecting the HT & DC connection complete in functional order incl testing on existing load all as specified & directed. Note :- (i) The maintenance of VCBs should be done through OEM/uthorised service agencies of HT Switchgear and provide certificate before execution. The approval of agency shall be given by Engr-in-charge. (ii) VCBs maintenance must start within 1 day of time frame after intimated by telephonically/Whatsapp Msg or letter failing which Rs 2000/- per day will be levied to the contractor as penalty. (iii) Cost of spare parts i.e relay, Auxiliary, triping coil, close coil, indictor LED lamp, etc shall be measured and paid separately.
M & L for comprehensive maintenance of 66 KV Isolators switchset of three at 66 KV MRS, taking shutdlown from 66 KV S/S Tibber disconnect from existing isolator carefully clean the male and female contact with CRC throughly, tightening the nut, bolts of female and male contact, check the insulator, and apply grease usage for electric equipment all the movale contact of isolator and repair or replacement the worn out parts by spare parts and reassembling the same and re-connecting the HT connection complete in functional order all as specified & directed. Note :- (i) The maintenance should be done by within one day of time frame after intimated by Tephonically/Whatsapp Msg or letter failing which Rs 2000/- per day will be levied to the contractor as penalty. (ii) Cost of spare parts i.e Female contact, P G Clamp etc shall be measured and paid separately.
Supply and fixing, in replacement, current transformer ratio 400 /200/5-5A VA 2.5 , 50 Hz class SP, Short Circuit Current Capacity 21.0 KA for 3 sec complete, all as specified and directed.
All as per above item ser No 47 but ratio 900/450/1-1-1-1A as per sample at site complete, all as specified and directed.
Supply and fixing, in replacement, current transformer ratio 100 /50/5-5A VA 2.5 , 50 Hz class SP, Short Circuit Current Capacity 21.0 KA for 3 sec complete, all as specified and directed.
Supply and fixing, in replacement of potential transformer ratio resin cast type, 11 KV with comprises the following:- (i) Rratio : 11 KV/r3/110V/r3/110V/r3 (ii) Core -I : CL-1.0, 50 VA (iii) Core -2 : Cl-3P, 50 VA
Supply and fixing in repair of Closing coil with 220 V DC easy pact VCB as per sample in site complete, all as specified and directed.
All as per item ser No 58 with 24 Volt DC as per sample in site complete, all as specified and directed.
Supply and fixing in repair of Triping Coil l with 220 V DC easy pact VCB as per sample in site complete, all as specified and directed.
All as per item ser No 60 with 24 Volt DC as per sample in site complete, all as specified and directed.
Supply and fixing in repair of flush mounted high speed tripping relay (86) aux volts 220 Volt DC and aux contract 4 NO+3 NC H/R as per sample in sitecomplete, all as specified and directed.
All as per item Ser No 62 above but aux volts 24 Volt DC as per sample complete, all as specified and directed.
Supply and fixing in repair flush mounted numerical MFM protection relay Micom P127/P3U3O type auxiliary volt 220 Volt DC with DI 07 and DO 08 as per sample complete, all as specified and directed.
Supply and fixing in repair flush mounted numerical IDMT protection relay P111L type aux volt 220 V DC and Aux contacts 3 NO+ 1C/O as per sample in site complete, all as specified and directed.
All as per item ser No 65 but aux volt 24 Volt DC as per sample in site complete, all as specified and directed.
Supply and fixing in repair PT Fuse as per sample in site complete, all as specified and directed.
Supply and fixing in repair digital type multifuctional meter 3 Phase 4 wire flush type as per sample in site complete, all as specified and directed.
Supply and fixing in repair digital type voltmeter inbuilt in VSS flush type 96 sq mm as per sample in site complete, all as specified and directed.
Supply and fixing in replacement of flush mounted DC operated auxiliary relay (63X) for transformer faults with three pair of relay element with following configuration : - Type : CAR-A-3-S, Aux volt : 220V DC, Aux Contacts : 2 NO S/R
Supply in replacement of digital numerical type differential Relay for C&R Panel 66 KV Sub Station (make, Schienider, ABB, Siemen) operating Voltage 220 volt DC,as per sample complete, all as specified and directed by Engr-in-charge.
Supply and fixing in replacement of Breaker Control Switch (TNC) return to neutral type 2 pole 2way with off complete, all as specified and directed by Engineer incharge.
S& F in replacement of auxliary switch complete as existing site for 11 KV VCB complete, all as specified and directed.
Supply and fixing in repair LED Type indicating light aux volt 220 Volt AC colour RED, YELLOW, BLUE as per sample in site in complete, all as specified and directed.
Supply and fixing in repair LED Type indicating light aux volt 220 Volt AC colour RED, GREEN,AMBER,WHITE as per sample in site in complete, all as specified and directed.
All as per ser item No 75 but aux volt 24 volt DC complete, all as specified and directed.
M&L in replacement of Vacuum intruppter/vacuum bottle Type WL 33379 25 KA/ as per sample complete, all as specified and directed.
Supply and fixing in repair/replacement of automatic spring charging motor operating voltage 230 Volt AC as per existing site complete, all as specified and directed.
S&F in repair flush type micro processor based alarm annunciator with P.B window 08 and aux voltage 220 Volt DC as per sample in site in complete, all as specified and directed.
S&F in repair Hooter flush type 96 sq mm aux voltage 220 Volt DC as per sample in site in complete all as specified and directed.
S& F in repair push buttons red, yellow and black with aux contacts 1 NO and 1 NC complete, all as specified and directed.
S&F in repair Aux relay with base Type RXM/Eq Aux voltage 220 V DC and aux contacts 2C/O/ 4/CO as per sample complete, all as specified and directed.
S&F in repair Aux relay with aux voltage 24 V DC and aux contacts 2C/O as per sample in complete, all as specified and directed.
Supply and fixing in replacement of space heater at 11 KV VCB of 110 Watt, 240 Volt complete, all as specified and directed.
Supply and fixing antipumping pluge-in type relay SPD/Eq type with aux votl 220 V Dc and Aux contacts 1 NO + 1 NC complete, all as specified and directed.
Supply and fixing in replacement of safe high voltage tape roll (HT Tape) length 25 RM complete, all as specified and directed.
Supply and re-filling of SF-6 gas complete, all as specified and directed by Engineer -in-Charge.
Supply and fixing in replacement of contactor for SF 6 operating Voltage 220 Volt DC complete, all as specified and directed.
Supply and fixing triping Coil for SF 6 operating Voltage 220 Volt DC as per existing complete, all as specified and directed.
Supply and fixing closing Coil for SF 6 operating Voltage 220 Volt DC complete, all as specified and directed.
M&L for disconnecting the existing transformer/DG Set dismantling the existing foundation of the transformer/DG Set and temporary arrangement fo the connecting the existing transformenr to feed the user and making foundation of outdoor type transformers PCC brick platform of size 3.0mx3.0mx1.5 mtr in cement mortar 1:6 over thick foundation bed in PCC 1:4:8 type D2 (using 40mm graded stone aggregate of 50 mm thick coping in PCC 1:2:4 type B-1 (using 20 mm graded stone aggregate ) over platform and 15 mm thick rendering in CM 1:6 to exposed surface of PCC and applying three coats of white wash including making electrical connections, earthings connection etc an testing the transformer for electrical connections, earthings connection etc and testing the transformer for smooth functioning complete, all as specified and directed by Engineer-in-charge.
S&F in replacement of barrel fuse as per sample complete, all as specified and directed.
S&F in replacement of HRC fuse as per site reqmt complete, all as specified and directed.
M&L for earthing complete with galvansed steel earth plates electrode 60cmX60cmX6mm thick burried directly in ground ( earth pit not less than 2.25 mtr deep below the ground level ) with edge of the plate not less then 1.5 mtr below the ground level connection to GI galvanised Iron strp 25mmX4mm as earthing lead by means of bolts/nuts chick nut & washers of GI or steel all ghown in electrical plate No 3 of SSR part I connected to earthing test point all as specified or indicated including testing on completion including watering GI pipe 20 mm bore medium grade and PCC chamber using PCC 1:3:6 type C2 C1 cover funnel & wire mesh complete, all as specified and directed by Engr-in-charge. Note :The whole earthing will be redone on quoted rate if the result found not satisfactorily and the decisiom of Engineer-in-charge will be final and binding. No extra cost will be paid to the contractor for rectification of the earthing.
Supply and fixing earth continuity galvanised iron strip of size 25x4 mm complete, all as specified and directed by Engineer in charge.
Supply and fixing of coarse aggregate in 20 mm graded in layers at Main Receiving Station and appliying of lime solution before laying of coarese aggregate complete, all as specified and directed by Engineer in charge.
Surface dressing n.exc 15cm deep of soft/loose soil site clearance ground sub stn and E/M installation complete, all as specified and directed.
Supply and fix, in replacement, maintenance free battery, 2 Volt 100 AH (as per existing sample/ capacity) complete, all as specified and directed.
Supply & fixing replacement brass nut bolts and washers off sizes as per samples complete, all as specified and directed.
Supply & fixing replacement iron nut bolts and washers off sizes as per samples for HT/LT side of transformers complete, all as specified and directed.
Supply & fixing alluminium lugs long barrel type suitable for 95 sq mm cable complete, all as specified and directed by engineer in charge .
Supply & Fixing replacement of over current & Earth Fault Relay for C &R Panel 66 KV Sub Station Make : Schnider ,Siemens, ABB , operating 220 voltage,as per sample complete, all as specified and directed by Engr-in-charge.
Supply and fixing in replacement of copper fuse wire capacity 25 Amp SWG 25 complete, all as specified and directed by Engineer -in-charge.
Supply and fixing of copper fuse wire capacity 10 Amp SWG 29 all a specified complete, all as specified and directed Engineer -in-charge.
Supply and fixing of copper fuse wire capacity 5 Amp SWG 35 complete, all as specified and directed by Engineer -in-charge.
M&L for testing of power Transformer Oil by power grid PSPCL and test report submitted to this office before execution of the the work, complete all as specified and directed by Engineer -incharge . Note : Following test shall be carried out during the test:- (a) Dissolve Gas Analysis (b) Water Content. (c) Specific resistance (d) Dielectric dissipation Factor (e) Dielectric Strength (f) Total Acidity (g) Inter Facial Tension At 27 degree C (h) Flash Point (j) Furan Analysis (k) Inhibitor Content
M&L for rewiring of all control wiring of VCB/C&R panel with 2.5 sq mm PVC Cable multistrand copper conductor complete, all as specified and directed by Engr -in-charge.
Supply and fixing of copper control cable 16 Core 2.5 Sq mm e shethed unarmoured complete, all as specified and directed by Engineer-in-Charge. Make : Havells, Polycab, Gloster.
Supply and fixing of copper control cable 4 Core 2.5 Sq mm all as specified complete, all as specified and directed by Engineer-in-Charge. Make : Havells, Polycab, Gloster
Supply and fixing in repair of Insulator grade 66 KV for Isolator switch at 66 KV MRS as per sample complete, all as specified and directed
Supply and fixing Female clamp suitable for 66 KV line isolator switch complete, all as specified and directed.
Supply and fixing Male Link rod in copper suitable for 66 KV line isolator switch size and length as per existing site requirement complete, all as specified and directed.
P S BUILDERS (BID ID -3080793)
HARPAL ENGINEERS AND BUILDERS (BID ID -3092297)
Raman Electric Trading Co (BID ID -3097686)
R D Bansal (BID ID -3092395)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .