Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.3 LAccepted-AOC | L1 | Accepted-AOC Accepted | |
| 2 | L2₹9.7 L+₹1.3 L (15.3%)Rejected-Finance | L2 | Rejected-Finance Rejected | |
| 3 | L3₹9.7 L+₹1.3 L (15.7%)Rejected-Finance | L3 | Rejected-Finance Rejected |
Tender Value
Refer Docs
EMD Value
₹19,000
Closing Date
8 Mar 2022, 6:00 pmClosed
ADMC
GARRISON ENGINEER NORTH BANGALORE T 64 MEANEE LINES MEG AND CENTRE BANGALORE 560042
REPAIR MAINTENANCE OF CENTRAL AC PLANT 360 TR AT ADMC AND CONNECTED ITEMS UNDER GE NORTH BANGALORE
2022_MES_506895_1
8278
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
ADMC
Class E Category c(i)
6 documents required · 6 mandatory
₹500
Yes
GARRISON ENGINEER NORTH BANGALORE
₹19,000
Yes
24 Mar 2022
9 Feb 2022
10 Mar 2022
9 Feb 2022
8 Mar 2022
17 Feb 2022
9 Feb 2022 - 16 Feb 2022
Amount
Dismantling existing cooling tower side cover carefully without damaging the other portion of cooling tower removing unserviceable PVC fills carefully from cooling tower supply and fix PVC fills for 200 TR capacity cooling tower including replacement of unserviceable bolts and Nuts etc all as directed.
Supply and fix removable type factory made mettalic pre -filters of 20 microm of standard size lift GI frame both side including taking out unserviceable mettalic pre - filters etc all as directed Make- Acrosol / Dyna / Johnflower / MAF
Supply and fix factory made high performance bag filters of 99 micron down to 5 micron standard size with multiple pockets and self supporting filter bagswith MS / GI anodised aluminium frame suitable for central AC plant including replacement of bolts and nuts and taking down unserviceable bag filters etc all as directed Make- Acrosoi / MAF / Dyna / Johnflower
Supply and fix water pressure gauges of any size up to 0- 300 PSI/0-150Kg cm² capacity including taking out unserviceable water pressure gauge etc all as directed Make- KI / H-Guru / Feibeg / Adarsh
Supply and charge R-22 Refrigerent Gas Make Fluron / refron / mefron
Supply and fix AC power contact 4 pole 415 vots 50 Hz of the following capacity including taking out unserviceable contact etc all as directed Make- L&T / Siemens/ BCH / CSS (a) 33 Amps to 63 A capacity MNX-32, 440 Volts AC Supply
(b) 65 Amps to 100 amps capacity MNX-95, 440 Volts AC
Disconnecting and isolating the compressor of Voltas 5H-120 model compressor from the system by putting dummy plates to suction and discharge valves opening of the compressor, removing of internal parts cleaning of the all parts throughly, replacement of Thrust washers O rings minor parts like Nuts, Bolts etc reassembling back all the serviceable parts removing of the dummy plate of the compressor, testing of compressor complete all as specified and as directed. Note : (i) Spare parts & consunable will be measured & paid seperately (ii) charging of compressor oil will be measuredn& paid separately.
Supply and fix the following spares for model Voltas 5H-120 compressor including taking down old unserviceable spare parts complete all as specified and as directed. (a) Main bearing pump and seal end
(b)Cylinder liner
© Connecting rod
(d) Discharge valve assembly
(e) Piston assembly
(f) Oil pump assembly
(g) Valve plate assembly
(h) Gasket set
(j) Oil filter
(k) SV reeds
(l) CR bearing
(m) SV spring
(n) pressure release valve
Discaling of condensing unit of 120 TR capacity of air conditioning plants by circulating descaling agent (HCL) through the condenser by forced feed method, removing of the end cover of the condenser cleaning of each tube of condenser throughly by the brushing refixing back the end cover of the condenser by removing of the rubber gasket, nuts bolts washers cleaning of spray nozzles, cooling tower cup, water line.strainer and testing spray nozzle working pressure all as specified and as directed.
Evacuation refrigerent gas from the system in to the empty cylinder of120 TR capacity of air conditioning plants leak testing of the plant with dry nitrogen (N2) pressure by seperating the entire system like low side high side, compressors, condensers and rectifing the leakage vaccummising, recharging of evaculated refrigerent gas testing and brazing of cooling coil complete all as directed Note : (i) Supply of refregirent gas & consumable will be measured and paid separately (ii) Installed capacity of the plant to be considered.
Supply and fixing of the following pressure cut-outs including dismantling of unserviceable cut-outs all as specified and as directed Make- Indfoss / Danfoss (a) HP/LP Cut-outs
(b) Oil Pressure cut-outs
(c ) Water pressure cut-outs
Disconnecting and removing the centrifugal monoblock pump set 3 phase 415 Volts from the existing position following capacity of any make, transporting to workshop, opening up check the pump winding, cutting and removing of the burnt out winding, rewinding with same size of gauge of copper conductor, insulating, varnishing greasing and replacing of ball bearing 2 Nos, reassembling, including cleaning, oiling, greasing of internal parts, replacing of worn out nut bolts, gland packing etc testing for proper functioning, bring back to site re fixing back in the same position including replacement of gland packing worn out nuts bolts etc, and testing and commissioning complete all as directed. (a) 15 HP Capacity
Pressure gauge of any size up to 0 to 300 PSI capacity including taking down unserviceable pressure gauge
PVC Ball valve high pressure with polythene float complete of size 25 mm dia including taking down unserviceable float valve etc all as specified and as directed Make Prayag / equivalent
Shaft seal assembly 5H120 of any make and model of compressor including removing of the unserviceable shaft seal assembly and testing all as specified and as directed.
Removing / Replacement of AHU Belt SPA 1550.
Removing / Replacement of AHU Belt SPA 1700.
Removing / Replacement of AHU Belt SPA 1360.
Removing / Replacement of AHU Belt SPA 1220.
Removing / Replacement of AHU Belt SPA 1600.
Removing / Replacement of Pressure gauge 0-100 Psig.
Removing / Replacement of fix Ceiling Psychrometer.
Rubber tyre coupling suitable for 120 TR capacity compressor motor including taking out U/S rubber coupling etc all as directed.
Supply and charge compressor oil servo frizol F-68 grade of IOC/BPCL / Hindustan petroleum all as directed
M.G. Enterprises
B5BUILDING SOLUTIONS
stage.html
html • 0.05 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .