Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹38.7 LAccepted-AOC | L1 | Accepted-AOC Lowest | |
| 2 | L2₹51.9 L+₹11.1 L (27.3%)Rejected-AOC SANTOKH VILA 81 1ST FLOOR PHASE XI MOHALI PUNJAB 160082 | 160082 | L2 | Rejected-AOC Other than lowest |
Tender Value
₹38.0 L
EMD Value
₹75,920
Closing Date
22 Apr 2022, 6:00 pmClosed
Major Auronee Das GE (Utility) Chandimandir
GE (Utility) Chandimandir
GE(U)/CHM-59/2021-22 REPAIR / REPLACEMENT IN RENEWAL OF LT MAIN PANEL IN VARIOUS WARDS OF COMMAND HOSPITAL (WC) UNDER GE (U) CHANDIMANDIR
2022_MES_505884_2
GE (U)/CHM-59/2021-22
Open Tender
Miscellaneous Works
Item Rate
180 days
GE (Utility) Chandimandir
Please refer as per tender documents
7 documents required · 7 mandatory
₹500
Yes
GE (Utility) Chandimandir
₹75,920
Yes
7 Sept 2022
25 Mar 2022
29 Apr 2022
25 Mar 2022
22 Apr 2022
8 Apr 2022
Amount
Supply installation, testing and commissioning of Indoor type LT feeder pillar/distribution boards in replacement (including taking up/ down old feeder pillar) thermolastic polycarbonate IP-65 in accordance with EN 60 529, dust proof, water proof and weather proof, metering panel shock proof, rust proof, corrosion free, acid & chemical resistant, fire retardant & self extinguishing, UV resistant, silica and halogen free recyclable material, glow wire tested at 9600 C in accordance with IEC 60529. The gasket material shall be polyurethane, while the gasket shall be internally embeded. The manufacture of board/panel shall submit a copy of type test report of a board made out of polycarbonate thermoplastic panel in accordance with IEC 60439-1. The report shall mention the following tests performed and passed out satisfactory :- (a) Degree of protection, (b) Temp rise (c) Dielectric properties (d) Short circuit withstand current (e) Effectiveness of protection cicuits (f) Clearance & creepage distance (g) Mechanical operation. Polycarbonate enclouser shall be fire retardant & self extingushing in accordance with IEC 60 695-2-11, DIN VDE 0304 part 3, UL subject 94 for flammability V-2. It shall be tested at glow wire test for 960 degree cent. The impact strength of polycarbonate enclousers/boards i.e the degree of protection against mechanical load shall be in accordance with EN 50298-98 for IK 08.
The lid closing and opening shall be done by quick fastering spring mechanism latches. Suitable accessories for armoured cable shall be supplied with the panel. These accessories shall not be fitted with screws, so that there is no loss of IP, but should be auto fit. The board manufacture shall submit the copy of type test reports for polycarbonate thermoplastic board only. Each board shall have individual rouiten test report of the manufacture & the panel board will have the following accessories. (a) 4 Nos heat shrink insulated bus bar of 1.5 times of incoming MCCB including all connection with aluminium strip.
INCOMING (i) MCCB four pole, 415 Volts, 50 Hz, 200 amps microprocessor based with LIG & LSIG protection and fault indication on MCCB, breaking capacity 36 KA with Ics= 100% Icu - 01 Nos. Make:- ABB/Schnieder/ Siemens/L&T. OUTGOING (i) MCCB four pole 415 volt, 50 HZ, 100 amps microprocessor based with LIG & LSIG protection and fault indication on MCCB, breaking capacity 36 KA with Ics= 100% Icu - 02 Nos. Make:- ABB/Schnieder/ Siemens/L&T. (ii) MCB SP 6-32 amps 240 volt- 60 Nos (iii) MCB SPN 32 amps 240 Volts -02 Nos (iv) Digital type multimeter LCD display complete for Ammeter 0-200 amps, Voltmeter 0-500 volt of size 96x96mm (v) LED indicator lamp (RYB) with control fuses -01Set NOTE:- All the switch gears used in the panel will be of same make.
Supply installation, testing and commissioning of floor mounted indoor cubical type fabricated LT panel board with 2.00 mm thick SS-316L Sheet, base frame 50x50x6mm MS angle. This shall be furnished with requisite test repants of LED indicator lamp (RYB) with control fuses. The report shall mention the following tests perfomed and passed out satisfactory:- (a) Degree of protection (b) Temp rise (c) Dielectric properties (d) Short circuit withstand current (e) Effectiveness of protection circuits (f) Clearance and creepage distance (g) Mechanical operation all as directed by Engr-in-Charge.
The lid closing and opening shall be done by quick fastering spring mechanism latches. Suitable accessories for armoured cable shall be supplied with the panel. A TPN aluminium busbar grade E-9 1 & heat shrinkbar column coated PVC sleeves, control and power wiring with & including insulator, lugs, nuts, bolts, washers, hinges, door gasket lock and other hardware items all as directed by Engr-in-Charge.
INCOMING (i) MCCB four pole, 415 Volts, 50 Hz,160 amps microprocessor based with LIG&LSIG protection and fault indication on MCCB, breaking capacity 36 KA with Ics= 100% Icu - 01 No. Make:- ABB/Schnieder/Siemens/ L&T. OUTGOING (i) MCCB four pole 415 volt, 50 HZ, 63 amps microprocessor based with LIG&LSIG protection and fault indication on MCCB, breaking capacity 36 KA with Ics= 100% Icu - 02 Nos. Make:- ABB/Schnieder/Siemens/ L&T. (ii) MCB SP 6-32 amps 240 volt- 60 Nos (iii) MCB SPN 32 amps 240 Volts -02 Nos (iv) Digital type multimeter LCD display complete for Ammeter 0-200 amps, Voltmeter 0-500 volt of size 96x96mm (v) LED indicator lamp (RYB) with control fuses -01 Set Note:- All the switch gears used in the panel will be of same make.
Supply installation, testing and commissioning of floor mounted indoor cubical type fabricated LT panel board with 2.00 mm thick SS-316L Sheet, base frame 50x50x6mm MS angle. This shall be furnished with requisite test repants of LED indicator lamp (RYB) with control fuses. The report shall mention the following tests perfomed and passed out satisfactory:- (a) Degree of protection (b) Temp rise (c) Dielectric properties (d) Short circuit withstand current (e) Effectiveness of protection circuits (f) Clearance and creepage distance (g) Mechanical operation all as directed by Engr-in-Charge.
The lid closing and opening shall be done by quick fastering spring mechanism latches. Suitable accessories for armoured cable shall be supplied with the panel. These accessories shall not be fitted with screws, so that there is no loss of IP, but should be auto fit. The board manufacture shall submit the copy of type test reports for polycarbonate thermoplastic board only. Each board shall have individual rouiten test report of the manufacture & the panel board will have the following accessories. (a) 4 Nos heat shrink insulated bus bar of 1.5 times of incoming MCCB including all connection with aluminium strip.
INCOMING (i) MCCB four pole, 415 Volts, 50 Hz, 250 Amps microprocessor based with LIG&LSIG protection and fault indication on MCCB, breaking capacity 36 KA with Ics= 100% Icu - 01 No. Make:- ABB/Schnieder/Siemens/ L&T. OUTGOING (i) MCCB four pole 415 volt, 50 HZ, 125 amps microprocessor based with LIG & LSIG protection and fault indication on MCCB, breaking capacity 25 KA with Ics= 100% Icu - 02 Nos. Make:- ABB/Schnieder/Siemens / L&T. (ii) MCB SP 6-32 amps 240 volt- 60 Nos (iii) MCB SPN 32 amps 240 Volts -02 Nos (iv) Digital type multimeter LCD display complete for Ammeter 0-200 amps, Voltmeter 0-500 volt of size 96x96mm (v) LED indicator lamp (RYB) with control fuses -01 Set Note:- All the switch gears used in the panel will be of same make.
Supply installation, testing and commissioning of indoor type LT feeder pillar/distribution boards in replacement (including taking up/ down old feeder pillar) thermolastic polycarbonate IP-65 in accordance with EN 60 529, dust proof, water proof and weather proof,,metering panel shock proof, rust proof, corrosion free, acid & chemical resistant, fire retardant & self extinguishing, UV resistant, silica and halogen free recyclable material, glow wire tested at 9600 C in accordance with IEC 60529. The gasket material shall be polyurethane, while the gasket shall be internally embeded. The manufacture of board/panel shall submit a copy of type test report of a board made out of polycarbonate thermoplastic panel in accordance with IEC 60439-1.
The report shall mention the following tests performed and passed out satisfactory :- (a) Degree of protection, (b) Temp rise (c) Dielectric properties (d) Short circuit withstand current (e) Effectiveness of protection cicuits (f) Clearance & creepage distance (g) Mechanical operation. Polycarbonate enclouser shall be fire retardant & self extingushing in accordance with IEC 60 695-2-11, DIN VDE 0304 part 3, UL subject 94 for flammability V-2. It shall be tested at glow wire test for 960 degree cent. The impact strength of polycarbonate enclousers/boards i.e the degree of protection against mechanical load shall be in accordance with EN 50298-98 for IK 08.
The lid closing and opening shall be done by quick fastering spring mechanism latches. Suitable accessories for armoured cable shall be supplied with the panel. These accessories shall not be fitted with screws, so that there is no loss of IP, but should be auto fit. The board manufacture shall submit the copy of type test reports for polycarbonate thermoplastic board only. Each board shall have individual routine test report of the manufacture & the panel board will have the following accessories. (a) 4 Nos heat shrink insulated bus bar of 1.5 times of incoming MCCB including all connection with aluminium strip.
INCOMING (i) MCCB four pole, 415 Volts, 50 Hz,150 amps microprocessor based with LIG&LSIG protection and fault indication on MCCB, breaking capacity 36 KA with Ics= 100% Icu - 01 No. Make:- ABB/Schnieder/Siemens / L&T. OUTGOING (i) MCCB four pole 415 volt, 50 HZ, 63 amps microprocessor based with LIG&LSIG protection and fault indication on MCCB, breaking capacity 25 KA with Ics= 100% Icu - 02 Nos. Make:- ABB/Schnieder/Siemens/ L&T. (ii) MCB SP 6-32 amps 240 volt- 60 Nos (iii) MCB SPN 32 amps 240 Volts -02 Nos (iv) Digital type multimeter LCD display complete for Ammeter 0-200 amps, Voltmeter 0-500 volt of size 96x96mm (v) LED indicator lamp (RYB) with control fuses -01 Set Note:- All the switch gears used in the panel will be of same make.
Supply installation, testing and commissioning of indoor type LT feeder pillar/distribution boards in replacement (including taking up/ down old feeder pillar) thermolastic polycarbonate IP-65 in accordance with EN 60 529, dust proof, water proof and weather proof, metering panel shock proof, rust proof, corrosion free, acid & chemical resistant, fire retardant & self extinguishing, UV resistant, silica and halogen free recyclable material, glow wire tested at 9600 C in accordance with IEC 60529. The gasket material shall be polyurethane, while the gasket shall be internally embeded. The manufacture of board/panel shall submit a copy of type test report of a board made out of polycarbonate thermoplastic panel in accordance with IEC 60439-1.
The report shall mention the following tests performed and passed out satisfactory :- (a) Degree of protection, (b) Temp rise (c) Dielectric properties (d) Short circuit withstand current (e) Effectiveness of protection cicuits (f) Clearance & creepage distance (g) Mechanical operation. Polycarbonate enclouser shall be fire retardant & self extingushing in accordance with IEC 60 695-2-11, DIN VDE 0304 part 3, UL subject 94 for flammability V-2. It shall be tested at glow wire test for 960 degree cent. The impact strength of polycarbonate enclousers/boards i.e the degree of protection against mechanical load shall be in accordance with EN 50298-98 for IK 08.
The lid closing and opening shall be done by quick fastering spring mechanism latches. Suitable accessories for armoured cable shall be supplied with the panel. These accessories shall not be fitted with screws, so that there is no loss of IP, but should be auto fit. The board manufacture shall submit the copy of type test reports for polycarbonate thermoplastic board only. Each board shall have individual rouiten test report of the manufacture & the panel board will have the following accessories. (a) 4 Nos heat shrink insulated bus bar of 1.5 times of incoming MCCB including all connection with aluminium strip.
INCOMING (i) MCCB four pole, 415 Volts, 50 Hz, 200 amps microprocessor based with LIG&LSIG protection and fault indication on MCCB, breaking capacity 36 KA with Ics= 100% Icu - 01 No. Make:- ABB/Schnieder/Siemens / L&T. OUTGOING (i) MCCB four pole 415 volt, 50 HZ, 63 amps microprocessor based with LIG&LSIG protection and fault indication on MCCB, breaking capacity 25 KA with Ics= 100% Icu - 02 Nos. Make:- ABB/Schnieder/Siemens/ L&T. (ii) MCB SP 6-32 amps 240 volt- 60 Nos (iii) MCB SPN 32 amps 240 Volts -02 Nos (iv) Digital type multimeter LCD display complete for Ammeter 0-200 amps, Voltmeter 0-500 volt of size 96x96mm (v) LED indicator lamp (RYB) with control fuses -01 Set Note:- All the switch gears used in the panel will be of same make.
Sub main wiring (with approved colour coding as per IS) with single core FRLS PVC insulated multistranded copper conductor cable 1.1 KV grade ( four runs of main cable(RYB&N) alongwith one run of single core FRLS PVC insulated flexible stranded copper Conductor 1.1 KV grade of earth for earthing drawn in existing conduit/ concealed conduits with following size. Make of wire-Havells/Polycab/KEI/Anchor
(a) 4 run of 16 Sqmm cable + 1 run of 16 Sqmm
(b) 4 run of 25 Sqmm cable + 1 run of 25 Sqmm
Sub main wiring (with approved colour coding as per IS) with single core FRLS PVC insulated multistranded copper conductor cable 1.1 KV grade (( four runs of main cable(RYB&N) alongwith one run of single core FRLS PVC insulated flexible stranded copper Conductor 1.1 KV grade of earth for earthing drawn into Suitable size of PVC conduit/ concealed conduits with following size. Make of wire-Havells/Polycab/KEI/Anchor
4 run of 16 Sqmm cable + 1 run of 16 Sqmm
4 run of 25 Sqmm cable + 1 run of 25 Sqmm
Supply and fixing, MCCB 4 Pole, 415 V, fixed type, 250 Amps with breaking capacity 36 KA. Make-Seimens/ABB/Legrand
Supply and fixing, MCCB 4 Pole, 415 V, fixed type, 200 Amps with breaking capacity 36 KA. Make-Seimens/ABB/Legrand
Supply and fixing, MCCB 4 Pole, 415 V, fixed type, 160 Amps with breaking capacity 36 KA, Make-Seimens/ABB/Legrand
chahalbuilders
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .