| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1st₹15.6 LAccepted-AOC | 1st | Accepted-AOC The lowest bidder M/s Kailash Chand Babulal has been accepted please. | |
| 2 | 2nd₹20.3 L+₹3.9 L (24.1%)Rejected-Finance | 2nd | Rejected-Finance L2 | |
| 3 | 3rd₹21.2 L+₹4.9 L (29.7%)Rejected-Finance | 3rd | Rejected-Finance L3 | |
| 4 | 4th₹21.3 L+₹5.0 L (30.6%)Rejected-Finance | 4th | Rejected-Finance L4 | |
| 5 | 5th₹21.8 L+₹5.4 L (33.1%)Rejected-Finance 10 2 NARAYAN BAG INDORE M P | 5th | Rejected-Finance L5 |
Tender Value
₹24 L
EMD Value
₹48,000
Closing Date
10 Aug 2020, 6:00 pmClosed
GE AWC MHOW
GE AWC MHOW
REPAIR / MAINTENANCE OF MCCBs, LT POLE PAINTING, SUB STATION FENCING AND CABLE WORKs AT 6/5 GR / DEMO BTY/ASC SUPPLY DEPOT EME Wksp AND ACE KLP DHAR ROAD UNDER GE AWC MHOW.
2020_MES_360323_1
8418 GE(AWC) /MHOW / OF 2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE AWC MHOW
All as per Tender Documents and NIT.
7 documents required · 7 mandatory
₹500
Yes
GE AWC MHOW
₹48,000
Yes
25 Sept 2020
11 Jul 2020
11 Aug 2020
11 Jul 2020
10 Aug 2020
27 Jul 2020
Amount
Excavation in trenches in any type of soil not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth for laying of cable and fixing pole,stays etc and getting out complete all as specified and directed
Returning , filling in includiing spreading levelling, watering and well ramming in layers not exceeding 25 cm thick with excavated soil comlete all as specified and directed
Removing excavated material (surplus soil ) to a distance not exc 50 mtr and depositing where directed at level not exc 1.5mtr above the starting point complete allas specified and directed.
M&L river washed and screened dry fine sand filling in trenches below and above / around under ground cable for cable protection, in duct under & abobe the cables including punning around cable complete all as specified and directed
M & L for unreinforced PCC Cable protection cover , Class LV ,Type1 flat ,size 250x150x40 as cable protection laid flat width wise complete all as specified and directed
Supply and laying galvanised iron pipe 'light Grade' 50 mm in trenches , under floors, roads, along poles for protection of cables with all necessary fittings, including sealing ends complete all as specified and directed .Make Jindal/Prakash Surya/Tata
Supply and laying galvanised iron pipe 'light Grade' 80 mm in trenches , under floors, roads, along poles for protection of cables with all necessary fittings, including sealing ends complete all as specified and directed .Make Jindal/Prakash Surya/Tata
Drilling (Horizontally) existing road (Maximum 10 mtr wide ) suitable for passing GI tubing 80 mm complete all as specified and directed.( GI tubing light grade measured and paid under respected item)
Supply, laying or fixing, jointing and testing inreplacement of LT under ground electric power cable of size 120 sqmm , 3.5 core. Crossed linked polyethylene (XLPE Cable ) insulated, galvanised steel strip or wire armoured, ISI -7098 Marked. With aluminium conductor multi stranded , heavy duty 1100 Volts grade of following sizes and core , complete all as specified laid in tenches / laid under floor or fixed naked with walls/ on poles/ in ducts/ in GI pipes etc:- Make Polycab, Gloster,RR Kabel,
Description same as per item no. 09.00 but size 95 sqmm , 3.5 core
Description same as per item no. 09.00 but size 70 sqmm , 3.5 core
Description same as per item no. 09.00 but size 50 sqmm , 3.5 core
Description same as per item no. 09.00 but size 35 sqmm , 3.5 core
Description same as per item no. 09.00 but size 25 sqmm , 3.5 core
Description same as per item no. 09.00 but size 16 sqmm , 4.0 core
Description same as per item no. 09.00 but size 10 sqmm , 4.0 core
Description same as per item no. 09.00 but size 10 sqmm , 2.0 core
Trimming/ Prunning lopping of tree branches touching to LT/HT lines not exceeding 30 CM girth shrub, vegetation, bushwood and saplings at least upto 2 M from outer Edge of ACSR including removing of branches of tree etc . To a distance exceeding 100 m and not exceeding 150M complete all as specified and directed . Note :- Linear length center to center of the poles shall only be measured. (ii) Shut down whenever required shall be taken in writing from Engr-in-Charge.
M & L painting of 09.0 mtr long steel pole with cross arm and clamp of any length and shape for LT over head line with two coat of aluminium paint including preparation of existing surfaces and marking pole No. in a 15 cm dia yellow circle and marking 03 Nos. black and 02 Nos. yellow bands/ strips with 30 cm wide fluorescent paint from bottom of pole up to 1.5 mtr height complete all as specified and directed..
Supply and fixing in repair 100 height, 65 mm dia, LT ,Pin type insulator, porcelin. Vitereous brown or green including 01 No. galvanised mild steel spindle, two galvanised iron washers and nuts suitable for working pressure of 1100 volts grade complete all as specified and directed. Make : WS Insulator, Jaipuria, Southern Insulator, Jaishree, Reychem, Birla 3M
Supply and fixing in repair of LT shakle type insulator, porcelain, vitreous white, brown or green 75 mm hibh and 90mm dia section of straps 31x3mm with12 mm dia of bolt, ball and socket type with clamp suitable for the conductor of required size and working pressure 1100 volts complete all as specified and directed. Make : Make : WS Insulator, Jaipuria, Southern Insulator, Jaishree, Reychem, Birla 3M
Supply and fixing (in replacement ) stay assembling complete with accessories, stay rod 20mm dia 2150mm long, 14mm dia 400mm GI, stay plate 230x230x6mm, loop type insulator (90x140mm), stay clamps and stay wire GI (7/8mm) of required length all as specified & shown in electrical plate No 1 of SSR Part-I - 1991 complete incl necessary PCC in foundation and earth work all as specified and as directed.
Material and labour for earthing inrepair complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 meter below normal ground level (with top edge of earth plate not less than 1.5 meter below ground level) connected to GI strip 32mm X 6mm main earthing lead by means of galvanized bolts, nuts and washers all as shown in electrical plate no 3 SSR Part-I with connected to earth test point & to main switch board etc with & including adequate quantity of charcoal dust and common salt alround earth plate, PCC (1:3:6) type C-1 (using 20mm graded black trap/granite/Basalt stone aggregate) for earth pit with 40 x 40 x 6mm mild steel angle iron frame for cover, pre cast RCC (1:2:4) type B-1 (using 20mm graded black trap/granite/Basalt stone aggregate) 40mm thick cover reinforced with 6mm dia bars 3 Nos both way with 12mm dia round bar handle, GI light grade watering pipe 20 mm dia with funnel and wire mesh, and 40 mm dia GI light grade earth lead protection pipe, complete all as specified and directed.
Description same as per item no. 09.00 but using galvanised earth lead wire 4.0 mm dia earthing lead.
Supply and fix in replacement of unserviceable LT joint straight through including jointing material and excavation upto 3mtr length and make good surface after jointing of cable complete of size 120 sqmm 3.5 core all as directed by Engineer-in-Charge. Make denson/ M seal/ Birla 3M.
Supply and fix in replacement of unserviceable LT joint straight through including jointing material and excavation upto 3mtr length and make good surface after jointing of cable complete of size 95 sqmm 3.5 core all as directed by Engineer-in-Charge. Make denson/ M seal/ Birla 3M.
Supply and fix in replacement of unserviceable LT joint straight through including jointing material and excavation upto 3mtr length and make good surface after jointing of cable complete of size 70 sqmm 3.5 core all as directed by Engineer-in-Charge.Make denson/ M seal/ Birla 3M.
Supply and fix in replacement of unserviceable LT joint straight through including jointing material and excavation upto 3mtr length and make good surface after jointing of cable complete of size 50 sqmm 3.5 core all as directed by Engineer-in-Charge. Make denson/ M seal/ Birla 3M.
Supply and fix in replacement of unserviceable MCCB 63 Amps 16 KA ,Triple pole,breaking cap 415 Volts, 50Hz,Fixed type complete all as directed by Engineer-in-Charge. Make:-Schneider, Legrand, L&T Lexic, C&S Electric Ltd, ABB
Supply and fix in replacement of unserviceable MCCB 100 Amps ,25 KA ,Triple pole,breaking cap 415 Volts, 50Hz,Fixed type complete all as directed by Engineer-in-Charge. Make:-Schneider, Legrand, L&T Lexic, C&S Electric Ltd, ABB
Supply and fix in replacement of unserviceable MCCB 125 Amps ,25KA ,Triple pole,breaking cap 415 Volts, 50Hz,Fixed type complete all as directed by Engineer-in-Charge. Make:-Schneider, Legrand, L&T Lexic, C&S Electric Ltd, ABB
Supply and fix in replacement of unserviceable MCCB 160Amps ,36 KA ,Triple pole,breaking cap 415 Volts, 50Hz Fixed type complete all as directed by Engineer-in-Charge. Make:-Schneider, Legrand, L&T Lexic, C&S Electric Ltd, ABB
Supply and fix in replacement of unserviceable MCCB 200 Amps 36 KA ,Triple pole,breaking cap 415 Volts, 50Hz,Fixed type complete all as directed by Engineer-in-Charge. Make:-Schneider, Legrand, L&T Lexic, C&S Electric Ltd, ABB
Supply and fix in replacement of unserviceable MCCB 250 Amps ,36 KA ,Triple pole,breaking cap 415 Volts, 50Hz,adjustiable thermal magnatic setting complete all as directed by Engineer-in-Charge. Make:-Schneider, Legrand, L&T Lexic, C&S Electric Ltd, ABB
M&Lfor Service cable of size 10 Sqmm 1100 Volt grade heavyduty cable PVC insulated aluminium conductor twin core cable flat or circular all as specified. Make :- RR Kable, Finolex, RPG (Asian), Universal, HPL India Ltd.
M&Lfor Service cable of size 6 Sqmm 1100 Volt grade heavyduty cable PVC insulated aluminium conductor twin core cable flat or circular all as specified. Make :- RR Kable, Finolex, RPG (Asian), Universal, HPL India Ltd.
Tightening and re-stringing of existing loose over head conductor (ACSR/Copper/GI continuous earth wire) any type on LT/HT poles including replacement of binding wire of required size and shape from insulators & jumpers, stringing and tightening of conductor to permissible sag complete. Note : Each line of wire to be measured.
Earth continuity conductor or main earthing lead fixed to wall on battenor recess or chases or buried in ground or drawn in pipe , galvanised earth strip of size 25x4mm , connected to earth equipment.(GI pipe measured & paid separetly)
Surface excavation n. exc. 30 cm deep and averaging 15 cm deep and getting out in old filling of stone aggregate and Screening/segregating incl spreading material complete for four pole/sub stn or for making path way complete.
Supply and spread 40 mm graded crushed stone aggregate around the four pole of sub stations complete all as specified and directed.
M&L for 100mm thick PCC 1:4:8 type D2 (using 40mm graded aggregate ) as in sub base of path all as specified and directed.
M&L for PCC 1:2:4 type-B-1 using 20 mm graded crushed stone aggregate as in coping of poles/struts and other similar location etc. with and including all necessary form work complete all as specified and directed.
S&F inreplacement of MCB TPN 63Amps 3 phase and neutral 240 volt , including complete all as specified and as directed. Make:-Schneider, Legrand, L&T Lexic, C&S Electric Ltd, ABB
Supply , installation , testing and commissioning .LT PANEL board outdoor type of size 1600 x 800 x 450 mm, Kiosk type factory assembled fabricated and of suitablesize angle iron, channel and MS sheet 3 mm thick (inner compartment is 2.0mm thick) double door type , front and rear openable with locking arrangement and indepent duly prewired with colour code three phases and netural for 415 volts, 50 Hz electric supply with and including suitable sizes of cable glands for incoming and outgoing cables , aluminium bus bar 600 Amps , cubical type duly powder coated over a coat of primer , grouting of panel 60 cm above the ground level by provisind 90 cm long angle iron frame bottom of panel 40x40x5 mm thick , welded on all four corners , embedded in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate upto 30 cm and,grouting the panel board on and including suitable size foundation structure with the following components. Make of MCCB:-Schneider, Legrand, L&T Lexic, C&S Electric Ltd, ABB And Make of panel:- CPRI Approved as pre-approved by GE. (a) MCCB 250 amps 4 pole Fixed type 36KA 415 volts (incoming) – 01No (b) MCCB 100 Amps 4 pole ,Fixed type, 25 KA 415 Volts (out going ) -04 Nos (c) MCB TPN 63Amps 3phase and neutral -03 No. (d) Aluminium Bus bar of capacity 400 Amps 3phase and neutral -1 set. (e)Digital type voltmeer 0-500 volts. (f) Digital type Ammeter with CT of suitable ratio for reading upto 400 amps load-01 No (g) Indicating lamps R,Y& B -01 set
M&L for spraying chemical (roundup) on area to remove unwanted vegitation /grass at various locations as directed by Engr-in-Charge Note- (1). Labour and equipments to spray chemical on required area are including in quoted rate.( 2). spry will be repeated quarterly or as per diredtion by Engr-in-Charge .
Supply and fixing in replacement of Aluminium conductor steel reinforced, including jumfering etc complete all as specified and directed.
Supply and fixing in replacement of cross-arms of MS channel or angle sections etc and setting aside complete all as specified and directed.
Supply and fixing in replacement on load change over three phase with netural 400 Amp with encloser including fixing arrangement all as directed by Engineer-in- Charge. Make:- L&T, C&S, Schneider, ABB, Siemens
Supply and fixing in replacement Bus bar 400 amp complete colour code with neuteral including arrangement of 200 amp MCCB three phase and netural with encloser including fixing arrangement all as directed by Engineer-in- Charge. Make of MCCB:-C&S, Legrand, Schneider
Supply and fixing in replacement Nature switch- 02sensor illuminance level for switching ON is upto 30 lux and for switching OFF 10 lux along with part night operation faciltyof 4-12 hrs arrangement all as directed by Engineer-in- Charge. Make:- Legrand, Hager, ABB, Schneider, L&T C&S Electric Ltd.
Supply and fixing in replacement Time switch- TS-203 with four time duretion memory arangement start time 00H 00M to 23 H 59M and 00H 01M to 23 H 59M all as directed by Engineer-in- Charge. Make:- Legrand, Hager, ABB, Schneider, L&T C&S Electric Ltd., EAPL
AGARWAL BUILDERS
ms shrilaxminarayan and sons
Vinayak Trading House
S.S. Engineers
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .