Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.3 LAccepted-AOC | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹25.7 L+₹1.4 L (5.80%)Rejected-AOC | L2 | Rejected-AOC Not Lowest Bidder | |
| 3 | L3₹28.7 L+₹4.5 L (18.3%)Rejected-AOC | L3 | Rejected-AOC Not Lowest Bidder | |
| 4 | L4₹29.2 L+₹5.0 L (20.5%)Rejected-AOC | L4 | Rejected-AOC Not Lowest Bidder |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
2 Jan 2021, 6:00 pmClosed
GARRISON ENGINEER NORTH SECUNDERABAD
Garrison Engineer North 35 Allenby Lines Secunderabad 500087
REPAIRS REPLACEMENT OF INTERNAL WIRING FITTINGS FIXTURES IN ZONE F AREA UNDER AGE E M N OF GE N SECUNDERABAD
2020_MES_400327_1
8920
Open Tender
Civil Works
Works
270 days
Garrison Engineer North 35 Allenby Lines Secundera
For Enlisted Contractors Class D Category bi and for Un Enlisted contractors meeting the Enlistment criteria for appropriate class and category along with EMD
6 documents required · 6 mandatory
₹500
GARRISON ENGINEER NORTH SECUNDERABAD
₹70,000
Yes
11 Feb 2021
3 Dec 2020
4 Jan 2021
3 Dec 2020
2 Jan 2021
18 Dec 2020
3 Dec 2020 - 17 Dec 2020
Amount
Taking down existing unserviceable point wiring of any description/type/ size of light/fan/power/two way/bell etc on TW batten/conduit including removal of batten / conduit / gutties / wooden boards / switches / sockets / regulators/ light fittings etc and removal of unserviceable material out of site area and making good the disturbed surfaces of wall/ceiling so as to match with the existing finishes complete all as specified & as directed.
Disconnecting and removing the MCB DBs from any height ,stripping out the fitting for examine replacement of US spare parts, reassembling, refixing in original position including minor repairs for the smooth functioning and testing complete all as specified & as directed.
M & L for Point wiring with 1.5 Sq mm copper conductor single core PVC insulated FRLS 1100 Volts multistranded drawn through and including rigid PVC conduit surface and conduit accessories of suitable dia medium grade and pressed steel terminal boxes including fixing/grouting sunken/ surface as per site requirement covered with suitable laminated sheet for fixing switches / sockets/ regulators etc including running up of 1.5 Sq mm copper conductor PVC insulated cable as earth continuity conductor along with wiring and connecting to the common earth dolly all as specified for One light/fan point controlled by one, one way switch 5 amps, SP Note: Cutting/chases will be measured and paid seperately
All as per Sl item No 3 here in before, but for One light point controlled by two 2 - w a y s w i t c h 5 amps, SP
All as per Sl item No 3 here in before, but for One 3 pin 5 Amps switch socket outlet point controlled by one switch on independent board .
All as per Sl item No 3 here in before, but for One 3 point 5 Amps switch socket outlet point controlled by one switch on the same board.
All as per Sl item No 3 here in before, but for One Bell point controlled by one, one way switch 5 amps, SP
All as per Sl item No. 3 here in before, but for using 2.5Sqmm single core copper conductor cable of multistranded PVC insulated sheathed FRLS 1100 Volts grade for 3 Pin 15 Amps switch socket combination point on independent board including running of 2.5 Sq mm copper conductor PVC insulated cable as earth continuity conductor complete all as specified & as directed.
M & L for Point wiring on surface conduit with 1.5 Sq mm FRLS copper conductor single core PVC insulated sheathed 1100 V multistranded drawn through conduit and including rigid 20 MM PVC conduit and conduit accessories of suitable dia medium grade and modular accessories including fixing/grouting sunken/ surface along with existing flush box of sutiable thickness covered with suitable modular cover plate including running up of 1.5 Sq mm copper conductor PVC insulated cable as earth continuity conductor along with wiring and connecting to the common earth dolly for fixing the switches/ sockets/ regulators etc all as specified for one Light/Fan Point Controlled by One Switch complete all as specified & as directed. Note: Cutting/chases will be measured and paid seperately
All as per Sl item No. 9 here in before, but for One light point controlled by two 2 - w a y s w i t c h 5 amps, SP complete all as specified & as directed.
All as per Sl item No. 9 here in before, but for One 3 pin 5 Amps switch socket outlet point controlled by one switch on independent board complete all as specified & as directed.
All as per Sl item No. 9 here in before, but for One 3 point 5 Amps switch socket outlet point controlled by one switch on the same board complete all as specified & as directed.
All as per Sl item No. 9 here in before, but for One Bell point controlled by one, one way switch 5 amps, SP complete all as specified & as directed.
All as per Sl item No. 9 here in befor, but for using 2.5 Sqmm single core copper conductor cable of multistranded PVC insulated sheathed FRLS 1100 Volts grade for 3 Pin 15 Amps switch socket combination point on independent board including running of 2.5 Sq mm copper conductor PVC insulated cable as earth continuity conductor complete all as specified & as directed.
S & F switch piano single pole flush type 5 amps, 230 volts complete all as specified & as directed.
S & F switch piano single pole flush type 15 amps, 230 volts complete all as specified & as directed.
S & F Switch piano single pole two way flush type 5 Amps capacity 230 volts complete all as specified & as directed.
S&F bell push 5 A flush type complete all as specified & as directed.
Supply and fix socket outlet flush type multipurpose 2 in 1, 3 Pin, 5 amps, 230 volts complete all as specified & as directed.
Supply and fix socket outlet flush type multipurpose 2 in 1, 3 Pin, 5/15 amps, 230 volts complete all as specified & as directed.
S & F switch socket combination flush type multipurpose 2/3 pin 5 amps 2 in 1 230 Volts complete all as specified & as directed.
S & F switch socket combination 2 in 1 multipurpose 3/5 pin 5/15 amps flush type with complete all as specified & as directed.
S & F electronic type regulator stepped Switch type heavy duty for ceiling fan suitable to work on 230 volts complete all as specified & as directed.
S & F electronic type regulator stepped socket type heavy duty for ceiling fan suitable to work on 230 volts complete all as specified & as directed.
S & F switch single pole Modular switch 1 way 6 Amps, 1 Module complete all as specified & as directed.
S & F switch single pole Modular switch 1 way 16 Amps, 1 Module complete all as specified & as directed.
S & F switch piano single pole Modular switch 2 way 6 Amps, 1 Module complete all as specified & as directed.
S&F Modular Bell Push 6A, 1 Module complete all as specified & as directed.
Supply and fix socket outlet modular type multipurpose 2/3 Pin, 6 amps, 230 volts combined 2 Module complete all as specified & as directed.
Supply and fix socket outlet modular type multipurpose 2/3 Pin, 6/16 amps, 230 volts combined 2 Module complete all as specified & as directed.
S & F Modular ceiling fan regulator stepped type heavy duty suitable to work on 230 volts, 1Module complete all as specified & as directed.
Supply & Replace Modular White cover plate with frame of 1 Module complete all as specified & as directed.
Supply & Replace Modular White cover plate with frame of 3 Module complete all as specified & as directed.
Supply & Replace Modular White cover plate with frame of 4 Module complete all as specified & as directed.
Supply & Replace Modular White cover plate with frame of 6 Module complete all as specified & as directed.
Supply & Replace Modular White cover plate with frame of 12 Module complete all as specified & as directed.
S&F buzzer working on 230 volts AC Supply complete all as specified & as directed.
S&F bell ding dong working on 230 volts AC Supply complete all as specified & as directed.
S & F lamp holder insulated body surface bakelite with back plate suitable for angle / batten fittings complete all as specified & as directed.
S & F ceiling rose three terminal surface bakelite type AC 50 Hz 230 volts of size 65 x 50 mm complete all as specified & as directed.
S & F wall mounted box type LED batten suitable for 20w with LED lamp, 6500K, 140-270Volts, along with integrated driver complete with 2 Nos round blocks with necessary fixing arrangements and connecting to the point wiring with necessary flexible copper conductor of multistrand three core 1.5 sqmm of suitable length from fitting to the ceiling rose with necessary mounting arrangements including all accessories with new 3 core multistranded copper conductor of size 23/0.193 from ceiling rose to fitting acomplete all as specified & as directed. Make: Havells-REGALBATTENT8UPTO1X22WDSBSWH, Tube- PHOTONULTRAE201213T8SSTL20LED865SPC or Crompton - IGP161LT8-16, TUBE- LT8-20-865-(2), Wipro, Bajaj
S & F LED tube rod suitable for 20w with LED lamp , 6500K, 140-270Voltsalong with integrated driver complete all as specified & as directed. Make: Havells - PHOTONULTRAE201213T8SS TL20LED865SPC, Crompton -TUBE- LT8-20-865-(2), Wipro, Bajaj
M&L LED security Light luminaire 25 watts with deep drawn housing including with necessary flexible copper conductor of multistrand three core 1.5 sqmm of suitable length and all accessories, with suitable pipe bracket 43 mm dia 0.60 Mtr length fixed on wall with suitable flat iron clamps and nut bolts. all as specified and as directed. Make: Havells- ENDURAPEARLSL2WLED757SASYTO PCMP or Crompton - LST-25-CDL-M or Wipro, Bajaj
S & F 15watt bulk head luminaire suitable for outdoor with high brightness giving glare free light and complete all as specified & as directed. Make : Havells: HEXAFT10WLED857SSYMBOPC, Crompton & Wipro
S & F wall mounted LED batten suitable for 10w along with integrated driver complete with 2 Nos round blocks with necessary fixing arrangements and connecting to all accessories with new 3 core multistranded copper conductor of size 23/0.193 from ceiling rose to fitting complete all as specified & as directed. Make: Havells-LUMILINEPLUBS10WLED865PCSS ,or Crompton - LDL-10-WW or Wipro, Bajaj
Supply & Replace MCB SP 6 to 32 Amps 240 volts for fixing on MCB DB's complete all as specified & as directed. Make:Havells - CAT Part No DHMGCSPF006-032 or equivalent in HPL/ STANDARD- DSMGCSPF006-032 Or L&T - BB10320C as approved by GE
Supply & Replace MCB SPN 40 to 63 Amps 240 volts for fixing on MCB DB's complete all as specified & as directed. Make: Havells - CAT Part No DHMGCSNF040 or equivalent in HPL/ STANDARD- DSMGCSNF040 or L&T - BB20400C as approved by GE.
Supply & Replace MCB Four pole, 415 volts suitable for fixing on MCB DB of capacity 63/100 Amps including removing the existing US one and making good the distrubed surface to match with the existing surface complete all as specified & as directed. Make: Standard- DSMGCFPF063 or L&T - BB40630C
Supply & Replace MCB Three pole, 415 volts suitable for fixing on MCB DB of capacity 63/100 Amps including removing the existing US one and making good the distrubed surface to match with the existing surface. Make:Standard- DSMGCTNF063 L&T - BB30630C
S & F sheet metal enclosure MCB DB SPN 4 way with 200 amps rated bus bar 240 volts double door with locking system complete all as specified & as directed. Make : Havells - CAT Part No DHDPSHODRWO4 or equivalent in HPL/ STANDARD- DSDPSHODIW04 & L&T- DBSPN004DD as approved by GE
S & F sheet metal enclosure MCB DB SPN 8 way with 200 amps rated bus bar 240 volts double door with locking system complete all as specified & as directed. Make : Havells - CAT Part No DHDPSHODRWO8 or equivalent in HPL/ STANDARD- DSDPSHODIW08 & L&T- DBSPN008DD as approved by GE
S & F sheet metal enclosure MCB DB SPN 12 way with 200 amps rated bus bar 240 volts double door with locking system complete all as specified & as directed. Make : Havells - CAT Part No DHDPSHODRW12 or equivalent in HPL/ STANDARD - DSDPSHODIW12 & L&T- DBSPN012DD as approved by GE.
S & F Vartical type TPN distribution board of 4 way double door with incoming MCCB TPN 415 volts AC, 3 phase, 50 Hz, 25 KVA with fixed magnetic setting for current ranging of capacity 63 Amps 10 KA (MCCB FP Confirming to IS 13947 (P-2) IEC: 947) made out of CRCA sheet housing with powder coated confirming to IS 13032, IS 8623, BS 5486 accomadated suitably in a mild steel enclosure weather proof made out of 3 mm thick mild steel sheet having hinged and robust locking arrangement including painting by red-oxide one coat and duly powder coated complete all as specified and as directed.
S & F Horizontal type TPN DB 8 way double door made out of CRCA sheet housing with powder coating & confirming to IS 13032, IS 8623, BS 5486 accomdated suitably in a MS enclosure weather proof made out of 3 mm thick MS sheet having hinged and robust locking arrangement including painting by red-oxide one coat and powder coated complete all as specified & as directed. Make :STANDARD - GEDSDPTHPDRW08 as approved by GE
S & F Single pole and Neutral enclosure with a two pin and earth plug and socket metal clad complete with one sing pole MCB 20 Amps (AC Box) complete all as specified & as directed.
M & L Submain wiring with 2 runs of single core 4 sqmm PVC insulated sheated multistranded FRLS 1100 volts grade with copper conductor drawn through existing non-metalic rigid PVC conduit and conduit accessories of medium grade not less than 20mm dia including one run of single core 4 sqmm PVC insulated sheated multistranded 1100 volts grade with copper conductor cable as earth continuty conductor along with the wiring and connected from DB to DB/main board including removing the existing unserviceable submain riwing complete all as specified & as directed. Note: 3 runs of 4 Square mm cable and 1 run of PVC conduit with accessories shall be measured as 1 unit of running metre.
M & L Submain wiring with 2 runs of single core 6 sqmm PVC insulated sheated multistranded FRLS 1100 volts grade with copper conductor drawn through existing non-metalic rigid PVC conduit and conduit accessories of medium grade not less than 25mm dia including one run of single core 6 sqmm PVC insulated sheated multistranded 1100 volts grade with copper conductor cable as earth continuty conductor along with the wiring and connected from DB to DB/main board including removing the existing unserviceable submain riwing complete all as specified and as directed. Note: 3 runs of 6 Square mm cable and 1 run of PVC conduit with accessories shall be measured as 1 unit of running metre.
Supply and replace Bi pin holder suitable for 40 to 20 Watts tubes(pin & screw type) complete all as specified & as directed.
Supply and replace PVC rectangular box (Gang box) with 5 Amps switch socket complete all as specified & as directed.
Supply and replace PVC rectangular box (Gang box) with 5/15 Amps switch socket complete all as specified & as directed.
Supply and replace Plug top 15 Amps 3 pin 250 Volts complete all as specified & as directed.
Earthing complete with galvanised steel earth plate electrode 60cm x 60cm x 6mm thick burried directly in ground to a depth not less than 2.25 m below ground level with top edge of earth plate not less than 1.5 m below normal ground level connected to GI earth lead wire 4 mm dia by means of bolts, nut, check nuts and washers etc of galvanised iron and earth lead protected by provision of GI pipe 15 mm bore of medium grade from earth electrode to DBs/Main switch all as shown in Electrical Plate No 3 of SSR Part I and connected to main switch board including excavation and earth work in any type of soil, PCC chamber in 1:2:4 Type B-1 using 20 mm graded stone aggregate 75 mm thick RCC cover in 1:2:4 type B-1 reinforced with 6mm dia bars at 75mm c/c both ways with 12mm dia MS bar handle made to shape, 20 mm dia medium grade GI watering pipe perforated at bottom 1.75m long with funnel and wire mesh, common salt and charcoal filling complete including testing on complete all as specified & as directed. Note: GI pipe 15mm dia & GI earth lead 4mm dia upto 7.5 m length is deemed to be included in quoted rate)
Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earting etc as required 4mm dia galvanised iron or steel wire complete all as specified & as directed.
Supply and replace PVC wire of Flexible cord with copper conductor multistanded of twin core 23/0.198 complete all as specified & as directed.
Supply and replace PVC copper wire of 1.5 sq mm complete all as specified & as directed.
Supply and replace PVC copper wire of 2.5 sq mm complete all as specified & as directed.
Supply and replace PVC copper wire of 4 sq mm complete all as specified & as directed.
Supply and replace PVC copper wire of 6 sq mm complete all as specified & as directed.
M&L for Cutting chases, pinning in. making good to facings where required and pointing in cement mortar 1:3 to ends or edges of andings, steps, cills, sunshades, shelves, lintels, etc.; and cutting chases for concealed water tubing or concealed conduit wiring, etc., and making good, cutting not exc 10 cm girth complete all as specified & as directed.
Taking down ceiling fans 48”/56” sweep or Exhaust fans upto 300mm, remaining/cleaning of dust properly cleaning, greasing& overhualing of bearings including refixing and connecting up complete all as specified & as directed. Note : Replacement of defective/worn out parts will be measured & paid for separately
Supply & fix 2.00 Mfd capacitor for ceiling fan complete all as specified & as directed.
Supply & fix 2.50 Mfd capacitor for ceiling fan complete all as specified & as directed.
Supply & fix 3.15/4.00 Mfd capacitor for exhaust fan complete all as specified & as directed.
Supply & fix ball bearing/Gun Metal Bush of exsiting ceiling fans on site complete all as specified & as directed.
Supply & fix for Flexible copper three core of size 23/0076” wire/cable complete all as specified & as directed.
Supply & fix for ‘U’ clamps complete with nut, bolts & split pins Heavy duty, suitable for existing ceiling fan.on site complete all as specified & as directed.
Supply & fix M.S. rod for ceiling fans 3 ft long with both end suitable size holes and cut mark complete all as specified & as directed.
Supply & fix Bolts, Nuts & washers for fan blades fixing of ceiling fan of any make/size/type as per site requirement ( 6 Nos for each set) complete,asuitable for existing ceiling fan.on site complete all as specified & as directed.
Supply & fix Supply And in replacement of fan blades of 1200/1400mm sweep size of metal blades-03 nos complete all as specified & as directed.
Rewinding of burnt Ceiling fan motor of any size with super enameled copper wire of suitable size as per details given below of any make, type, model incl transporation (inclusive of material & labour) complete all as specified & as directed.
Rewinding of burnt Exhaust fan motor of 300mm Sweep with super enameled copper wire of suitable size ncluding ball bearings , bush as per details given below of any make, type, model incl transporation (inclusive of material & labour) complete all as specified & as directed.
Taking down the geyser of 25 /35 litres capacity from its mounting by removing all water and electric connection and disassembling the geyser, Descaling cleaning the inner tank thoroughly and there should not be any bad test of water. Examining the water tightness of storage tank after cleaning. Examining the physical condition of thermostat, base assembly fusible plug and outer tank for its serviceability. Inspection of pilot lamps. Reassembling the all the geyser parts and testing including checking all electrical system (ensuring there is no current leakage) and hydraulic testing. Re-fixing the Geyser and making electric connection, water inlet and outlet connection and testing and checking of all the functioning of water inlet outlet valves connected with geysers complete all as specified & as directed. Note : Replacement of defective/worn out parts will be measured & paid for separately
All as per Sl item No 82 here in before, but for 50 litres capacity Geyser complete all as specified & as directed.
Supply and fix rubber PVC gasket to ensure water tightness for 25/35 liters capacity complete all as specified & as directed.
Supply and fix rubber PVC gasket to ensure water tightness for 50 liters capacity complete all as specified & as directed.
Supply & fix MS base plate including load relay of any type with inlet and outlet pipes of suitable size with screws as per requirement complete all as specified & as directed.
Supply & fix heating element of the 1.5KW rating as required at site including rubber washers of any make and type complete as per sample complete all as specified & as directed.
Supply & fix heating element of the 2KW rating as required at site including rubber washers of any make and type complete as per sample complete all as specified & as directed.
Supply & fix Steel inner tank of 25 litre capacity geyser tank by made out of steel sheets appropriate thickness complete all as specified & as directed.
Supply & fix Steel inner tank of 50 litre capacity geyser tank by made out of steel sheets appropriate thickness complete all as specified & as directed.
Supply & fix thermostat for the geysers of the 25 to 35 Liters capacities complete all as specified & as directed.
Supply & fix thermostat for the geysers of the 50 Liters capacities complete all as specified & as directed.
Supply & Replace Air Release Valve of Existing Size complete all as specified & as directed.
Supply and Replace Indication lamp of Existing Size/Model (Set of Two) Red & Green complete all as specified & as directed.
S&F in replacement of 1100 Volt grade cable flexible 3 core PVC insulated PVC sheathed with stranded copper conductor of size 2.5 sqmm complete all as specified & as directed.
gsrinivasarao
EXELLENT POWER CORPORATION
Srinivash Engineers
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .