Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.2 LAccepted-AOC | L1 | Accepted-AOC Lowest | |
| 2 | L2₹30.8 L+₹1.2 L (3.95%)Rejected-Finance SA 15 144 S 1 CHANDAN HERITAGE HAVELIA CHAURAHA SARNATH VARANASI U P 221007 | VARANASI | VARANASI | UTTAR PRADESH | 221007 | L2 | Rejected-Finance Other Than Lowest | |
| 3 | L3₹47.5 L+₹17.9 L (60.5%)Rejected-Finance M 78 GARU HARKISHAN NAGAR PASCHIM VIHAR NEW DELHI 110087 | NEW DELHI | WEST DELHI | DELHI | 110087 | L3 | Rejected-Finance Other Than Lowest | |
| 4 | L4₹43.4 L+₹13.8 L (46.7%)Rejected-Finance | L4 | Rejected-Finance Other Than Lowest | |
| 5 | L5₹46.0 L+₹16.4 L (55.3%)Rejected-Finance | L5 | Rejected-Finance Other Than Lowest |
Tender Value
₹44.7 L
EMD Value
₹89,480
Closing Date
17 Jun 2025, 6:00 pmClosed
GE AF Gorakhpur
GE AF Gorakhpur
REPAIR/ MAINT LT DISTRIBUTIOB SYSTEN AT TECH AREA AND UPS FIRE FIGHTING SYSTEM LAUNDRY PLANT AND STABILISER WITH ALLIED ITEMS UNDER GE AF GORAKHPUR
2025_MES_709441_1
9318/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE AF Gorakhpur
Class D cat b i
8 documents required · 8 mandatory
₹500
GE AF Gorakhpur
₹89,480
Yes
31 Jul 2025
21 May 2025
19 Jun 2025
21 May 2025
17 Jun 2025
4 Jun 2025
21 May 2025 - 28 May 2025
Amount
Excavation in trenches n. exc 1.5 m wide and n.exc 1.5 m in depth and getting out soft/loose soil complete all as specified and as directed for laying of under ground cable, foundation of pole and stay etc. complete all as specified and as directed at site.
Returning, filling in, including spreading, levelling, watering and well remmining in layers not exc 25 cm. Complete all as specified and directed at site.
Removing excavated material n.exc 50 m and depositing where directed at a level n. exc 1.5 m above the starting point acomplete all as specified and as directed at site.
M&L for sand cushioning to U/G cable in layers of 23 cm thick( 8 Cm before laying the cable and 15 Cm thick after laying the cable) in trenches complete all as specified and directed.Note :- Only Puned down volume shall be measured. complete all as specified and as directed at site.
Supply and lay burnt best quality locally available old size sub class 'B' bricks laid in trenches perpendicular to U/G cable for cable protection complete all as specified and as directed.
Laying only serviceable bricks obtained from the items specified here-in-before (i.e during taking out of under ground cable),laid flat dry, in trenches with width of the bricks laid to the axis of cable for protection of cable complete all as specified and as directed
Taking out unserviceable LT U/G cable from trenches of size 6 Sqmm to 120 Sqmm 2/3.5/4 core complete all as specified and as directed.
Supply and lay in trenches or passing through pipe XLPE insulated armoured, heavy duty electric cable with aluminium conductor 1100 volts grade, cross-sectional area 10 Sqmm 4 core
All as per item No-8 above but of size 16 sqmm 4 core complete all as specified and as directed at site.
All as per item No-8 above but of size 25 sqmm 4 core complete all as specified and as directed at site.
All as per item No-8 above but of size 35 sqmm 3.5core complete all as specified and as directed at site.
All as per item No-8 above but of size 50 sqmm 3.5core complete all as specified and as directed at site.
All as per item No-8 above but of size 70 sqmm 3.5core complete all as specified and as directed at site.
All as per item No-8 above but of size 95 sqmm 3.5core complete all as specified and as directed at site.
All as per item No-8 above but of size 120 sqmm 3.5core complete all as specified and as directed at site.
All as per item No-8 above but of size 150 sqmm 3.5core complete all as specified and as directed at site.
All as per item No-8 above but of size 185 sqmm 3.5core complete all as specified and as directed at site.
All as per item No-8 above but of size 240 sqmm 3.5core complete all as specified and as directed at site.
Boring holes horizontally under road without damaging the surface of road ( minimum 1.0 Metre below the road surface with the help of GI tubing not exc 100 mm bore(dia) for passing UG cable, complete all as specified and as directed. NOTE : - GI Pipe laid will be measured and paid separately under respective item complete all as specified and as directed at site.
S&F in replacement of 40 mm bore GI tubing light grade with all fittings laid across road, in trenches or across PCC drain, along electric pole or floor/wall for cable protection with suitable size of MS clamps and nut and botls/washers complete all as specified and as directed at site.
S&F in replacement of 25 mm bore GI tubing light grade with all fittings laid across road, in trenches or across PCC drain, along electric pole or floor/wall for cable protection with suitable size of MS clamps and nut and botls/washers ccomplete all as specified and as directed at site.
M&L for earthing complete with galvanised steel earth plate electrode 600 x 600 x 6 mm thick, burried directly into the ground (earth pit not less than 2.25 mtr below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to GI earth strip 32x6 mm by means of bolts, nuts, check nuts, and washers of galvanised iron or steel all as shown iln electrical plate No. 3 connected to earthing test point all as specified or indicated including excavation and connected earth work, PCC chamber and cover, watering pipe, funnel wire mesh but without earth lead protection pipe and test on completion after dismantling unserviceable erthing (above GL only) complete all as specified and as directed at site.
Dismantling existing unserviceable feeder pillar box including disconnection from different sites .
Fabrication, supply, installation, testing and commissioning in replacement of outdoor type feeder pillar box floor mounted made out from 3.15 mm thick MS sheet ( CPRI type tested) with canopy type roof, front operated, one part hinged doors with locking arrangement comprising of Aluminium bus bar suitable for 3 phase, 4 wire, 415 volts,50 Hz, AC supply mounted on suitable bus bar insulators, 200 Amps rating suitably drilled and tapped for bolts with openable two part front and rear shutter with heat strinkable PVC sleeving having RYB-B colour code drilling holes for connection of incoming and outgoing cable, complete powder coated painting, testing and installation on PCC/brick foundation, connection of cable with suitable aluminium lugs all as specified and directed.
Repairing of unserviceable MCCBs/MCBs/changeover switch in LT panel/ DBs any type including replacing of burnt out lugs, including cutting of burnt cable terminals ,prepare and crimping the cable lugs with LT cables in no light/unhealthy light complaints and making serviceable in all respect by providing skilled manpower.Work shall also include checking and removal of leakages in neutral and phase in 440/220 Volts connection as and when directed.NOTE:- (a) The rate quoted by the contractor for Each Job is deemed to inclusive in rate quoted (b) The ladder and T&P as required will be provided by the contractor(c)Risk factor will be the contractor's end(d) Minor items like cable lugs,Insulation tape,nut,bolts etc deemed to be included in rate quoted (e)Major Items will be measured and paid separately in the relevant items here under:-
S & F in replacement MCCB 630 Amps, 4 pole, 415 volts, 50 Hz 50 KA breaking capacity with adjustable thermal magnetic release with spreader link on both sides with existing size and make as suitable to fit in the existing LT FPB all as specified and directed
S & F in replacement MCCB 400 Amps, 4 pole, 415 volts, 50 Hz 36 KA breaking capacity with adjustable thermal magnetic release with spreader link on both sides with existing size and make as suitable to fit in the existing LT FPB all as specified and directed
S & F in replacement MCCB 315 Amps, 4 pole, 415 volts, 50 Hz 36 KA breaking capacity with adjustable thermal magnetic release with spreader link on both sides with existing size and make as suitable to fit in the existing LT FPB all as specified and directed
S & F in replacement MCCB 250 Amps , 4 pole, 415 volts , 50 Hz , 25 KA breaking capacity with adjustable thermal magnetic release, with spreader links on both sides with existing size and make as suitable to fit in the existing LT FPB all as specified and directed
S & F in replacement MCCB 200 Amps , 4 pole, 415 volts , 50 Hz , 25 KA breaking capacity with adjustable thermal magnetic release, with spreader links on both sides with existing size and make as suitable to fit in the existing LT FPB all as specified and directed
S & F in replacement MCCB 160 Amps , 4 pole, 415 volts , 50 Hz , 25 KA breaking capacity with adjustable thermal magnetic release, with spreader links on both sides with existing size and make as suitable to fit in the existing LT FPB all as specified and directed
Supply only in replacement on load Changeover switch 415 Volt in sheet metal enclosure 4 pole of capacity 200 Amp all as specified and directed
Supply only in replacement on load Changeover switch 415 Volt in sheet metal enclosure 4 pole of capacity 400 Amp all as specified and directed
M&L straight through joints( epoxy) for LT underground cable including joint kits suitable for aluminium conductor cable 3.5 core 6 sqmm to 240 sqmm all as specified and directed
M&L outdoor LT END Termination Heat Shrink Kits for LT underground cable suitable for aluminium conductor cable of size 6 sqmm to 240 Sqmm (3.5/4C) all as specified and directed
M & L for preparing old painted surfaces by scraping and removing old paints,rust etc from steel tubular poles (above the planting depth and PCC coping of 9.0 Metre long pole) and Mild Steel cross arms, cable protection pipe,brackets etc and applying one coat of synthetic enamel paint alternate yellow & black strips painting ( 5 Nos each strip 300 mm wide) and remaining portion of pole and cross arms,cable protection pipe,brackets etc painted with one coat of aluminium paint including marking of pole No with black background and white lettering with all arrangement for ladder etc all as specified and directed .
Dismantling of old PCC/steel tubular pole of any size with necessary disconnection of electric wire, demolition of concrete foundation including excavation, earth work as reqd & removing the same from site complete all as specified and as directed.
Supply & errection of steel tubuler swaged & welded pole 9.0 m long type 410 SP- 31 complete with CI base plate and finial tapper plug , bolts nuts screw conforming to IS: 2713 (part I to III) complete painting of pole with two coat of aluminium paint over a coat of red oxide primer and applying one coat of synthetic enamel paint alternate yellow & black strips painting ( 5 Nos each strip 300 mm wide ) all as specified and directed.
Disconnection and dismantling of existing serviceable under ground cable of size 6 Sqmm to 240 Sqmm 2/4 core from LT Panel/FPB and taking out cable/cable loop from underground by excavtion of soft/loose soil and insertion of heat shrinkable PVC colour sleeves on cable cores and crimping of suitable size aluminium cable lugs as required and refixing the same in its original position complete all as specified and as directed.
M & L for coarse aggregate 40 mm graded 1 including spreading, leveling over the cleared surfaces at sub station complete all as directed.
Supply and spary of grass burning chemical(Paraquat dicholride 24 SI Herbicides ) with the help of manually opearted machine complete in sub station complete in air force stn directed by engineer incharge.
Detecting of fault of LT UG cable (any place any length any type /size) with help of vehicle mounted cable fault locator including detecting exact location of cable fault and remove of cable for rectification. complete all as specified and as directed.
Repair/Maintenance of laundry plant and its overhauling with spare parts to be paid separately.(i) heating strip industrial type 3 KW complete all as specified and meet the criteria as per existing equipment.
(ii) Butterfly valve 2" complete all as specified and meet the criteria as per existing equipment.
(ii) Butterfly valve 5" complete all as specified and meet the criteria as per existing equipment.
(iv) contactor complete all as specified and meet the criteria as per existing equipment.
(v) Indicating lamp(R,Y,B) complete all as specified and meet the criteria as per existing equipment.
(vi) Push button complete all as specified and meet the criteria as per existing equipment.
(vii) Belt(B-72) complete all as specified and meet the criteria as per existing equipment.
(viii) Timer complete all as specified and meet the criteria as per existing equipment.
(ix) MCB 63A complete all as specified and meet the criteria as per existing equipment.
(X) Rewinding of Motor 2 HP 3 phase complete all as specified and meet the criteria as per existing equipment.
(xi) Labour charge for complete overhauling of the plant complete all as specified and meet the criteria as per existing equipment.
Supply & erection in replacement of Internal Hydrant Valve stainless steel coupling 63mm dia with cost iron wheel
Supply & erection in replacement of 63 MM DIA 15 MTR Long RRL hose pipe with 63 mm dia male / female coupling
Supply & erection in replacement of Hose Box (600*300*200) size made 16/18 SWG thick having 04mm thickness glass double door
Supply & erection in replacement of NRV 100mm Dia complete all as specified and meet the criteria as per existing equipment.
Supply & Erection in replacement of Air release valve complete all as specified and meet the criteria as per existing equipment.
Supply & Erection in replacement of Butterfly valve 100mm dia complete all as specified and meet the criteria as per existing equipment.
Pump room(all pump) maintenance and all hydrant line testing & Commissioning complete all as specified and meet the criteria as per existing equipment.
Supply & fixing of Diesel engine Battery 150 AH, 12/24 volt complete all as specified and meet the criteria as per existing equipment.
M&L for spray Paint of All Hydrant & Pump,pipeline as per IS code complete all as specified and meet the criteria as per existing equipment.
M&L for taking out and disconnecting of UPS (digital/analog type), 3 phase, 415 volts, AC, 50 Hz, 3 to 20 KVA and detecting the internal faults of following parts/assembly etc of any make and type and repair / replace the same defective parts of same type / capacity as OEM design and testing on load complete all as reqd and as directed :- (Note :- Spare parts/assembly will be measured and paid seperately) (a) Intelligent slot (b) SNMP card (c) Transformer (d) Auxillary circuit (e) Communication port/EPO port (f) Support time (g) Suitable operating software package (h) LCD/LED display information (j) Buzzer alarm status (k) Bypass switch (l) Identification menu
Supply only Intelligent slot of UPS 3 to 20 KVA 3 phase complete all as specified and meet the criteria as per existing equipment.
Supply only SNMP card of UPS 3 to 20 KVA 3 phase complete all as specified and meet the criteria as per existing equipment.
Supply only Transformer of UPS 3 to 20 KVA 3 phase complete all as specified and meet the criteria as per existing equipment.
Supply only Auxillary circuit of UPS 3 to 20 KVA 3 phase complete all as specified and meet the criteria as per existing equipment.
Supply only Communication port / EPO port of UPS 3 to 20 KVA 3 phase complete all as specified and meet the criteria as per existing equipment.
Support time of UPS 3 to 20 KVA 3 phase complete all as specified and meet the criteria as per existing equipment.
Supply only Suitable operating software package of UPS 3 to 20 KVA 3 phase as reqd at site.
Supply only LCD/LED display system of UPS 3 to 20 KVA 3 phase complete all as specified and meet the criteria as per existing equipment.
Supply only Buzzer alarm system of UPS 3 to 20 KVA 3 phase complete all as specified and meet the criteria as per existing equipment.
Supply only Bypass switch of UPS 3 to 20 KVA 3 phase complete all as specified and meet the criteria as per existing equipment.
M&L for taking out and disconnecting of UPS (digital/analog type), 3 phase, 415 volts, AC, 50 Hz, 200 KVA and detecting the internal faults of following parts/assembly etc of any make and type and repair / replace the same defective parts of same type / capacity as OEM design and testing on load complete all as reqd and as directed :- (Note :- spare parts/assembly will be measured and paid seperately) (a) Intelligent slot (b) SNMP card (c) Transformer (d) Auxillary circuit (e) Communication port/EPO port (f) Support time (g) Suitable operating software package (h) LCD/LED display information (j) Buzzer alarm status (k) Bypass switch (l) Identification menu
Supply only Intelligent slot of UPS 200 KVA 3 phase complete all as specified and meet the criteria as per existing equipment.
Supply only SNMP card of UPS 200 KVA 3 phase complete all as specified and meet the criteria as per existing equipment.
Supply only Transformer of UPS 200 KVA 3 phase complete all as specified and meet the criteria as per existing equipment.
Supply only Auxillary circuit of UPS 200 KVA 3 phase complete all as specified and meet the criteria as per existing equipment.
Supply only Communication port / EPO port of UPS 200 KVA 3 phase complete all as specified and meet the criteria as per existing equipment.
Support time of UPS 200 KVA 3 phase complete all as specified and meet the criteria as per existing equipment.
Supply only Suitable operating software package of UPS 200 KVA 3 phase complete all as specified and meet the criteria as per existing equipment.
Supply only LCD/LED display system of UPS 200 KVA 3 phasecomplete all as specified and meet the criteria as per existing equipment.
Supply only Buzzer alarm system of UPS 200 KVA 3 phase complete all as specified and meet the criteria as per existing equipment.
Supply only Bypass switch of UPS 200 KVA 3 phase complete all as specified and meet the criteria as per existing equipment.
Supply only Electrolytic surge capacitor 3300 Mfd, 500 Volt DC for UPS 20 KVA 3 phase complete all as specified and meet the criteria as per existing equipment.
Disconnecting / taking out old unserviceable batteries of capacity 12 volts, upto 50 AH from existing UPS (digital/analog type) of capacity 3 phase, 415 volts 3 to 200 KVA and Supply / install / connecting of maintenance free, dry cell battery of capacity 12 volts up to 50 AH as reqd at site all as directed. Make : Exide/Amaron
All as per item No.37 above but of capacity 12 volts, upto 100 AH complete all as specified and meet the criteria as per existing equipment.
All as per item No.37 above but of capacity 12 volts, upto 150 AH complete all as specified and meet the criteria as per existing equipment.
Disconnection of all electrical connection and opening of Automatic Servo voltage stabilizer , Three phase, balanced load 300-480 volts and derive volts 400-440 volts, + 1.5 Volts, air/oil cooled of capacity upto 40 KVA of any make/design, opening and cleaning of transformer and repairing the faults, re-assembling after replacement of unserviceable/defective, worn out parts with new parts of same make/type/capacity reassembling, commissioning and testing in satisfactory manner and testing on load complete (Note :- Spare parts/assembly will be measured and paid seperately)
Disconnection of all electrical connection and opening of Automatic Servo voltage stabilizer, Three phase, balanced load 300-480 volts and derive volts 400-440 volts, + 1.5 Volts, air/oil cooled of capacity 75 /150 / 200 KVA of any make/design, opening and cleaning of transformer and repairing the faults, re-assembling after replacement of unserviceable/defective, worn out parts with new parts of same make/type/capacity reassembling, commissioning and testing in satisfactory manner and testing on load complete (Note :- Spare parts/assembly will be measured and paid seperately)
Supply only Control relay suitable for upto 40 KVA voltage stablizer complete all as specified and meet the criteria as per existing equipment.
Supply only Control relay suitable for 75 KVA voltage stablizer complete all as specified and meet the criteria as per existing equipment.
Supply only Control relay suitable for 150 to 200 KVA voltage stablizer/Isolation Transformer.
Supply only Voltmeter 0-500 volts suitable for 75 to 200 KVA voltage stabilizer / Isolation Transformer complete all as specified and meet the criteria as per existing equipment.
Supply only Automatic printed circuit board (electronic control circuit) suitable for upto 40 KVA servo voltage stabilizer complete all as specified and meet the criteria as per existing equipment.
Supply only Automatic printed circuit board (electronic control circuit) suitable for 75 KVA servo voltage stabilizer complete all as specified and meet the criteria as per existing equipment.
Supply only Automatic printed circuit board (electronic control circuit) suitable for 150 & 200 KVA servo voltage stabilizer / Isolation Transformer.
Supply only Time relay circuit upto 200 KVA with all accessories complete all as specified and meet the criteria as per existing equipment.
Supply only Transformer main copper wound upto 5 Kg suitable for 5 to 20 KVA, 3 phase voltage stabilizer with copper winding complete all as specified and meet the criteria as per existing equipment.
Supply only Transformer main copper wound upto 15 Kg suitable for 40 & 75 KVA, 3 phase voltage stabilizer with copper winding complete all as specified and meet the criteria as per existing equipment.
Supply only Dimmer Circuit of Servo voltage stabilizer of capacity 10 to 75 KVA, suitable for Stabilizers / Isolation Transformerscomplete all as specified and meet the criteria as per existing equipment.
Supply only Dimmer Circuit of Servo voltage stabilizer of capacity 150 & 200 KVA, suitable for Stabilizers/Isolation Transformers complete all as specified and meet the criteria as per existing equipment.
M&L for repair of Servo Motor (synchronous) of Servo type voltage stabilizer, three phase 415 volt, AC of capacity 40/75 KVA. complete all as specified and meet the criteria as per existing equipment.
M/s A.K Construction (BID ID -3318463)
SALUJA CONSTRUCTION CO (BID ID -3326326)
Yaduvanshi Traders (BID ID -3318671)
Hindustan Power Corporation (BID ID -3325975)
M I & CO. (BID ID -3326724)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .