Loading…
Loading…
Tender ID
| # | Company | Status |
|---|---|---|
| 1 | Accepted-Technical 29 108 A STREET NO 10 VISHWAS NAGAR DELHI 110032 | DELHI | SHAHDARA | DELHI | 110032 | Accepted-Technical Admitted |
| 2 | Accepted-Technical | Accepted-Technical Admitted |
| 3 | Rejected-Technical 0 MADHUPUR SAKARDAHA MADHUPUR SAKARDAHA SARAON MADHUPUR SAKARDAHA ALLAHABAD UTTAR PRADESH 212502 | PRAYAGRAJ | UTTAR PRADESH | 212502 | Rejected-Technical Rejected being due to No in WLR QE Dec 2025 |
Tender Value
₹1.2 Cr
EMD Value
₹2.0 L
Closing Date
21 Apr 2026, 6:00 pmClosed
HQ CWE PRAYAGRAJ
HQ CWE NEW CANTT PRAYAGRAJ
REPAIR/ MAINT OF INTERNAL ELECTRIFICATION, WATER SUPPLY, DG SET AND FIRE FIGHTING OF OFFICE COMPLEX AND MD ACCN OF DAD AREA AT NEW CANTT UNDER GE (WEST) PRAYAGRAJ.
2026_MES_756655_1
82070/W/E8
Open Tender
Civil Works
Item Rate
270 days
Prayagraj
Class B and Category b(i)
6 documents required · 6 mandatory
₹1,000
GE (West) Prayagraj
₹2.0 L
Yes
6 May 2026
17 Mar 2026
28 Apr 2026
17 Mar 2026
21 Apr 2026
7 Apr 2026
Taking down carefully sub main wiring of any type/size complete with MCB DBs MCB, isolators wooden batten, concealed/surface conduit/casing caping etc. removing materials including accessories for taking credit and making good disturbed surface to match the existing complete all as specified & directed.
M&L for concealed sub main wiring using FRLSH PVC insulated, unsheathed stranded copper conductor cable single core of following sizes of voltage rating upto and including 1100 volts drawn in and including rigid PVC concealed conduit of dia not less than 20 mm dia medium grade with all fittings and accessories along with one run of PVC insulated unsheathed stranded copper conductor as earth continuity conductor complete all as specified & directed. Note:- (i) Two runs of single core PVC cable with one run of earth conductor and conduit shall be measured as one length. (ii) The cost for cutting, chases required and making good the disturbed surface shall deemed to be included in the quoted unit rate
2x4.0 sq. mm + 1x4.0 sq. mm earth wire.
2x6 sq. mm + 6x sq. mm earth wire.
2x10 sq. mm + 10x sq. mm earth wire.
4x10.0 sq. mm +1x10.0 sq. mm earth wire.
M&L for surface sub main wiring using FRLSH PVC insulated, unsheathed stranded copper conductor cable single core of following sizes of voltage rating upto and including 1100 volts drawn in and including non metallic PVC rigid, medium grade not less than 20mm dia surface conduit / non metallic PVC casing and caping with all fittings and accessories along with one run of PVC insulated unsheathed stranded copper conductor as earth continuity conductor complete all as specified & directed. Note:- (i) Two runs of single core PVC cable with one run of earth conductor and conduit shall be measured as one length. (ii) The cost for cutting, chases required shall deemed to be included in the quoted unit rate.
2x2.5 sq. mm + 1x2.5 sq. mm earth wire.
2x4.0 sq. mm + 1x4.0 sq. mm earth wire.
2x6.0 sq. mm + 6x sq. mm earth wire.
Taking down carefully aluminium / copper point wiring any type for one light , fan, socket power point or buzzer controlled by one switch complete including fitting / fixtures such as switches, ceiling roses, holder, socket, light fitting etc; for credit and making good disturbed surfaces of walls, ceilings etc, complete all as specified & directed.
M&L for point wiring with FRLSH PVC insulated unsheathed stranded copper conductor cable 1.5 Sqmm (nominal area) 1100 volts grade, along with one single run of same size and type of copper wire as continuous earth wire to common earth dolly drawn in and including non metallic PVC rigid, medium grade concealed conduit with all fixing accessories of 20mm dia, and including modular sunken box, cover plate / frame for any module as requiredat site with all accessories and including fixing with switch, socket, ceiling rose, fan regulator,holder, etc. and making good to disturbed conceal surfaces complete all as specified and directed for the following :- Note: (a) Colour code of wire shall be strictly followed , Red for Phase , Black for neutral and green for earth wire. (b) The unit rate quoted is deemed to be inclusive of cost of cutting chases in wall for providing concealed conduit and making good to match with existing finish/surface. (c) Only 04 point shall be allowed is one circuit.
One light/fan/bell point controlled by one switch.
One point for socket outlet 5 amps on independent board.
One point for socket outlet 5 amp same board.
One light point controlled by two 2-way switches.
All as per item No. 5 above but for one socket outlet 16 Amp on independent board with 4.0 Sq mm cable and 4.0 Sq mm earth wire.
M&L for point wiring with FRLSH PVC insulated unsheathed stranded copper conductor cable 1.5 Sqmm (nominal area) 1100 volts grade, along with one single run of same size and type of copper wire as continuous earth wire to common earth dolly drawn in and including non metallic PVC rigid, medium grade concealed conduit with all fixing accessories of 20mm dia, using new pressed steel sunk terminal boxes of thickness not less 1.2mm, new 3mm thick laminated sheet cover with brass screw and cup washers with all accessories including fixing with switch, socket, ceiling rose, fan regulator,holder, etc. and making good to disturbed conceal surfaces complete all as specified and directed for the following :- Note:(a) Colour code of wire shall be strictly followed , Red for Phase , Black for neutral and green for earth wire. (b) The unit rate quoted is deemed to be inclusive of cost of cutting chases in wall for providing concealed conduit and making good to match with existing finish/surface
One light/fan/bell point controlled by one switch.
One point for socket outlet 5 amps on independent board.
One point for socket outlet 5 amp same board.
One light point controlled by two 2-ways switches.
All as per serial item No. 6 above but for one socket outlet 16 Amp on independent board with 4.0 Sq mm cable and 4.0 Sq mm earth wire.
M&L for point wiring with FRLSH PVC insulated unsheathed stranded copper conductor cable 1.5 Sqmm (nominal area) 1100 volts grade, along with one single run of same size and type of copper wire as continuous earth wire to common earth dolly drawn in and including non metallic PVC casing and caping/PVC conduit of appropriate size on wall/roof surface with all fixing accessories including fixing with switch, socket, ceiling rose, fan regulator,holder, etc. and polycarbonate modular/modular GI sunken boxs, and modular sunken box, cover plate / frame for any module as required at site with all accessories and making good to disturbed conceal surfaces complete all as specified and directed for the following :- Note: (a) Colour code of wire shall be strictly followed , Red for Phase , Black for neutral and green for earth wire.
One light/fan/bell point controlled by one switch.
One point for socket outlet 5 amps on independent board.
One point for socket outlet 5 amp same board.
All as per item No. 7 above but for one socket outlet 16 Amp on independent board with 4.0 Sq mm cable and 4.0 Sq mm earth wire.
S&F in replacement of A C starter unit consisting of one 25 Amp capacity starter, one 240 V 25 Amps 10 KA SPN MCB, one 25 Amps socket and one 25 Amps plug top prewired complete as specified after taking out old unserviceable starter unit all as directed.
Receiving complaints from complaint cell, lodged by the occupants of electrification nature, rectification of the fault as per the complaint lodged by the user onward KWH meter in respect of main distribution board having switch fused, MCB distribution board in sheet metal enclosure, point wiring fixture for light/fan/bell/light/Ceiling Fan, testing of Electronic meters or power socket complete repairs to the extent by removing connections from the system removing faults in wires, battens, conduit, sunken boxes, junction boxes, main switches, MCBs/DBs utility light fitting, lamp holders AC ceiling/exhaust fans and other connected fixtures of the internal electrification including providing of petty stores such as wires of appropriate size and conductor matching to existing one up to the length of 1 mtr including insulation tap, screws, nuts as required to rectified the fault with regard to the complaint lodged and refixing of fittings, fixture to their position as dismantled complete all as directed at site to the entire satisfaction of Engr-in-charge/users. Note - (i) All spares required and accessories, required for repairing will be paid under relevant items of this schedule. Instructions -(a) Attending complaint including taking down/refixing of LED light fittings and repair/ Replacement part (Labour ) and minor repair shall be measured against under relevant of Sch "A items . (b) Cost of material and labour for replacement of new items shall be measured and paid separately . (c) Panalty : Penalty for not attending complaints within stipulated time frame will be the liable to Rs 500.00 of per day for non attending the complaints multiple number of days of delay (d) Priority -1 (to be done within 8 hours from time of lodging complaint): No light, repair/replacement of switches, fan regulator, replacing burnt/damaged wiring, replacement of burnt MCBS and Main switch, voltage fluctuation, current leakage and replacement of tube lights.
Supply only in repalacement of modular switch 1 way, 6 amps, 230V AC, one way.
Supply only in repalacement of modular socket out let 2-in-1, 3 pin, 6 amp flush type 2 module.
Supply only in repalacement of modular switch flush type 16 amps, 230V AC single pole one way.
Supply only in repalacement of modular socket out let 2-in-1, 3 pin, 5 & 16 amp flush type 2 module.
Supply only in repalacement of modular switch 2 way, 6 amps, 230V AC, one way.
Supply only in repalacement of modular bell push flush type 6 amp, 1 module SP, 230V AC.
Supply only in repalacement of modular fan regulator, 5 stepped, electronic type, single phase, 120 watt, socket size incl connection.
Supply only in repalacement of switch piano flush button single pole one way 6 amps.
Supply only in repalacement of switch 2 way, 6 amps, 230V AC, one way
Supply only in repalacement of socket outlet 5 pin 6 amp flush type.
Supply only in repalacement of socket out let multipurpose 3 pin 16 amp and one 3 pin 6 amp controlled by one switch.
Supply only in repalacement of switch piano flush button single pole one way 16 amps.
Supply only in repalacement of switch & socket out let combination multipurpose 3 pin 16 amp and one 3 pin 6 amp controlled by one switch.
Supply only in repalacement of ceiling fan regulator step type 240 Volt AC
Supply only in repalacement of PVC insulation tape of width -18mm in length of 25 mtr ISI marked for proper insulation of joints in wire.
Supply only in repalacement of condenser of 2.5 Mfd , 240 volt, AC confirming to IS -1709 suitable for fans.
Supply only in repalacement of condenser of 3.15 Mfd , 240 volt, AC confirming to IS -1709 suitable for fans.
Supply only in repalacement of ceiling rose surface backelite three terminals.
Supply only in repalacement of call bell Dingdong type AC 230 Volts single pole.
Supply only in repalacement of bell push flush type 6 amp, 230V AC.
Supply only in replacment of Modular metal flush box of 12 module.
Supply only in replacment of Modular metal flush box of 8 module.
Supply only in replacment of Modular metal flush box of 6 module.
Supply only in replacment of Modular metal flush box of 4 module.
Supply only in replacment of Modular metal flush box of 3 module.
Supply only in replacment of Modular metal flush box of 2 module.
Supply only in replacment of Modular white plate cover with frame of 12 module.
Supply only in replacment of Modular white plate cover with frame of 8 module.
Supply only in replacment of Modular white plate cover with frame of 6 module.
Supply only in replacment of Modular white plate cover with frame of 4 module.
Supply only in replacment of Modular white plate cover with frame of 3 module.
Supply only in replacment of Modular white plate cover with frame of 1/2 module.
Supply and fixing Angle/Batten type Lamp holder, PVC/Polycarbonate type with back plate suitable for light fittings.
Supply & Fix in replacment single pole and neutral enclosure with a two pin earth plug and socket complete with one single pole MCB 20 Am "B" Curve.complete all as specified and directed.
Taking down main switches fuse unit, MCB/Kit kat distribution board any type/size/capacity with steel enclosure along with MCB’s /Kit kat fuse of any amps/ways including wooden board or from steel board and making good disturbed surfaces complete all as specified and as directed. Note: Any disturbed surfaces of wall will be matched properly as the existing colour surfaces.
Supply and fixing in replacement of factory made epoxy polyester powder coated distribution board SP & N 4 way fabricated from recommended thick CRCA sheet with metal double door (IP-43 protection ) fixed flush to wall and suitable for universal mounting and including aluminium alloy bus bar, Neutral bar, standard DIN rail, eath bar and cable ties for cable management, top and bottom removable gland plates with knockouts and suitable for one DP MCB as incomer and 2 SP MCBs as outgoings complete all as specified and conforming to IS: 8623 alongwith cable end box for above DB all as specified and directed. Note:- (a) MCBs shall be measured and paid separately. (b) All cables terminating into MCBs shall be connected by using suitable copper lugs/thimbles/sleeves and its cost shall be deemed to be included under respective item of Sch. (c) making good and finishing of disturbed surfaces matching with the exisitng surfaces plastering, wood box work, painting if reqd any type incl ecessary fixing arrangements complete deemed to be included under respective item of sch. (d) Make of MCBs /MCCBs and MCB DBs shall be same makes.
Supply and fixing in replacement of factory made epoxy polyester powder coated distribution board SP & N 8 way fabricated from recommended thick CRCA sheet with metal double door (IP-43 protection ) fixed flush to wall and suitable for universal mounting and including aluminium alloy bus bar, Neutral bar, standard DIN rail, eath bar and cable ties for cable management, top and bottom removable gland plates with knockouts and suitable for one DP MCB as incomer and 6 SP MCBs as outgoings complete all as specified and conforming to IS: 8623 alongwith cable end box for above DB all as specified and directed. Note: (a) MCBs shall be measured and paid separately. (b) All cables terminating into MCBs shall be connected by using suitable copper lugs/thimbles/sleeves and its cost shall be deemed to be included under respective item of Sch. (c) making good and finishing of disturbed surfaces matching with the exisitng surfaces plastering, wood box work, painting if reqd any type incl ecessary fixing arrangements complete deemed to be included under respective item of sch. (d) Make of MCBs/MCCBs and MCB DBs shall be same makes.
Supply and fixing in replacement of factory made epoxy polyester powder coated distribution board SP & N 12 way fabricated from recommended thick CRCA sheet with metal double door (IP-43 protection ) fixed flush to wall and suitable for universal mounting and including aluminium alloy bus bar, Neutral bar, standard DIN rail, eath bar and cable ties for cable management, top and bottom removable gland plates with knockouts and suitable for one DP/SPN MCB as incomer and 8 SP MCBs as outgoings complete all as specified and conforming to IS: 8623 alongwith cable end box for above DB all as specified and directed. Note- (a) MCBs shall be measured and paid separately. (b) All cables terminating into MCBs shall be connected by using suitable copper lugs/thimbles/sleeves and its cost shall be deemed to be included under respective item of Sch. (c) making good and finishing of disturbed surfaces matching with the exisitng surfaces plastering, wood box work, painting if reqd any type incl ecessary fixing arrangements complete deemed to be included under respective item of sch. (d) Make of MCBs/MCCBs and MCB DBs shall be same makes.
Supply and fixing in replacement of factory made epoxy polyester powder coated distribution board TP & N 4 way fabricated from recommended thick CRCA sheet with metal double door (IP-43 protection ) door IK 09 fixed flush to wall and suitable for universal mounting and including aluminium alloy bus bar, Neutral bar, standard DIN rail, eath bar and cable ties for cable management, top and bottom removable gland plates with knockouts and suitable MCBs as complete all as specified and conforming to IS: 8623 alongwith cable end box for above TPN/isolator all as specified and directed. Note: (a) MCBs shall be measured and paid separately. (b) All cables terminating into MCBs shall be connected by using suitable copper lugs/thimbles/sleeves and its cost shall be deemed to be included under respective item of Sch. (c) making good and finishing of disturbed surfaces matching with the exisitng surfaces plastering, wood box work, painting if reqd any type incl ecessary fixing arrangements complete deemed to be included under respective item of sch. (d) Make of MCBs/ MCCBs and MCB DBs shall be same makes.
Supply and fixing in replacement of factory made epoxy polyester powder coated distribution board TP & N 4 way (VTPN MCCB DB) with metal double door (IP-43 protection) and double door IK-09 fabricated from recommended thick CRCA sheet and fixed on wall and suitable for universal mounting and including aluminium alloy bus bar, Neutral bar, standard DIN rail, earth bar and cable ties for cable management, top and bottom removable gland plates with provn for DPX 125 4 pole MCCB as incommer and 16 to 32 SP MCBs outgoings complete all as specified and conforming to IS: 8623 along with cable end box for above DB all as specified. Note :- (a) MCBs/MCCB shall be measured and paid separately. (b) All cables terminating into MCBs shall be connected by using suitable copper lugs/thimbles/sleeves and its cost shall be deemed to be included under respective item of Sch. (c) making good and finishing of disturbed surfaces matching with the exisitng surfaces plastering, wood box work, painting if reqd any type incl ecessary fixing arrangements complete deemed to be included under respective item of sch. (d) Make of MCBs/MCCBs and MCB DBs shall be same makes.
S&F MCB 63 to 100 Amps TPN 10 KA C curve 415 volt complete all as specified and directed.
S&F MCB SPN 40-63 Amps KA C curve 240 Volt complete all as specified and directed.
S&F MCB SPN 32 Amps 10 KA C curve 240 volt complete all as specified and directed.
S&F MCB Single pole 6 to 32 Amp, 240 volts, 'C' series, 10 KA breaking capacity & making connection complete all as specified and directed.
S&F in repair MCB Single pole 40 -63 Amp, 240 volts, 'C' series, 10 KA breaking capacity & making connection complete all as specified and directed.
Supply and fix in replacement of MCCB 125 Amp 4 pole 25 KA at 415 V fixed type complete.complete all as specified and directed.
Supply and fix in replacement of MCCB 100 Amp 4 pole 25 KA at 415 V fixed type complete.complete all as specified and directed.
Supply and fix in replacement of MCCB 160 Amp 4 pole 36 KA at 415 V fixed type with sheet metal enclosure compitable to mount it including all lugs, seprater etc complete all as specified and directed.
Supply and fixing in replacement of Non Metallic Rigid PVC casing caping 20mm size/ conduit pipe of 20mm dia size, ISI Marked, conforming to IS 9537 Part III, medium grade including all fittings like bends, elbow reducer, junction boxes, tee bell mouth all fixing accessories such as coupler lock, nuts, saddles pipe hooks etc complete in all respect as specified and directed. 20 mm dia
All as per item No. 58 above but size 25 mm casing caping/25mm dia conduit pipe.
Supply & fixing in replacement of worn out/rusted sunken box of following sizes with pressed MS/GI steel terminal boxes of depth not less than 50 mm, flush type of thickness lot less than 1.22 mm of following size along with new 3.0 mm thick plastic laminated sheet cover of suitable size including cutting/drilling hole and fixing switches, sockets, fan regulator etc as removed from old sheet and fitted with cadmium plated screw washer and making good to disturbed surface with cement mortar complete in all respect as specified and directed.
100 mm X 100 mm.
175 mm X 100 mm.
250 mm X 200 mm.
Supply & fixing in replacement Three pin metalic socket outlet suitable for sheet metal enclosure complete all as specified & directed. Make : Bentac/C&S/HPL or equialent as approved by GE.
Supply & Fixing in replacement Three pin metallic plug top suitable for sheet metal enclsoure complete all as specified & directed. Make : Bentac/C&S/HPL or equialent as approved by GE.
M&L for Dismantling of ceiling fans AC single phase 230 volts of sizes 1200mm/1400mm any make / model , dismantled its stator,rotor, cutting out burnt copper winding and providing New Winding with super enamelled copper winding wire existing size including cleaning of slots providing oil impregnated insulation paper or minimax, fibre, insulation in slots and well wraping , with cotton tape, bind with cotton thread and varnishing over all with winding varnish with bearing & paiting of complete as aproved by Engineer - in - charge and cleaning of bearing housing and shaft, replacing spares such as condenser, split pins, blade screws etc as required and deposited to MES store after testing complete all as specified and directed. Note - (i) Fans to be collected by the contractor at their own arrangement from AGE E/M store for repair/rewinding and to be deposited at same place after making serviceable duly tested.
All as per item No. 66 as above but for Exhaust Fan of Sweep Size 300/380mm , AC ,single phase 230/240 volts.
All as per item No. 66 as above but for Wall Mounted/Padestral Fan of Sweep Size 400/450mm , AC ,single phase 230/240 volts.
Supply and fixing in replacement of ventilation fans PVC body of size 300 mm sweep AC single phase 230/240 volts including taking down the old unserviceable one and depositing the same in MES yard for further disposal as per existing procedure complete all as specified & directed.
S&F in replacement of LED light fitting 1x9W/1X10Wbulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed.
Supply and fixing LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete all as specified & directed.
M&L in replacement of energy saver LED battan fitting 20 watt,120 Lumen /watt, 230 Volts, single tube mounting including with electronic driver LED Printed board, end cover, connector box etc and accessories, prewired, LED including required fixing arrangements and electrical connection two core copper cable from ceiling rose to led light fitting all as directed .
M&L in replacement of bracket for building security light made out of 40 mm bore GI pipe medium grade not less than 1.2 mtr length bent at 120 degree to shape fixed on pole/wall with and including 50x6mm FI clamps = 02 Nos with nut bolts, washers including painting of clamps with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed.
Supply and fixing in replacement of LED street light fitting 35 Watt 120 Lumen /watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed.
M&L in replacement of earthing complete with M.S. galvanized earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25 M deep below normal GL) with top edge of the earth plate not less than 1.5M below normal GL, connected to galvanized earth lead wire 4 mm dia by means of bolts, nuts, check nuts & washers of GI or steel incl excavation, PCC (1:3:6) type C-1 chamber with RCC cover (1:2:4) type B0, 40 mm thick reinforced with 8 mm dia bar, 3 Nos. both way, 15 mm dia light grade GI protection pipe, funnel with wire mesh,watering pipe of size 20 mm dia med. grade, lugs, main Earthing lead upto 7.5 mtr incl. Charcoal dust, salt etc. all as shown in electrical plate No. 3of SSR Pt-I, 2009 specification. Note:- The rates quoted shall also deemed to include the cost of Earth test point and earth wire and protection pipe upto 7.5 meter beyond the earth plates electrode.
M&L for earthing complete with galvanised steel earth plate electrode 600x600x6 mm thick buried directly in ground (earth pit not less than 2.25m deep below GL with top edge of plate not less than 1.50 m below normal ground level) connected to galavanised earth lead strip 36mm x 6 mm (7.5m) as means of bolts, nuts, check nuts and washer besides brazing at all joints as shown on drawings and including excavation, earth work, GI pipe (ISImark) light grade 40mm bore for protection of GI strip from earth electrode to and including the earth test point, supplying and laying charcoal dust, common salt, PCC 1:3:6, type C-1(using 20 mm graded crushed stone aggregate ) chamber and mild steel angle iron frame 40 x 40 x 3 mm and 40 mm thick pre-cast RCC cover 1:2:4 , type B-1(using 20 mm graded crushed stone aggregate ) reinforced with 8 mm dia TMT bars @ 75 mm C/C both ways with mild steel handle 12 mm dia, PGI funnel and wire mesh, 20 mm dia GI pipe light grade(ISI marked) for watering all as shown in electrical plate No 3 of SSR Part-I and connected to earth test point including testing & taking down of old/ ineffective earthing complete all as specified and directed. Note:- The rates quoted shall also deemed to include the cost of Earth test point and earth wire and protection pipe upto 7.5 meter beyond the earth plates electrode.
Supply and fixing of GI pipe light grade of size 40 mm bore for laying in trenches/floors or walls including all fittings for fixing complete as required and directed by Engineer-in-Charge.
Supply and fixing of GI pipe light grade of size 15 mm bore for laying in trenches/floors or walls including all fittings for fixing complete as required and directed by Engineer-in-Charge.
M&L for earth continuity conductor or main earthing lead 4 mm dia GI or steel wire fixed to wall on batten or recessed or buried in ground or drawn in conduit/pipe all as required at site.
Excavation in trenches n.exc 1.5m wide and n.exc 1.5m depth as in hard/ dence soil including forming of bottom surface to required level or slope for laying of CI/ GI pipe complete all as specified and directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers n.exc 25cm each complete all as specified and directed.
Removing of surplus excavated material (soil) to a distance n.exc 50m and deposited where directed at a level n.exc 1.5m above the starting point complete all as specified and directed.
M&L for cutting of road metal surface for passing of pipe lines and making good the road surface with 150mm thick layer of compacted stone aggregate and existing thickness bituminous macadam or PCC 1:2:4 type B-1 using 20mm graded stone aggregate complete all as specified and directed. Note: (i) Excavation and earth work shall be measured and paid separately under relevant item. (ii) Proper compaction shall be done to avoid any settlement.
Taking up unserviceable CI/DI rusted/ Asbestus Cemented / PVC broken pipe line (including all fittings) with spigot and socket/ Flanged ends and removal from site including burning out joints and recovering lead complete all as specified and directed for the following sizes/bores of pipes :-(Earth work shall be measured and paid separately).
150mm bore dia.
100mm bore dia.
Laying only in trenches CI pipe with spigot and socketed ends complete after cleaning properly/thoroughly & removal of all blockage removing all silt and deposited organics inside using bamboo or rod with brush complete all as specified and directed for the following sizes/bore of pipes :- Note:- CI fittings and jointing material shall be measured & paid seperately.
150 mm bore dia
100 mm bore dia
Supply & laying in trenches cast iron pipe with spigot and socketed ends centrifugally cast class ‘LA’ in any length laid in trenches of following size complete all as specified and directed for the following sizes/bore of pipes (CI fittings and jointing material shall be measured and paid separately) :-
150mm bore dia.
100mm bore dia.
Supply & laying in trenches ductile iron (DI) pipe with spigot and socketed ends centrifugally cast class 'K-7' in any length laid in trenches complete all as specified and directed for the following sizes/bore of pipes (DI fittings and jointing materials shall be measured and paid separately) :-
150 mm bore dia.
100 mm bore dia.
M&L for cutting of the cast iron pipe in position for insert of new tee in CI/ DI specials, branches etc. with suitable size of clamp of size 40 x 6 mm with nuts, bolts and washer of the following sizes complete all as specified and directed.
150 mm bore
100 mm bore
80 mm bore
M&L for rubber gasket joint suitable for DI pipe and fittings with size of nuts, washer & bolts etc complete all as specified and directed for the following sizes :-
150 mm bore.
100 mm bore.
M&L for clamp joint with rubber or fibre board gasket including nut and bolts for straight end joint to flanged pipes and fittings for the following sizes complete all as specified and directed.
150 mm bore.
100 mm bore.
80 mm bore dia.
Supply, fixing, jointing and testing in repair of cast iron sluice valve class I (ISI MARKED) PN-1.6 type latest IS 14846-2000 flanged ends, drilled having BRASS spindle with cast iron wheel head at top complete with nuts, bolts, washer and rubber gasket etc complete including taking down unserviceable sluice valve complete all as specified and directed for following bore of DI pipe line :-
150 mm bore.
100 mm bore.
80 mm bore.
Supply, fixing, jointing and testing of cast iron non return valve flanged ends as per IS-5312 (ISI Marked) complete with washer nuts/ bolts and rubber gasket complete including taking down unserviceable non return valve complete all as specified and directed for following bore of CI pipe line.
150mm bore dia.
100mm bore dia.
Dismantling old broken / damaged valve pit chamber and construct valve pit chamber of size 1050mm x 1050 mm x 1050 mm (internal dimention) complete including excavation and earth work, PCC 1:4:8, type D-2 using 40mm graded stone aggregate, brick work in cement mortar 1:6, plastering in cement mortar 1:4 (internally) and including 3mm thick mild steel sheet cover fixed in angle iron frame 40x40x6mm and painting with two coat of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed.
All as per item No 93 above but size of valve chamber is 900 x 900 x 900 mm (internal) and all as specified and directed.
All as per item No 93 above but size of valve chamber is 450x 450 x 450 mm (internal) and all as specified and directed.
M&L for cutting of cast iron pipes in position for insertion of new tees, branches, etc. and reducing to required length of 100mm bore of pipe complete all as specified and directed.
M&L for cutting of cast iron pipes in position for insertion of new tees, branches, etc. and reducing to required length of 150mm bore of pipe complete all as specified and directed.
M&L drilling and tapping cast iron water mains (in position) for branch connection of 20/25 mm bore CI/GI pipe including and provn of suitable size MS clamp with nuts, bolts and washers and welded with one GI socket complete all as specified and directed.
M&L for actual detecting the leakage of existing CI/DI pipe any type and repairing the joint with new lead & jute/wool refixing after testing for leakage proof pipe line and including returning filling and making good disturbed surface complete for following bore of CI pipe line :- Note :- Excavation and earth work will be measured and paid separately.
150 mm bore.
100 mm bore.
80 mm bore.
All as per item No. 99 here-in-before but using old lead.
150 mm bore.
100 mm bore.
80 mm bore.
M&L for actual detecting the leakage of existing GI pipe line any type laid in trenches/ wall/ floor including excavation upto one cum taking out existing pipeline and repair including replacement of GI fitting such as tee, socket, reducer, elbow, union, etc complete and refixing after testing for leakage proof pipe line and making good disturbed surface complete for following bore of GI pipe line :- Note :- Excavation and earth work will be measured and paid separately.
32 to 80 mm GI pipe.
15 to 25 mm GI pipe.
Taking up old rusted GI / UPVC / CPVC / PPR Pipes and connections including clearing the pipes free from scaling for reusing the same complete all as directed for the following sizes :- Note :-Excavation will be measured and paid separately
90 mm dia bore.
63 mm dia bore.
50 mm dia bore.
40mm dia bore.
32 mm dia bore.
25 mm dia bore.
20 mm dia bore.
15 mm dia bore.
Relaying/ refixing of old steel tubing and connection in new or old position including necessary cuttings, threading, and new fittings such as bends, elbows, socket nipples, tapers, and reducers etc all as specified and directed
50 mm dia bore.
40 mm dia bore.
32 mm dia bore.
25 mm dia bore.
20 mm dia bore.
15 mm dia bore.
Supply and lay steel water tubing GI medium grade ISI marked with all fittings laid in trenches or fixed to wall etc complete for the following sizes:- Note :- Excavation and earth work will be measured and paid separately.
50 mm dia bore
40 mm dia bore
32 mm dia bore
25 mm dia bore
20 mm dia bore
15 mm dia bore
Supply and laying in 3- layer PP-R Poly propylene random copolymer) concealed pipes SDR 7.4 (PN16) UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply all PP-R plain & brass threaded polypropylene random fittings laid in trenches. PPR Pipes heavy duty pipes with working pessure 6 Kg/SqCm and certified with ISI standards all fitting such as Union, reducers, elbow, tee, socket, brass insert , MTA, bend, short pieces connection, back nuts, diminishig pieces, caps, plugs , etc laid in Walls, ceiling & laid in floor, laid in trenches / upto service tank complete with solvent of the following size with all fitting complete all as specified and directed.
90 mm outer dia.
63 mm outer dia.
50 mm outer dia.
40 mm outer dia.
32 mm outer dia.
25 mm outer dia.
20 mm outer dia
S&F Gun metal gate valve ISI marked with iron wheel head screwed both ends for iron pipes and fixed for the following sizes including taking down of unserviceable gate valves complete all as specified and directed.
50 mm bore.
40 mm bore.
32 mm bore
25 mm bore
20 mm bore
15 mm bore
Supply and fix PPR Gate Valves (Brass Insert) ISI marked head screwed both ends for PPR pipes with and fixed in repairs for the following sizes:
63 mm bore.
50 mm bore.
40 mm bore.
32 mm bore.
25 mm bore.
20 mm bore.
M&L for two coat painting of Over head tank all water pipe lines going up and down including washout pipe lines of pump houses with colour code of synthetic enamel paint (Hammor tone finish) with spray machine including the aero marking of the pipeline entry and exit must match complete to entire satisfaction of Engineer-in-Charge.
Taking out burnt/ unserviceable submersible pump set suitable for MS column pipe 100 mm bore from 35 to 40m below ground level complete all as specified and directed.
Lowering of submersible pump set after necessary repair and rewinding suitable for MS column pipe 100 mm bore including replacement of rubber packing, nuts, bolts, washers and cable connection with suitable size copper conductor complete all as specified and directed.
Taking out burnt/ unserviceable submersible pump set suitable for MS column pipe 150 mm bore from 35 to 40m below ground level complete all as specified and directed.
Lowering of submersible pump set after necessary repair and rewinding suitable for MS column pipe 150 mm bore including replacement of rubber packing, nuts, bolts, washers and cable connection with suitable size copper conductor complete all as specified and directed.
Supply & Fixing in replacement of 100 mm bore MS coloumn pipe in 3 metre length having wall thickness 5.4 mm with both ends flanged and drilled 6 to 8 holes with flange packing nut bolts & washers of suitable size complete all as specified & directed.
Supply & Fixing inreplacement 150 mm bore MS coloumn pipe in 3 metre length having wall thickness 5.4 mm with both ends flanged and drilled 6 to 8 holes with flange packing nut bolts & washers of suitable size complete all as specified & directed.
Disconnecting of all electric / water supply connection from the panel/water line, taking out submersible pump set including column pipe (motor and pump) of 10 HP to 40 HP capacity of any make / model from site to workshop, dismantling the pump part by part, after stripping off the pump and motor, segregating the unserviceable and serviceable parts, cleaning, re-metalling and machine polishing, slot cutting, threading of all parts as required, re-assembling including replacement of worn out spares and painting with one coat of synthetic enamel paint, re-transporting to work-site lowering the pump set including column pipe and re-connection of electrical and mechanical joint, testing of pump set complete all as directed by the Engr-in-Charge.
M&L for rewinding of electric motor of submersible pump of capacity 7.5 HP of any make 3 phase, 415V, with PVC insulated heavy duty superior quality copper winding wires of suitable gauge/size matching to existing , straightening and replacement of U/s spares part, cleaning of stator slots properly by using adequqte size of sand paper including inslating materials complete all as directed by Engr-in-Charge. Note : Spares reqd for the same will be measured and paid separately under relevant items
All as per item No. 116 here -in - but 25 HP capacity.
All as per item No. 116 here -in - but 30 HP capacity.
All as per item No. 116 here -in - but 40/41 HP capacity.
Supply only spare parts required for repair of motor 5 HP to 10 HP against Sch 'A' item No 115 here -in- before:-
Thurst plate.
Segment bearing complete set.
Segment housing body CI.
Lower bush body.
Upper bush body .
Pump connector.
Upper bearing body.
Lower bearing body.
S/S sleeve for rotor shaft.
Oil seal.
GM bush for submersible motor pump.
Sand guard.
Supply and fix in replacement of PVC Insulated submersible flat cable 3 core with jointing material insulated water proof copper conductor multi staranded 1100 Volts grade of the following size compelete all as specified and directed.
S&F in repair MCB triple pole 32 Amps, 'C' curve incl necessary incoming & outgoing elect connections, copper lugs, etc., complete all as specified and directed.
Repair and maintenace of existing starter panel, replacement of single phase preventor matching with motor of type VSP-3 and re-assembling of the panel including rectification of fault and safety device, adjustment of time etc complete as directed by the Engr-in-Charge. Make : L&T,/Legrant/Havells.
S&F in repair push button switch for panel any type and of any colour as directed by the Engr-in-Charge.
S&F in repair indication lamp set LED type as directed by the Engr-in-Charge.
S&F in replacement of over load relay directly mounted relay range 10 to 16A complete all as specified and directed. Make : L&T/Legrant/Havells.
S&F in replacement of over load relay directly mounted relay range 20 to 32 A complete all as specified and directed. Make : L&T/Legrant/Havells.
S&F in repairs single phase preventor relay with timer- SDz5, SPPR + Timer, 415V complete all as specified and directed. Make:L&T,/Legrant/Havells) incl necessary elect connections.
S&F in repair timer 440 Volt Gt 200 AC thermal type with coil as directed by the Engr-in-Charge. Make : L&T/Legrant/Havells) or equivalent of make BCH / Siemens.
Repair and maintenance of existing starter panel, replacement of defective power contactor 3 pole, 415 Volt AC 3 phase type ML-3 and re-assembling of the panel including rectification of fault and safety device, adjustment of time etc complete as directed by the Engr-in-Charge. (Make : L&T,/Legrant/Havells) or equivalent model of Siemens / BCH.
S&F in repairs fully automatic star delta starter in Sheet-Steel Enclosure Type ML 4 FASD (Motor Rating -70 Amp, AC-3 Duty, 415V, 50Hz, 3Ph) incl necessary incoming & outgoing elect connections, copper lugs, etc., as directed. Make : L&T,/Legrant/Havells or equivalent..
Disconnection and lifting up of submersible pump set (motor, pump and column pipe) and development of tube well by using chemical with suitable capacity air compressor and vertical turbine equipments (till sand free portable water is available to the satisfaction of Engr-in-Charge) including to & fro hire charge of special T&P including lowering of pump and motor complete and testing on load of pump set (motor and pump) as directed by the Engr-in-Charge.
S&F of stator set of submersible motor for 30 HP duly winded with PVC insulated wire and including taking out existing unserviceale stator set complete all as specified and directed. Make . KSB /SU /Kalama
S&F of rotor set of submersible motor for 30 HP duly winded with PVC insulated wire and including taking out existing unserviceale stator set complete all as specified and directed. Make . KSB /SU /Kalama
M&L for cleaning and disinfecting of over head tanks of capacity 50,000 Gallons capacity located at PCDA (P) complete all as specified and directed comprising with the following operations:-
(i) In the first step, dewatering of OH tank shall be carried out with portable submersible pump with flow rate not less than 30000 litres/hr.
(ii) In the second step, removal of left over dirty water and sludge shall be carried out with suitable sludge removal pump.
(iii) In the third step, cleaning of internal walls, floors, ceiling of OH tank by high pressure water jet is to be done. High pressure machine should develop pressure 80-120 bar. It should be ensured that no dirt, algae or mass shall remain on surface of tank.
(iv) In the fourth step, removal of remaining sludge shall be carried out with industrial vacuum cleaner.
(v) In the fifth step, OH tank shall be sterilized by spraying anti bacterial agent (Tanclean or equivalent as approved) using high pressure machine. Dose of this agent must be as per OCED guidelines 423 adopted on 17 Dec 2001 (i.e. 1 litre of concentrated agent mixed with 40 litres of water to produce mixture. 1 litre of this mixture is to be used to disinfect 10000 litres capacity tank and higher capacity tanks in proportion).
(vi) In the last step, treatment of inside tank by exploring UV radiation to kill further suspended or floating bacteria. This is to be done by glowing UV lamp inside tank as per NSF standard 55-1991 (i.e. 16000 µW-sec/cm² or in other words 3-5 minutes according to capacity of tank).
Notes: (a) The work should be got executed through reputed specialised water tank cleaning agency and shall be approved in writing by GE before commencement of this work. (b) After completion of work a certificate regarding bacteria free should be submitted to Deptt. (c) Coloured photographic evidence of stage wise cleaning of OHT shall be submitted in duplicate to the Deptt. (d) Date of Cleaning, date of expiry and capacity of tank will be written on OHT with Paint with 5cm high letters or figures (Block, Roman) complete. (e) The cost of above requirement is deemed to be inclusive in contractor's quoted rates and no any extra payment shall be admisible on this account.
Taking out centrifugal pump incl. electric motor 5 HP ,3 phase ,415 Volts after ,disconnecting the electric connection dismantling the motor cutting the burnt winding and cleaning the slots with non greasy materials and rewinding with super enameled copper wire (Gauge of copper is to match the existing size) with insulating material, varnishing complete. Reassembling the motor, repair and overhauling of pumps, replacement of bearing,grinding , polishing of impeller, neckring ,greasing complete all as directed , and making electric connection and testing complete to entire satisfaction of Engr-in-charge.
Pump motor coupling suitable for pump 5 HP as per sample complete all as specified and directed.
Key to coupling stainless steel suitable for pump 5 HP as per sample complete all as specified and directed.
Bearing to pump shaft suitable for pump 5 HP as per sample complete all as specified and directed.
Refilling of gland suitable for pump 5 HP as per sample complete all as specified and directed.
S&F submersible pump of capacity 40/41 HP with electric driven motors of suitable capacity as per design 3 Phasae 415 Volt with head 70.00 M to 110 Mtr and dicharge 1400 LPM to 2800 LPM complete including taking down unserviceable submersible pump complete all as specified and directed and making electrical connection and testing complete to eniter satisfaction of Enginer in charge. Make :- KSB/Kirloskar
Supply and testing Clorine testing kit with Reagent Bottle,Colour Comparator, Test Jar complete all as specified and directed. Make: Tolexo/REMCO/Koundal
M&L for testing of water samples including collection of samples in bottles/containers and depositing to testing agency i.e. CGWB, UP Pollution Control Board or any approved Govt. lab in same day and submitting results complete all as specified for following parameters:- (a) Turbidity, (b) Ph value, (c) Total hardness, (d) Iron, (e) Chloride, (f) Residual Free Chloride, (g) Fluoride, (h) Dissolved Solids, (j) Calcium, (k) Mercury, (l) Arsenic, (m) Lead, (n) Pesticides, (o) Alkalinity, (p) Nitrate, (q) Total collifarm, (r) e- Collifarm.
M&L for decanning of Water Sump of Fountain including cleaning, desludging, scrapping, painting with two coats of synthetic enamel paint in required shade including repair of leakage of sump with required existing PCC 1:2:4 type B-1 and cement plaster in CM 1:4 complete all as specified and directed.
S&F in replacement Chromium plated Brass nozzles of size 1" dia of water fountain complete all as specified and directed.
S&F in replacement Chromium plated Brass nozzles of size 1/2" dia DN15 High Quality Brass Column Fireworks Fountain Nozzles Sprinkler Spray Head NB0374 having 17 holes of water fountain complete all as specified and directed.
S&F in replacement under Water LED fountain light with water tight enclosure of approved shade of water fountain complete all as specified and directed. Make: Electrolite cat no. SLUW302 or equivalent as approved in Philips/ BAJAJ/ L&T/ Crompton.
S&F in replacement under Water Submersible Light LED fountain light fittings Lamp 3x20W withTransformer 12v/50Hz 60VA with water tight enclosure including LED lamp of approved shade of water fountain complete all as specified and directed. Make: Philips/ BAJAJ/ L&T/ Crompton.
S&F in replacement horizental type Submersible pump, 1 HP capacity, single phase 415 Volts from water fountain including connection, along with suitable size of starter complete all as specified and directed. Make: KSB/ L&T/ Crompton.
S&F in replacement pressure pump, 3/4 HP capacity, single phase 230Volts with pressure tank & auto cut off mechanisum at 2 Kg/cmsq pressure complete all as specified and directed. Make: KSB/ L&T/ Crompton.
S&F bib tap PVC 15mm dia including taking out unserviceable bib tap of any description complete all as specified and directed.
S&F in replacement Integral LED avaition light comprising of aluminium housing with polycarbonate enclosure including provn of three core cable of copper conductor of size 2.5 sqmm 3 core of white covering for making connection, fixing the fitting on OHT including GI pipe heavy duty 20 mm all necessary fixing with sheddel/clamps piece accessories complete all as directed. Make: Bajaj cat No BGAV 302 LED/ Mapro/ Havells.
Supply & Fixing of 6 core X 1.5 sq.mm dia. PVC insulated copper stranded armoured cable complete all as specified and directed.
Supply & Fixing of 5 Pair X 0.5 sq.mm dia. PVC insulated copper stranded armoured cable complete all as specified and directed.
Supply only Calcium based white/off white free flowing granular disinfectant chlorination chemical decomposing at 177 Degree centrigrade, molecular weight 142.98, toxicity-oral rate LD 50 : 850 mg/kg in 45 kgs 65% chlorine content container packing including loading & unloading at site complete all as directed. Make : E-in-Cs approved make or make a approved by GE
Supply & fixing in repair commissioning & testing complete of DIGITAL WATER LEVEL INDICATION DEVICE, operating on single phase supply direct display in 19 mm size digital system in meter or cm of water over head tank ensuring alarm while water fall or rise over pre-determined limit with the following description : the entire unit must operate through a compact electronic circuit, which must ensure reliable operation at 230 Volt + 5% with reliable in digit display and alarm at low and high level or over head tank complete as directed by Engineer-in-Charge. Make : SECO type DDS-2 / Surya / Akash / Phototron.
M&L periodical servicing of diesel engine driven Gen set 3 phase 415 volts 50 c/s AC supply by cleaning thoroughly and replacing fuel filters ,air filters, oil filters draining out engine oil etc. and replacing with new oil, tightening of all gaskets , connection of battery terminals, electric cable connections foundation bolts, coupling bolts etc including test running and tappet setting of alternator by checking and setting of voltage and frequency all as directed by Engr-in-charge. Make OF DG SET : Kirloskar/ Crompton greaves/Cummins. Make of filters : kirloskar/CG/Fleet guard/MICO Note-:Engine oil, Fuel filters, Air filters, oil filters and other worn out spare part replaced will be measured and paid separately under respective item of sch 'A' . for following capacities of DG set
320 to 400 KVA DG Set.
160 to 250 KVA DG Set.
62.5/63 KVA DG Set..
25 to 40 KVA DG Set.
Supply and fixing in replacement of maintenance free battery with initially charged capacity 180 AH , 12 Volt complete all as specified and as directed. Make :- Exide/Amron
Supply and fixing in replacement of maintenance free battery with initially charged capacity 150 AH , 12 Volt complete all as specified and as directed. Make :- Exide/Amron
Supply and fixing in replacement of maintenance free battery with initially charged capacity 90 AH , 12 Volt complete all as specified and as directed. Make:- Exide/Amron
Supply, fixing & testing in replacement of Radiator of 320 to 500 KVA DG Set water cooled of kirlokar make with copper tubings including replacement of connected items such as inlet & outlet rubber hoses & all other connected items complete all as specified and directed.
All as per item No. 161 above but Cap 100 to 250 KVA.
All as per item No. 161 above but Cap 40 to 62.5/63 KVA.
M&L for replacement of UNSV radiator hose pipe set complete as per sample of D G set of following capacity:-
200 to 320 KVA DG Set.
100 to 160 KVA DG Set .
63/62.5 KVA DG Set .
40/50 KVA DG Set.
M&L for replacement of UNSV fan belts as per sample for DG sets of following capacity:-
200 to 320 KVA DG Set.
100 to 160 KVA DG Set .
63/62.5 KVA DG Set .
40/50 KVA DG Set .
M&L in replacement of stranded copper conductor battery lead for 24 volts D C grade red for (+)ve terminal and black for (-)ve terminal fitted with battery terminal at one end & battery lug at other end complete length 1.5 mtr complete all as specified and directed.
M&L for cleaning of radiator by cleaning agent/Radiwash (make:fleetguard/coolguard) including removal/ dismantling of radiator from engine transporting to work shop or cleaned at site , soldering / brazing,testing for any leakage , remounting to its original position as per entire satisfaction of Engr - in-charge for following capacity of DG Set:
320 to 400 KVA DG Set.
200 to 250 KVA DG Set.
82.5 to 160 KVA DG Set.
62.5/63 KVA DG Set..
25 to 40 KVA DG Set.
M&L for replacement of set of hose clips for DG sets of following capacity:-
320 to 400 KVA DG Set.
200 to 250 KVA DG Set.
82.5 to 160 KVA DG Set.
62.5/63 KVA DG Set..
M&L to drain out the old used engine oil from sump of DG Sets & cleaning & refilling with new engine oil 15 W 40 up to required level including topup complete all as specified and directed. Make : Castrol/ HP or equivalent of Servo.
M&L for coolant radicool SFO premix of castrol or equivalent of shell/Volvoline, complete all as specified and directed.
M&L for replacement of defective self starter assembly by new self starter assembly 12/24 volts complete all as specified and directed. Make:- Lucas Cat Part No. 03.034.101 / Bosch.
All as per item No. 171 above but alternator assembly. Make: Lucas Cat partv No. 03.130.01/ Boss/PMG.
Supply & fixing of micro processer start/stop control PCB panel for following cap of DG set by taking out unserviceable relay complete with following parameters. Make: Kirlosker/ Greaves /Cummins (a) Individual phase current (Amps) (b) Phase voltages (V) (c ) Generator output frequency (Hz) (d) Engine water temperature (Deg.C) (e) Lube oil pressure (kpa) (f) Working hours (g) Push button (Starter) & (stop) (h) LED indications for main function
250 to 320 KVA DG Set.
100 to 160 KVA DG Set.
62.5 to 82.5 KVA DG Set.
15 to 40 KVA DG Set.
M&L in for replacement of PCB card for DG set AMF pannelfor following capacity:-
250 to 320 KVA DG Set.
100 to 160 KVA DG Set.
62.5 to 82.5 KVA DG Set.
Supply and fixing in replacement of MCCB 100 Amps, 415 Volts, 3 Pole, breaking capacity 16 KA, ISI Marked, Fix type, complete all as specified and directed.
Supply and fixing in replacement of MCCB 200 Amps, 415 Volts, 4 Pole, breaking capacity 36KA, ISI Marked, Fix/ Adjustable type complete all as specified and directed.
Supply and fixing in replacement of MCCB 250 Amps, 415 Volts, 4 Pole, breaking capacity 36KA, ISI Marked, Fix/ Adjustable type complete all as specified and directed.
Supply and fixing in replacement of MCCB 350 to 400 Amps, 415 Volts, 4 Pole, breaking capacity 36KA, ISI Marked, Fix/ Adjustable type complete all as specified and directed.
M&L in for replacement of timer switch 0 to 80 seconds Make Siemens for 200/500 KVA AMF pannel complete all as specified and directed.
M&L for servicing of DG set 320/500 KVA AMF panel,setting of time delay switch ,tightening of all electrical incoming & outgoing connections including replacement of cable lugs& adjustment of solenoid switches& Relays
M&L for painting of Generating set of capacity 250 KVA to 320 KVA complete in existing colour with two coat of synthetic enamelled paint by spray machine over one coat of primer after preparation of surfaces installed at Hisar Mil Stn complete all as specified and as directed.
M&L for painting of Generating set of capacity 40 KVA to 160 KVA complete in existing colour with two coat of synthetic enamelled paint with spray machine over one coat of primer after preparation of surfaces installed at western & eastern pocket drainage pump House complete all as specified and as directed.
Supply and replacing in repair Euroload four pole change over with advance Neutral On load change over switch I-O-II ,Current Rating 400/630 Amps, 415 Volts complete all as specified and directed.
Supply only Diesel Filter suitable for 40 KVA to 160 KVA DG set complete all as specified and directed. Make:- Kirloskar/CG/KG/Cummins..
Supply only Diesel Filter suitable for 200 KVA to 320 KVA DG set complete all as specified and directed. Make - Kirloskar/CG/KG/Cummins
Supply only Lub Oil filter suitable for 40 KVA to 160 KVA DG set complete all as specified and directed. Make - Kirloskar/CG/KG/Cummins
Supply only Lub Oil Filter suitable for 200 KVA to 320 KVA DG set complete all as specified and directed. Make - Kirloskar/CG/KG/Cummins
Supply only Air filter suitable for 40 KVA to 160 KVA DG set complete all as specified and directed. Make - Kirloskar/CG/KG/Cummins
Supply only Air Filter suitable for 200 KVA to 320 KVA DG set complete all as specified and directed. Make - Kirloskar/CG/KG/Cummins
Supply only spare parts & accessories of original make for repair of DG set 160 to 250 KVA under serial Item No. 157 all as directed by Engr-in-Charge :- Note:- All spares & accessories shall be fixed in the DG set only after prior inspection & Approval of Engineer-in-Charge for which these shall be produced by the contractor at store yard of AGE E/M New Cantt
Kit bypass filter
Upper Gasket set (Cylinder head)
Valve exhaust
Valve inlet
Valve seat Exhaust
Valve seat Inlet
Guide valve
Collet Valve
Spring valve
Kit turbo charging
Kit injector
Kit Piston and ring set
Kit Cylinder liner
Kit Sump Gasket
Gear pump assembly (Fuel pump FIP)
Gasket Set
Gear assembly
Ball bering/roller bearing
Head gasket
Nozzle
Liner
Battery terminal
Packing Kit
Crank
Main bearing
CR bearing
Came bush
Connecting Rod
Rod balancing
Third washer
Valve seal
Supply only spare parts & accessories of original make for repair of DG set 40 to 82.5 KVA under serial items No. 157 here-in-before all as directed by Engr-in-Charge :- Note :- All spares & accessories shall be fixed in the DG set only after prior inspection & Approval of Engineer-in-Charge for which these shall be produced by the contractor at store yard of AGE E/M New Cantt .
Kit Fuel filter
Kit Lub oil filter
Kit bypass filter
Kit Air cleaner
Air filter
Upper Gasket set (Cylinder head)
Valve exhaust
Valve inlet
Valve seat Exhaust
Valve seat Inlet
Guide valve
Collet valve
Spring valve
Kit turbo charging
Kit injector repair
Kit Piston and ring set
Kit Cylinder liner
Kit Sump Gasket
Gear pump assembly (Fuel pump FIP)
Gasket Set
Gear assembly
Ball bering
Head gasket
Nozzle
Liner
Battery terminal
Packing Kit
Crank
Main bearing
CR bearing
Came bush
Connecting Rod
Rod balancing
Third washer
Valve seal
Dismantling of DG Set Alternator of cap 100 to 250 KVA carefully and carry to authorised workshop for repair and re-fixing the same in its original position after repair and testing the same up to satisfaction of AGE E/M complete all as direted.
Cutting out old burnt winding of alternator, cleaning the slot of stator and rewinding the same with super enamelled copper winding wire of appropriate gauge complete with all insulating materials, Nomex paper, cotton tape, glass sleeve, soldering rod, Grease etc complete for 100/200/250 KVA size complete all as specified and directed.
Repairing of armature shaft both side by depositing metal on it, grinding & polishing to make appropriate size of the shaft complete for 100/200/250 KVA size complete all as specified and directed.
Supply and replacing Ball bearing at DE (Driven End) side of No.6310 /6311/6312/6314 Make-NBC/SKF-01 No for 100/200/250 KVA size complete all as specified and directed.
Supply and replacing rectifier Diod for 100/200/250 KVA size complete all as specified and directed.
Supply and replacing AVR (Automatic Voltage Regulaotr) for 100/200/250 KVA size complete all as specified and directed.
Dismantling of DG Set Alternator of cap 100 to 250 KVA carefully and carry to authorised workshop for repair and re-fixing the same in its original position after repair and testing the same up to satisfaction of AGE E/M complete all as direted.-01 No.
Cutting out old burnt winding of alternator, cleaning the slot of stator and rewinding the same with super enamelled copper winding wire of appropriate gauge complete with all insulating materials, Nomex paper, cotton tape, glass sleeve, soldering rod, Grease etc for 250 to 380 KVA DG Set complete all as specified and directed.
Repairing of armature shaft both side by depositing metal on it, grinding & polishing to make appropriate size of the shaft complete for 250 to 380 KVA DG Set complete all as specified and directed.
Supply and replacing Ball bearing at DE (Driven End) side of No.6310 /6311/6312/6314 Make-NBC/SKF-01 No for 250 to 380 KVA DG Set complete all as specified and directed.
Supply and replacing rectifier Diod for 250 to 380 KVA DG Set complete all as specified and directed.
Supply and replacing connetion plate of suitable size for 250 to 380 KVA DG Set complete all as specified and directed.
Supply and replacing AVR (Automatic Voltage Regulaotr) for 250 to 380 KVA DG Set complete all as specified and directed.
M&L for repair/overhauling of existing starter panel board of any size/type including cleaning with compressed air tightening of all electric connections to switces including repair/replacment of existing MCB/ switch fuse disconnector units each of any rating including testing complete with fixing of door (front & backside) with proper fixing & locking arrangement replacement of wornout lugs, nut, bolts, internal wiring with suitable size (minimum 1.5 sqmm) of PVC copper conductor wire and lugs, proper connention to main earth lead, to be provided/replaced as required at cable entries, fixing of door front & back with copper locking arrangement as requred as site and painting with spary machine with super eanameled paint light grey paint in outer/ inner side of pannel after cleaning and prepaing surface including sign writing complete all as spcified and directed Note : Spares part to be repalaced shall be measured and paid sparately as supply only
Contractor TF 34 make siemens or equivalent approved
Supply only Conactor TF 30 Make Siemens or equivalents approved
Supply only Conactor TF 31 Make Siemens or equivalents approved
Supply only PVC Connector
Supply only Over Load Relay capacity 20-30 amp Make Siemens or equivalents approved
Supply only Over Load Relay capacity 10-20 Make Siemens or equivalents approved
S&F in replacement of Exhaust silencer complete with muffler of 160 KVA/62.5 KVA DG set complete connects engine and DG silencer to drive away hot gases generated during operation of DG to atmosphere through silencer complete all as specified and directed.
Dismantling and taking out the self starter,12 Volt DC fitted in 40/62.5/82.5 KVA 3 phase 50 HZ of DG sets and strip opening of Self starter 12 Volt DC for carrying out repair/ servicing /overhauling mechanically ,cleaning, oiling/greasing/varnishing, fixing of serviceable parts in position, removing & replacement of defective / unserviceable parts with new parts, complete and re-assembling of Self starter 12 Volt DC after repair/ servicing /overhauling and fixing the same in position and testing complete all as specified and directed Note :- (i) Repairs/servicing / reassembling and testing of Self starter 12 Volt DC shall be carried out through a authorised service center .(ii) The quoted rates of the contractor includes for fixing the serviceable parts in position and replacement of unserviceable parts with new parts. The new replaced parts shall be measured and paid for separately under appropriate item of Sch `A’ as `supply only ‘ but quoted rates are inclusive of replacement of small/minor parts such as nuts, bolts, washers, shim, small springs, screws/gaskets/ packing /studs etc. (iii) The quoted rates of contractor are deemed to be included cost of transportation to and fro authorized service centre.
Supply only the following items/spare parts suitable for self starter, 12 Volt DC fitted in 40/62.5/82.5 KVA 3 phase 50 HZ of DG set , dismantled/fixed under Sch `A` item No. 208 here in above complete all as specified and directed. Note :- (i) Fixing element of these items is included under the rates quoted by the contractor for Schedule `A' item No 208 here in above. (ii) Contractor shall have no claim on account of variation of quantities of any item or non execution of any item.
Solenoid switch suitable for self starter, 12 Volt DC
Commutator suitable for self starter, 12 Volt DC
Carbon brush suitable for self starter, 12 Volt DC
Field coils suitable for self starter, 12 Volt DC
Bendix pinion assembly suitable for self starter, 12 Volt DC
Bush suitable for self starter, 12 Volt DC
M&L for replacement of unserveceable interconnection wiring and its interlocking system in AMF electric control panel for DG set with using and including PVC insulated and unsheathed stranded copper conductor cable, single core, minimum 1.5 Sqmm size or as required 1100 Volts grade cable for making functional controls of the DG set, auxiliary contactor, push buttons, indicator, amps meter, volt meter complete as required at site for functioning of DG set in auto and manual mode, checking AC/DC circuits and removing & replacement of defective / unserviceable parts with new parts, complete all as specified and directed . Notes: (i) The complete panel shall be checked and tested on full load after necessary repairs and replacement of unserviceable wiring. for its smooth functioning and proper interlocking including shutt down on high water tempreture and low Oil pressure. (ii) All control wires shall be properly bunched, tied, ferruled for proper identification and crimped with adequate size of copper lugs. the cost of same are deemed to include under these items. (iii) The quoted rates of the contractor includes for fixing the serviceable parts in position and replacement of unserviceable parts with new parts. The new replaced parts shall be measured and paid for separately under appropriate item of Sch `A’ as `supply only ‘ but quoted rates are inclusive of replacement of small/minor parts such as nuts, bolts, washers, shim, small springs, screws/gaskets/ packing /studs etc.
Supply only the following items/spare parts suitable for AMF pannel of DG set , dismantled/fixed under Sch `A` item No. 210 here in above complete all as specified and directed. Note :- (i) Fixing element of these items is included under the rates quoted by the contractor for Schedule `A' item No. 210 here in above. (ii) Contractor shall have no claim on account of variation of quantities of any item or non execution of any item.
Electronic timer,on delay type, dual range, suitable of 220 Volts/ 24 Volts, 2NO+2NC, 50 Hz, AC supply/ DC supply , for 0-60 seconds.
Power contactor 3 pole with 2NO + 2NC auxiliary contacts, coil voltage 220 volts, AC 3 rating 400 Amps.
Auxilliary relay 8 pin, 220 Volts , AC , 2 change over.
Bimetal under volt / over volt relay suitable for 3 phase, 3 wire with 2 NO+2NC auxiliary contacts
Engine starting relay with sequence timer & Master timer suitable for 12 / 24 Volts DC supply.
Indicating lamps LED type with holder for 12 / 24 volts DC supply.
Digital electronic volt meter 0-500 V range suitable for 415 Volts panel flush pattern square type size 96mmX96mm.
HRC fuse DIN type with base for AC circuit 415 volts having rating of 400 Amps.
No volt coil 100 to 400 Amp complete for suitabel capacity of DG sets panels.
M&L for Cleaning of MS fuel tank of DG sets of 100 to 320 ltr capacity by collecting the fuel in cleaned barrels and removing sludge deposited/accumulated inside the tank of and disposal of sludge at a distance not exceeding 100 metre and cleaning the tank with kerosene oil , replacement of fuel tank strainer and unserviceable fuel gauge with new PVC fuel level indicator fixed with clips to the tank and marking levels for every 10 litre by marking and numbering on the side of fuel tank with synthetic enameled paint and refilling the collected fuel after filtration complete all as specified and directed.
M&L Testing of fire hydrant system of building at each floor by cheking serviceability of water pressure, hydrant valve, pumps, wheel, spindle assembly, Coupling , Assembly with Lug, canvas hose, MS pipe, brass nozzle, pressure gauge etc. comlete all as specified and directed. Note : The contractar shall maintain a register of seriviceability state of each fire hydrant system of each building including taking signature of JE / Engineer-in-charge and user.
M&L for Cleaning, dusting and servicing LT panel , MCCBs, Automatic S/D Starter, Bus bars tightening cable connections, providing lugs , cable glands and replacing of worn out parts such as busbar spout , spacers, hinges, locks, and connected items/Mechanical parts etc for its smooth functioning including Internal spray Paiting of the panel ,Insulation of busbar , replacement of control wiring, cleaning the disturbed area beneath the LT panel and removing vegitation , derbis etc all as specified and directed by the Engineer in charge. Note:- Rate quoted deemed to include for removing and replacing of defective items where required, complete all as specified and directed.
M&L for Servicing of existing 6/8/10/12 zone fire alarm panel ,re-wiring defective connection, changing defective minor spare parts such as relays, connectors, electronic components etc and testing the panel on every zone complete all as specified and directed.
General Servicing to Diesel Engine Generating Set for Fire Hydrant Systems any type and make including checking all rubber/hose pipes, checking of coupling joints, v belts speed governer, air filter, filter elements valve tappet adjustments, radiator lines, leakage of coolent, oil including oiling/greasing & repalcement of consumable parts such as minor items like nut/bolt, washers, gasket, welding works etc (included in unit rate) and replacement of worn out/unserviceable parts (to be measured seperately as supply only) suitable for 33 KVA capacity Engines Make : Kirloskar. Note : Cost facotor of labours for servicing & fixing of parts shall be deemed to be included in unit rate. However worn out & unserviceable parts to be replaced will be measured and paid saparately as supply only. Make of spare parts same as of DG Set or as per sample .
Supply only Fuel filter per sample.
Supply only Lub Oil Filter as per sample
Supply only set of hose pipe plain as per sample
Supply only air filter outer element
Supply only air filter inner element
Supply only Fan belt V ribbed as per sample
Taking down Radiator assembly from the Diesel Engine set cleaning with soap water and acid, cleaning the fins with Kerosene Oil and water complete and refixing including soldering if any leakage detected for the 33 KVA DG Set complete all as specified and directed. Make: Kirlosker and all as directed.
S&F in replacement of Adjustable Over load Bi-metalic thermal relay of size 40 to 63 A , three phase 415V , fixed on existing fire pump starter panel and testing complete all as specified and directed . Make: L&T / ABB / Havells or equivalent.
S&F in replacement of single phase preventer suitable for 10/12.5 HP pump sets, connecting on existing starter panel complete all as specified and directed. Make: L&T / ABB / Havells or equivalent.
S&F in replacement of power contactor ,continous current rating 63A ,3 phase, 440V on existing fire pump control panel comlete all as specified and directed. Make: L&T / ABB / Havells or equivalent.
S&F in replacement of push switch with NO/NC auxilary contacts, rated 230V 6A complete all as specified and directed. Make: L&T / ABB / Havells or equivalent.
S&F in replacement of LED indicator rated 230V , fixed in existing starter panel complet all as specified and directecd. Make: L&T / ABB / Havells or equivalent.
M&L Rewinding of Induction motor up to 40 HP capacity Three Phase with enameled copper winding wire of suitable gauge, providing insulating materials such as fibre glass, tape,varnishing ,heating up the assembling, including replacement of bearings/bushes by using hydraulic press, commissioning complete testing to full load all as specified and directed including dismantling & taking to work shop and bring back and fixing complete all as specified directed.
M&L Rewinding of Inductio motor up to 10 HP capacity Three Phase with enameled copper winding wire of suitable gauge, providing insulating materials such as fibre glass, tape,varnishing ,heating up the assembling, including replacement of bearings/bushes by using hydraulic press, commissioning complete testing to full load all as specified and directed including dismantling & taking to work shop and bring back and fixing complete all as specified directed.
S&F in replacement power supply transformer of rating 24V, 5 Amps,120 VA for fire alarm panel ,including fixing and connecting on existing control panel and testing complete all as specified and directed.
S&F in replacement power supply SMPS of rating 24V, 5 Amps for fire alarm panel ,including fixing and connecting on existing control panel and testing complete all as specified and directed.
S&F in replacement of rubber gasket for pipe flange/pump connections with exsiting suitable side complete all as specified and directed. Make: Inseal / sealmax or equivalent.
S&F in replacement of 63 mm dia, 15 mtr long rubberized fabric reinforced rubber lined canvas hose conforming to 15636-1988 including gun metal male & female instantaneous coupling hose and coupling conforming to IS 903-1975 all as specified and directed. Make : Cease fire / winco / valson / swati / ABC fire or equivalent.
S&F in replacement of 20 mm dia, 30 mtr long rubber hose reel conforming to IS 444-1987 with gun metal nozzle complete all as specified and directed . Make : Cease fire / winco / valson / swati / ABC fire or equivalent.
Supply and fixing inreplacement of Hose cabinet of size 750mm x 600mm x 500mm made of 2mm thick MS sheet with 4mm thick glazed glass doors i/c necessary locking arrangement suitable to accommodate 15 mtr . Long hose pipe , 1 No. branch pipe mounted on wall OR raised brick platform & duly painted with Scarlet red colour as per specification
S&F in replacement of Gun Metal single way fire hydrant landing valve of size 63mm dia ISI marked with instantaneous coupling complete all as specified and directed by Engineer-in-Charge. Make : Cease fire / winco / valson / swati / ABC fire or equivalent.
S&F in replacement of Gun Metal double way fire hydrant landing valve of size 63mm dia ISI marked with instantaneous coupling complete all as specified and directed by Engineer-in-Charge. Make : Cease fire / winco / valson / swati / ABC fire or equivalent.
S&F in replacement of Gun Metal Bonate of size 63mm dia with spindle assembly ,Gland nut ,Operating CI Wheel for hydrant valve complete all as specified and directed by Engineer-in-Charge. Make : Cease fire / winco / valson / swati / ABC fire or equivalent.
S&F in replacement of Gun Metal Coupling Assembly of size 63mm dia with Lug (Locking Pin) for hydrant valve all as specified and directed by Engineer-in-Charge Make : Cease fire / winco / valson / swati / ABC fire or equivalent.
S&F in replacement of Hydrant valve wheel of size 63mm dia all as specified and directed. Make : Cease fire / winco / valson / swati / ABC fire or equivalent.
S&F of replacement of manual call point with glass cover and connected items complete all as specified and directed. Make: Fire tech / Chery tech or equivalent .
S&F in replacement of Fire Alarm sounders / electronic hooter / sirens electronic type horizantal single stage continous normal operation for atleast 50 minutes with sound level 65 dB to 120 dB measured at 1.5 Mtr with sound output variation of + 5 dB, 500 mtrs range with connected items complete all as specified and directed. Make: Fire tech / Chery tech or equivalent.
S&F in replacement of pressure gauge of size 4" dia, 0-21 Kg/cm2 rating complete all as specified and directed. Make : Wika / cole-parmer / Ashcroft / weksler or equivalent.
S&F in replacement of sealed maintenace free lead acid battery of capacity 12V, 7/7.5AH battery, including connecting the wire with proper lugs,nuts bolts etc and testing the changing system to ensure the battery get charge complete as all as specified and directed. Make: Exide / Amaron / Sonic.
S&F hose reel drum suitable for 63 mm.dia and 15mtr length conforming to IS 884-1985 all as specified and directed. Make : Cease fire / winco / valson / swati / ABC fire or equivalent.
S& F hose reel drum suitable for 20 mm.dia and 30 mtr length conforming to IS 884-1985 all as specified and directed. Make : Cease fire / winco / valson / swati / ABC fire or equivalent.
S&F in replacement of brass nozzle 20mm dia and complete all connectesd items all as specified and directed. Make : Cease fire / winco / valson / swati / ABC fire or equivalent.
S&F in replacement of brass nozzle 63 mm dia and complete all connectesd items all as specified and directed.Make : Cease fire / winco / valson / swati / ABC fire or equivalent.
S&F in replacement of GM gate valve of size 65mm dia after dismantling the existing union, nipple and cutting out rusted threaded portion and making new thread for inserting new GM gate valve (heavy duty) of ISI marked complete all as specified and directed. Make : Neta / Kiran / Leader / kirloskar or equivalent makes.
S&F in replacement of GM gate valve of size 80mm dia after dismantling the existing union, nipple and cutting out rusted threaded portion and making new thread for inserting new GM gate valve (heavy duty) of ISI marked complete all as specified and directed. Make : Neta / Kiran / Leader / kirloskar or equivalent makes.
S&F in replacement of foot valve CI with ISI marked heavy duty conforming to IS 4038 of rubber ball lock type including all accessories regular little rubber gasket, nut & bolts, washers etc complete of size 150mm dia complete all as specified and directed at site. Make : Neta / Kiran / Leader / kirloskar or equivalent makes.
S&F in replacement of butterfly Valve 100 mm dia cast copper alloy screwed down high pressure with iron wheel screwed both sides for iron pipe confirming to IS 13095 and complete all as specified. Make : Neta / Kiran / Leader / kirloskar
S&F in replacement of MS pipe carefully and supply, laying and connecting heavy grade ERW steel pipe of 100 mm NB, 6 mm thick as per IS 3589 (1981) including cutting / welding / grinding etc. and painting with two coats of synthetic enamel paint (post box red colour) over a coat of red oxide complete all as specified. Make : Jindal / Tata or equivalent.
M&L Painting of entire fire Hydrant system of each building with two coat of synthetic enamal post box red colour paint chromate after scrubing,removing of old painted surface and preparing the surface.It also includes painting of electric panel and all marking with white colors,(valve pipeline,hydrants,tank,lid etc.) all as directed by Engineer-in- charge.
M&L De-watering, removing all mosses, algae and dirt from internal walls, floors & mouths of pipes of RCC overhead tanks (Fire tanks) by using steel wire brush and cleaning with high pressure industrial vacuum cleaner including removing of dirty water completely using sludge pump set and disposing off the same to a safe distance and applying of anti bacterial sterilization spray to internal surfaces using Zero bacterial compound (Sodium hypochlorte) or equivalent approved chemical complete and writing the date of cleaning on outside of tank using synthetic enamel paint of white colour over black background with letters of size 50mm height x 50mm breadth, complete all as specified and directed for OH Fire tank upto 20000 litres capacity.
S&F in replacement of fire hook confirming to IS 927- 1981,hook head is made up of forged carbon steel duly painted with anti-corrosive paint, handle shall made of bamboo of length not less then 3 mtr, hook should marked with ISI marked all as specified.
S&F in replacement of fire beater to confirming to IS 8096-1992 ,beater blade is made out of steel wire mesh of size 452 x 352 mm. with fire resistant frame and handle is made out of solid bamboo of length 1.8 mtr, dia 30+ 5 mm. comlete all as specified and directed.
M&L in replacement fire mild steel fire bucket confirming to IS 2546-1974, body made out of minimum 1 mm. Thickness, of capacity min 10 ltr and bucket is duly painted and marked as per fire standard complete all as specified and directed.
M&L for fabricating outdoor fire bucket stand made out off 50mm x 50mm x 6mm angle iron and MS sheet top roof made out of mimimum 3mm thickness for hanging 04 Nos of fire bucket and extingusher with proper foundation and placing the stand whenever specified by engineer -in-charge. including necessary welding ,cutting etc.and painting with post box red color comlete all as specified and directed
stage.html
html • 0.02 MB
tech_bid_open.pdf
tech_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.49 MB
BOQ_847566.xls
BOQ • 6.68 MB
Particularspecifications.pdf
Additional Documents • 0.58 MB
Indepageandfwdingpage.pdf
Tender Documents • 0.65 MB
Makes.pdf
Additional Documents • 0.54 MB
Specialcondition.pdf
Additional Documents • 0.49 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .