Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹35.1 LAccepted-AOC 154 GANDHI MARKET AMBALA CANTT HARYANA 133001 | AMBALA CANTT | AMBALA | HARYANA | 133001 | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹39.3 L+₹2.3 L (6.24%)Rejected-Finance 186 GANDHI MARKET AMBALA CANTT 133001 | AMBALA CANTT | AMBALA | HARYANA | 133001 | L2 | Rejected-Finance Being not lowest | |
| 3 | L3₹43.4 L+₹6.4 L (17.3%)Rejected-Finance 5021 1 CAT III MODERN HOUSING COMPLEX MANIMAJRA CHANDIGARH | CHANDIGARH | CHANDIGARH | 160001 | L3 | Rejected-Finance Being not lowest | |
| 4 | L4₹44.4 L+₹7.4 L (20.1%)Rejected-Finance 1170 BENGALI MOHALLA NEAR PRABHAKAR HOSPITAL AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | L4 | Rejected-Finance Being not lowest | |
| 5 | L5₹44.7 L+₹7.6 L (20.6%)Rejected-Finance | L5 | Rejected-Finance Being not lowest |
Tender Value
Refer Docs
EMD Value
₹97,500
Closing Date
2 Feb 2023, 6:00 pmClosed
Capt Arvind Kumar
GE (P) Dappar
Special Repairs to LT distribution at Mag No. 4 to 13 and NM No 5 to 12 in depot area at Mil Stn Dappar under GE (P) Dappar
2023_MES_573610_1
GE (P) DPR-42/2022-23
Open Tender
Civil Works
Works
180 days
GE (P) Dappar
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE (P) Dappar
₹97,500
Yes
9 Jul 2023
7 Jan 2023
4 Feb 2023
7 Jan 2023
2 Feb 2023
20 Jan 2023
7 Jan 2023 - 20 Jan 2023
Amount
Taking down unserviceable poles of steel/PCC complete all as specified and directed.
Dismantling acessories of MS channel or angle etc complete.
Dismantling insulators any type/ size.
Dismantling stay assembly complete (dimolition of concrete etc).
Dismantling earth wire conductor, service feeder or distribution span.
Dismantling of ACSR conductor any size.
Taking down old unserviceable cables of any size.
Dismantling GI pipe off any size complete.
M&L for dismantling old unserviceable LT panel along with disconnecting connected cables, supplying, installing, testing and commissioning of 415Volts 3Phase 4 Wire factory fabricated and tested all as per existing IEC 60439 Part 1, floor mounted, IP 55 grade, Outdoor double door LT cubical panel made out of CRCA MS sheet duly powder coated with Seimens grey shade RAL 7032, dust and veremin proof with suitable size TPN PVC sleeved aluminium bus bar incld. angle iron base frame of suitable size. Panel should be mounted/grouted on 150 mm thick PCC (1:4:8) type D2 below nearest greound level and should be with 400 mm offsets on all 04 sides of the panel complete and should be inclusive of following fitted in accessories :-
(i) MCCB 4 pole 35 kA 250 Amp with Ics =100% Icu & thermal magnetic adjustable type all as per L&T or equivalent including spreader terminals - set of 04 and direct rotary handle -01 No, Current transfomer 250/5A -01 Nos,Shunt Release as per OEM specifications and model or equivalent in legrand/ABB/Schenider/L&T - 01 No (For incoming).
(ii) MCCB 4 pole 25 kA 100 Amp with Ics =100% Icu & thermal magnetic adjustable type all as per L&T or equivalent including spreader terminals - set of 04 and direct rotary handle -02 No, Current transfomer 100/5A -02 Nos,Shunt Release as per OEM specifications and model or equivalent in legrand/ABB/Schenider/L&T- 02 Nos . ( For LT Panel No.1 and 3)
(iii) MCCB 4 pole 25 kA 63 Amp with Ics =100% Icu & thermal magnetic adjustable type all as per L&T or equivalent including spreader terminals - set of 04 and direct rotary handle -02 No, Current transfomer 100/5A -02 Nos,Shunt Release as per OEM specifications and model or equivalent in legrand/ABB/Schenider/L&T- 02 Nos.
(iv) MCB TPN 63 Amp - 02 Nos
(v) Internal wiring with PVC insulated, multi stranded copper conductor cable, 1100 V grade, IS 694 marked of appropriate size but not less than 2.5 sqmm. (vi ) Digital Voltmeter & Ammeter with necessary CT's.-01 No per incoming MCCB Make : AE/Conserve/Rishabh (vii) Spare chambers for future extension of MCCBs as per requirement - 01 spare compt. (viii) Phase indiacting lamps (R-Y-B) - 01 set of 3 nos per incoming & outgoing.
M&L for dismantling old unserviceable LT panel along with disconnecting connected cables, supplying, installing, testing and commissioning of 415Volts 3Phase 4 Wire factory fabricated and tested all as per existing IEC 60439 Part 1, floor mounted, IP 55 grade, Outdoor double door LT cubical panel made out of CRCA MS sheet duly powder coated with Seimens grey shade RAL 7032, dust and veremin proof with suitable size TPN PVC sleeved aluminium bus bar incld. angle iron base frame of suitable size. Panel should be mounted/grouted on 150 mm thick PCC (1:4:8) type D2 below nearest greound level and should be with 400 mm offsets on all 04 sides of the panel complete and should be inclusive of following fitted in accessories :-
(i) MCCB 4 pole 25 kA 100 Amp with Ics =100% Icu & thermal magnetic adjustable type all as per L&T or equivalent including spreader terminals - set of 04 and direct rotary handle -01 No, Current transfomer 100/5A -01 Nos,Shunt Release as per OEM specifications and model or equivalent in legrand/ABB/Schenider/L&T - 01 No (For incoming).
(ii) MCCB 4 pole 25 kA 63 Amp with Ics =100% Icu & thermal magnetic adjustable type all as per L&T or equivalent including spreader terminals - set of 04 and direct rotary handle -02 No, Current transfomer 100/5A -01 Nos,Shunt Release as per OEM specifications and model or equivalent in legrand/ABB/Schenider/L&T- 01 Nos.
(iii) MCB TPN 63 Amp - 05 Nos
(iv) Internal wiring with PVC insulated, multi stranded copper conductor cable, 1100 V grade, IS 694 marked of appropriate size but not less than 2.5 sqmm. (v ) Digital Voltmeter & Ammeter with necessary CT's.-01 No. per incoming MCCB Make : AE/Conserve/Rishabh (vi) Spare chambers for future extension of MCCBs as per requirement - 01 spare compt. (vii) Phase indiacting lamps (R-Y-B) - 01 set.of 03 Nos per incoming & outgoing
M&L for dismantling old unserviceable LT panel along with disconnecting connected cables, supplying, installing, testing and commissioning of 415Volts 3Phase 4 Wire factory fabricated and tested all as per existing IEC 60439 Part 1, floor mounted, IP 55 grade, Outdoor double door LT cubical panel made out of CRCA MS sheet duly powder coated with Seimens grey shade RAL 7032, dust and veremin proof with suitable size TPN PVC sleeved aluminium bus bar incld. angle iron base frame of suitable size. Panel should be mounted/grouted on 150 mm thick PCC (1:4:8) type D2 below nearest greound level and should be with 400 mm offsets on all 04 sides of the panel complete and should be inclusive of following fitted in accessories :-
(i) MCCB 4 pole 25 kA 100 Amp with Ics =100% Icu & thermal magnetic adjustable type all as per L&T or equivalent including spreader terminals - set of 04 and direct rotary handle -01 No, Current transfomer 100/5A -01 Nos,Shunt Release as per OEM specifications and model or equivalent in legrand/ABB/Schenider/L&T - 01 No (For incoming).
(ii) MCCB 4 pole 25 kA 63 Amp with Ics =100% Icu & thermal magnetic adjustable type all as per L&T or equivalent including spreader terminals - set of 04 and direct rotary handle -01 No, Current transfomer 100/5A -01 Nos,Shunt Release as per OEM specifications and model or equivalent in legrand/ABB/Schenider/L&T- 01 No.
(iii) MCB TPN 63 Amp - 03 Nos
(iv) Internal wiring with PVC insulated, multi stranded copper conductor cable, 1100 V grade, IS 694 marked of appropriate size but not less than 2.5 sqmm. (v ) Digital Voltmeter & Ammeter with necessary CT's.- 01 No per incoming MCCB Make : AE/Conserve/Rishabh (vi) Spare chambers for future extension of MCCBs as per requirement - 01 spare compt. (vii) Phase indiacting lamps (R-Y-B) - 01 set of 03 Nos per incoming & outgoing.
M&L for dismantling old unserviceable LT panel along with disconnecting connected cables, supplying, installing, testing and commissioning of 415Volts 3Phase 4 Wire factory fabricated and tested all as per existing IEC 60439 Part 1, floor mounted, IP 55 grade, Outdoor double door LT cubical panel made out of CRCA MS sheet duly powder coated with Seimens grey shade RAL 7032, dust and veremin proof with suitable size TPN PVC sleeved aluminium bus bar incld. angle iron base frame of suitable size. Panel should be mounted/grouted on 150 mm thick PCC (1:4:8) type D2 below nearest greound level and should be with 400 mm offsets on all 04 sides of the panel complete and should be inclusive of following fitted in accessories :-
(i) MCCB 4 pole 25 kA 63 Amp with Ics =100% Icu & thermal magnetic adjustable type all as per L&T or equivalent including spreader terminals - set of 04 and direct rotary handle -01 No, Current transfomer 100/5A -01 Nos,Shunt Release as per OEM specifications and model or equivalent in legrand/ABB/Schenider/L&T - 01 No (For incoming).
(ii) MCB TPN 63 Amp - 05 Nos
(iii) Internal wiring with PVC insulated, multi stranded copper conductor cable, 1100 V grade, IS 694 marked of appropriate size but not less than 2.5 sqmm. (iv ) Digital Voltmeter & Ammeter with necessary CT's - 01 No. per incoming MCCB .Make : AE/Conserve/Rishabh (v) Spare chambers for future extension of MCCBs as per requirement - 01 spare compt. (vi) Phase indiacting lamps (R-Y-B) - 01 set of 03 Nos per incoming & outgoing.
M&L for dismantling old unserviceable LT panel along with disconnecting connected cables, supplying, installing, testing and commissioning of 415Volts 3Phase 4 Wire factory fabricated and tested all as per existing IEC 60439 Part 1, floor mounted, IP 55 grade, Outdoor double door LT cubical panel made out of CRCA MS sheet duly powder coated with Seimens grey shade RAL 7032, dust and veremin proof with suitable size TPN PVC sleeved aluminium bus bar incld. angle iron base frame of suitable size. Panel should be mounted/grouted on 150 mm thick PCC (1:4:8) type D2 below nearest greound level and should be with 400 mm offsets on all 04 sides of the panel complete and should be inclusive of following fitted in accessories :-
(i) MCCB 4 pole 35 kA 250 Amp with Ics =100% Icu & thermal magnetic adjustable type all as per L&T or equivalent including spreader terminals - set of 04 and direct rotary handle -01 No, Current transfomer 250/5A -01 Nos,Shunt Release as per OEM specifications and model or equivalent in legrand/ABB/Schenider/L&T - 01 No (For incoming).
(ii) MCCB 4 pole 25 kA 200 Amp with Ics =100% Icu & thermal magnetic adjustable type all as per L&T or equivalent including spreader terminals - set of 04 and direct rotary handle -01 No, Current transfomer 200/5A -01 Nos,Shunt Release as per OEM specifications and model or equivalent in legrand/ABB/Schenider/L&T- 01 Nos . ( For Prop LT Panel)
(iii) MCCB 4 pole 25 kA 63 Amp with Ics =100% Icu & thermal magnetic adjustable type all as per L&T or equivalent including spreader terminals - set of 04 and direct rotary handle -02 No, Current transfomer 100/5A -01 Nos,Shunt Release as per OEM specifications and model or equivalent in legrand/ABB/Schenider/L&T- 02 Nos.
(iv) MCB TPN 63 Amp - 06 Nos
(v) Internal wiring with PVC insulated, multi stranded copper conductor cable, 1100 V grade, IS 694 marked of appropriate size but not less than 2.5 sqmm. (vi ) Digital Voltmeter & Ammeter with necessary CT's.- 01 No. per incoming MCCBMake : AE/Conserve/Rishabh (vii) Spare chambers for future extension of MCCBs as per requirement - 01 spare compt. (viii) Phase indiacting lamps (R-Y-B) - 01 set of 02 Nos per incoming & outgoing.
M&L for dismantling old unserviceable LT panel along with disconnecting connected cables, supplying, installing, testing and commissioning of 415Volts 3Phase 4 Wire factory fabricated and tested all as per existing IEC 60439 Part 1, floor mounted, IP 55 grade, Outdoor double door LT cubical panel made out of CRCA MS sheet duly powder coated with Seimens grey shade RAL 7032, dust and veremin proof with suitable size TPN PVC sleeved aluminium bus bar incld. angle iron base frame of suitable size. Panel should be mounted/grouted on 150 mm thick PCC (1:4:8) type D2 below nearest greound level and should be with 400 mm offsets on all 04 sides of the panel complete and should be inclusive of following fitted in accessories :-
(i) MCCB 4 pole 35 kA 160 Amp with Ics =100% Icu & thermal magnetic adjustable type all as per L&T or equivalent including spreader terminals - set of 04 and direct rotary handle -01 No, Current transfomer 160/5A -01 Nos,Shunt Release as per OEM specifications and model or equivalent in legrand/ABB/Schenider/L&T - 01 No (For incoming).
(ii) MCCB 4 pole 25 kA 63 Amp with Ics =100% Icu & thermal magnetic adjustable type all as per L&T or equivalent including spreader terminals - set of 04 and direct rotary handle -02 No, Current transfomer 100/5A -01 Nos,Shunt Release as per OEM specifications and model or equivalent in legrand/ABB/Schenider/L&T- 04 Nos.
(iii) MCB TPN 63 Amp - 02 Nos
(iv) Internal wiring with PVC insulated, multi stranded copper conductor cable, 1100 V grade, IS 694 marked of appropriate size but not less than 2.5 sqmm. (v ) Digital Voltmeter & Ammeter with necessary CT's.-01 No. per incoming MCCB. Make : AE/Conserve/Rishabh (vi) Spare chambers for future extension of MCCBs as per requirement - 01 spare compt. (vii) Phase indiacting lamps (R-Y-B) - 01 set of 03 Nos per incoming & outgoing.
Excavation in trenches not exc. 1.5 m wide and not exceeding 1.5m depth for foundation of poles/laying of cables/stay/strut etc not exceeding 10 Sq m on plan and getting out in soft/loose soil.
Earth work in excavation by mechanical means (hydraulic excavator)/in foundation trenches or drains (not exceeding 1.5m in width or 10 sqm on plan) in all kind of soil , including dressing of sides and ramming of bottoms,lift upto 1.5m, including getting out the excavated soil and disposal of surplus excavated soil as directed within a lead of 50m all as specified and directed by engr-in-charge.
Returning, filling including spreading, leveling watering and well ramming in layers not exceeding 25 cm as directed.
Removing excavated material (soil) n.exc 50m and depositing where directed at a level not exceeding 1.5 mtr above the starting point
M&L for providing Fazilka river sand as in sand cushioning to under ground cable including punning down of sand in layers as specified and as directed
M&L precast concrete cable cover, class LV, type 1 with peak, size 250mm x 150mm x 40mm.
Make bore to road width for providing GI pipe medium grade both end socketed for passing armoured cable complete all as specified.
M&L for 50 MM bore galvanized steel tubing light garde (ISI marked) protection of cable fixed to pole/walls or laid in floors, road crossing ducts with all necessary fittings and fittings and fixed with clamps, bolts, nuts and washers etc complete all as specified and directed.Make : Tata/Jindal/Surya
M&L for 80 MM bore galvanized steel tubing light garde (ISI marked) protection of cable fixed to pole/walls or laid in floors, road crossing ducts with all necessary fittings and fittings and fixed with clamps, bolts, nuts and washers etc complete all as specified and directed.Make : Tata/Jindal/Surya
M&L for GI pipe light grade 25mm with all fittings fixed in wall or laid in trenches all as specified and directed by engr-in-charge.
Supply and fix XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 25 sqmm 4 core all as specified and directed by engr-in-charge.
Supply and fix XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 35 sqmm 3.5 core all as specified and directed by engr-in-charge.
Supply and fix XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 50 sqmm 3.5 core all as specified and directed by engr-in-charge.
Supply and fix XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 70 sqmm 3.5 core all as specified and directed by engr-in-charge.
Supply and fix XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 95 sqmm 3.5 core all as specified and directed by engr-in-charge.
Supply and fix XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 120 sqmm 3.5 core all as specified and directed by engr-in-charge.
Supply and fix in replacement for earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25 meters deep below normal ground level) with top edge of plate not less than 1.5 meter deep below normal ground level connected to galvanized earth strip of size 25 x 4 mm, 7.5m long means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No 3 of SSR part I connecting to earthing test point and testing on completion with and including PCC pit in mix 1:3:6 type c1 with RCC 1:2:4 type B-1, 40mm thick cover reinforced with 6mm dia MS bars 3 Nos both ways with lifting book made out of 6mm dia bar, watering arrangement with funnel and wire mesh and 20mm bore light grade GI watering pipe, common salt and charcoal filling, necessary excavation and earth work, complete all as directed.
M/S Sonu Traders
M/s APEX ENTERPRISES
The Rahul Vig
kapil engg works
HARISH SALES CORPORATION
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .